Trade Price
£117.44
Per
1
Unit
EA
Pack Quantity
1
Range of produc
C120
Range
Multi9
Product name
C120
Product or component type
Miniature circuit-breaker
Device short name
C120H
Device application
Distribution
Poles description
2P
Number of protected poles
2
Neutral position
Left
[In] rated current
100 A at 30 °C
Network type
AC
Trip unit technology
Thermal-magnetic
Curve code
C
Breaking capacity
15000 A Icn at 230...400 V AC 50/60 Hz conforming to IEC 60898-1 10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 230...400 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at <= 250 V DC conforming to EN/IEC 60947-2
Suitability for isolation
Yes conforming to IEC 60947-2
Network frequency
50/60 Hz
[Ue] rated operational voltage
440 V AC 50/60 Hz 230...400 V AC 50/60 Hz 400...415 V AC 50/60 Hz <= 250 V DC
Magnetic tripping limit
5...10 x In
[Ics] rated service breaking capacity
7500 A 50 % conforming to IEC 60898-1 - 230...400 V AC 50/60 Hz 5 kA 50 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 15 kA 50 % conforming to EN/IEC 60947-2 - 230...400 V AC 50/60 Hz 7.5 kA 50 % conforming to EN/IEC 60947-2 - 400...415 V AC 50/60 Hz 15 kA 100 % conforming to EN/IEC 60947-2 - 250 V DC
Limitation class
3 conforming to IEC 60898-1
Contact position indicator
Yes
control type
Toggle
local signalling
ON/OFF indication
Mounting mode
Clip-on
mounting support
35 mm symmetrical DIN rail
Comb busbar and distribution block compatibility
NO
9 mm pitches
6
height
81 mm
Width
54 mm
Depth
73 mm
Net weight
0.41 kg
Mechanical durability
20000 cycles
Electrical durability
5000 cycles conforming to IEC 60947-2
Connections - terminals
Tunnel type terminals1…50 mm² rigid Tunnel type terminals1.5…35 mm² flexible
Wire stripping length
15 mm
Tightening torque
3.5 N.m
earth-leakage protection
Separate block
Standards
IEC 60898-1 EN/IEC 60947-2
product certifications
GOST
Quality labels
NF
IP degree of protection
IP20 conforming to IEC 60529
Pollution degree
3 conforming to IEC 60947-2
Tropicalisation
2 conforming to IEC 60068-1
Relative humidity
95 % at 55 °C
Operating altitude
2000 m
ambient air temperature for operation
-30…60 °C
Ambient air temperature for storage
-40…70 °C
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
7.5 cm
Package 1 Width
8.5 cm
Package 1 Length
5.5 cm
Package 1 Weight
0.387 kg
Warranty
18 months
Datasheet
Technical Data