Micrologic 7.0H (Harmonics) is an electronic control unit used on Masterpact NT 06 to 16 and Masterpact NW 08 to 63 fixed circuit breakers. This control unit has a selective and earth-leakage protection (LSIV), and is designed to protect power circuits and loads. It embeds adjustable long time protection against overloads. It provides also adjustable short-time protection and instantaneous protection against short-circuits. Micrologic 7.0H offers an adjustable residual earth leakage protection. Micrologic 7.0H indicates overloads with an Alarm LED. It is able to display the trip cause through 3 others LEDs. Micrologic 7.0H is equipped with a digital LCD screen that displays power measurement and current/voltage harmonics. This control unit can be associated with fixed Masterpact NT and NW basic frame.
Range
MasterPact
Range of product
MasterPact NW MasterPact NT
Product or component type
Control unit
Trip unit name
MicroLogic 7.0 H
Trip unit technology
Electronic
Range compatibility
Masterpact NT06...16 Masterpact NW08...40 Masterpact NW40b...63
Device application
Distribution
Number of poles
3P 4P
Protected poles description
4t 3t 3t + N/2
Trip unit protection functions
Selective + earth-leakage protection
Protection type
for overload protection (long time) for short time short-circuit protection for instantaneous short-circuit protection for earth-leakage protection
Trip unit rating
630 A at 50 °C 800 A at 50 °C 1000 A at 50 °C 1250 A at 50 °C 1600 A at 50 °C 2000 A at 50 °C 2500 A at 50 °C 3200 A at 50 °C 4000 A at 50 °C 5000 A at 50 °C 6300 A at 50 °C
Network type
AC
Network frequency
50/60 Hz
Circuit breaker mounting mode
Fixed
Long-time pick-up adjustment type Ir (thermal protection)
Adjustable 9 settings
[Ir] long-time protection pick-up adjustment range
0.4...1 x In
Long-time protection delay adjustment type tr
Adjustable 9 settings
[tr] long-time protection delay adjustment range
0.7…16.6 s at 7.2 x Ir 0.7…24 s at 6 x Ir 12.5…600 s at 1.5 x Ir
Thermal memory
20 mn
Short-time protection pick-up adjustment type Isd
Adjustable 9 settings
[Isd] Short-time protection pick-up adjustment range
1.5...10 x Ir
Short-time protection delay adjustment type tsd
Adjustable
[tsd] Short-time protection delay adjustment range
0…0.4 s I²t=off 0.1…0.4 s I²t=on
Instantaneous protection pick-up adjustment type Ii
Adjustable 9 settings
[Ii] instantaneous protection pick-up adjustment range
2...15 x In Off
earth-leakage protection
Integrated
Earth-leakage protection sensitity adjustment type IΔn
Adjustable 9 settings
[IΔn] earth-leakage protection sensitivity adjustment range
0.5…30 A
Earth-leakage sensitivity
10 A for class A 30 A for class AC
Earth-leakage protection time delay adjustement type Δt
Adjustable 5 settings
[Δt] Earth-leakage protection time delay adjustment range
60…800 ms
Zone selective interlocking ZSI
With
Local signalling
3 LEDs (red) for electrical fault 1 LED (red) for internal error
Display type
Digital display
Type of measurement
Harmonics meter Power meter
communication of data
Measurement readout Protection and alarm settings Maintenance indicators
Ambient air temperature for operation
-25…70 °C
Ambient air temperature for storage
-40…85 °C
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
8.0 cm
Package 1 Width
6.0 cm
Package 1 Length
20.0 cm
Package 1 Weight
2.091 kg
Warranty
18 months
Datasheet