48116

NW5000 H2 4P fixed ACB

Trade Price

£50,304.91

Per

1

Unit

EA

Pack Quantity

1

48116

Technical Specifications

Range

MasterPacT

Product name

MasterPact NW

circuit breaker name

MasterPact NW50H2

Product or component type

Circuit breaker

Device application

Power distribution protection

Poles description

4P

Neutral position

Left

Control unit

Without control unit

[In] rated current

5000 A at 40 °C

Performance type

H2 150 kA 440 V AC

[Ue] rated operational voltage

690 V AC 50/60 Hz

Suitability for isolation

Yes conforming to EN/IEC 60947-2

Selectivity category

Category B

Control type

Push-button

Mounting mode

Fixed

[Icu] rated ultimate short-circuit breaking capacity

150 kA at 220/415 V AC 50/60 Hz 150 kA at 440 V AC 50/60 Hz 130 kA at 525 V AC 50/60 Hz 100 kA at 690 V AC 50/60 Hz

[Ics] rated service breaking capacity

150 kA at 220/415 V AC 50/60 Hz 150 kA at 440 V AC 50/60 Hz 130 kA at 525 V AC 50/60 Hz 100 kA at 690 V AC 50/60 Hz

[Icw] rated short-time withstand current

100 kA 1 s 100 kA 3 s

[Icm] rated short-circuit making capacity

330 kA 220/415 V AC at 50/60 Hz 330 kA 440 V AC at 50/60 Hz 286 kA 525 V AC at 50/60 Hz 220 kA 690 V AC at 50/60 Hz

Integrated instantaneous protection (DIN in kA peak)

243…297 kA

Sensor rating

2500 A 5000 A

[Ui] rated insulation voltage

1000 V AC 50/60 Hz

[Uimp] rated impulse withstand voltage

12 kV

Power dissipation in W

660 W

Maximum breaking time

25 ms

maximum closing response time

80 ms

mounting support

Backplate Rails

Upside connection

Rear

downside connection

Rear

Connection pitch

230 mm

Mechanical durability

10000 cycles with maintenance 5000 cycles without maintenance

Electrical durability

1500 cycles 440 V AC 50/60 Hz without maintenance conforming to EN/IEC 60947-2 1500 cycles 690 V AC 50/60 Hz without maintenance conforming to EN/IEC 60947-2 AC-23A: 1500 cycles 440 V AC 50/60 Hz without maintenance conforming to EN/IEC 60947-3 AC-23A: 1500 cycles 690 V AC 50/60 Hz without maintenance conforming to EN/IEC 60947-3 AC-3: 6000 cycles 440/690 V AC 50/60 Hz without maintenance conforming to EN/IEC 60947-3

height

352 mm

Width

997 mm

Depth

297 mm

Net weight

160 kg

standards

EN/IEC 60947-1 EN/IEC 60947-2

product certifications

CE CCC EAC

IP degree of protection

IP30 conforming to IEC 60529

Pollution degree

4 conforming to IEC 60664-1

Ambient air temperature for operation

-25…70 °C

Ambient air temperature for storage

-40…85 °C

Operating altitude

0...2000 m without derating 2000 m...5000 m with derating

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

60.0 cm

Package 1 Width

50.0 cm

Package 1 Length

120.0 cm

Package 1 Weight

145.129 kg

Warranty

18 months

Document Links

Catalogue page

Datasheet