Trade Price
£4,585.07
Per
1
Unit
EA
Pack Quantity
1
Range
MasterPact
Range of product
MasterPact NT MasterPact NW
Product or component type
Control unit
Trip unit name
MicroLogic 6.0 P
Trip unit technology
Electronic
Range compatibility
Masterpact NT06...16 Masterpact NW08...40 Masterpact NW40b...63
Device application
Distribution
Number of poles
4P 3P
Protected poles description
4t 3t 3t + N/2
Trip unit protection functions
Selective + earth-fault protection
Protection type
for overload protection (long time) for short time short-circuit protection for instantaneous short-circuit protection for earth fault
Trip unit rating
630 A at 50 °C 800 A at 50 °C 1000 A at 50 °C 1250 A at 50 °C 1600 A at 50 °C 2000 A at 50 °C 2500 A at 50 °C 3200 A at 50 °C 4000 A at 50 °C 5000 A at 50 °C 6300 A at 50 °C
Network type
AC
Network frequency
50/60 Hz
Circuit breaker mounting mode
Fixed
Long-time pick-up adjustment type Ir (thermal protection)
Adjustable 9 settings
[Ir] long-time protection pick-up adjustment range
0.4...1 x In
Long-time protection delay adjustment type tr
Adjustable 9 settings
[tr] long-time protection delay adjustment range
0.7…16.6 s at 7.2 x Ir 0.7…24 s at 6 x Ir 12.5…600 s at 1.5 x Ir
Thermal memory
20 mn
Short-time protection pick-up adjustment type Isd
Adjustable 9 settings
[Isd] Short-time protection pick-up adjustment range
1.5...10 x Ir
Short-time protection delay adjustment type tsd
Adjustable
[tsd] Short-time protection delay adjustment range
0…0.4 s I²t=off 0.1…0.4 s I²t=on
Instantaneous protection pick-up adjustment type Ii
Adjustable 9 settings
[Ii] instantaneous protection pick-up adjustment range
Off 2...15 x In
Ground-fault protection pick-up adjustment type Ig
Adjustable 9 settings
[Ig] ground-fault protection pick-up adjustment range
0.2...1 x In for 400 A < In < 1250 A 0.3...1 x In for In <= 400 A 500...1200 A for In >= 1250 A
Ground-fault protection time delay adjustment type tg
Adjustable
[tg] ground-fault protection time delay adjustment range
0…0.4 s I²t=off 0.1…0.4 s I²t=on
earth-leakage protection
Without
Zone selective interlocking ZSI
With
Local signalling
3 LEDs (red) for electrical fault 1 LED (red) for internal error
Display type
Digital display
Type of measurement
Power meter
communication of data
Measurement readout Protection and alarm settings Maintenance indicators
Ambient air temperature for operation
-25…70 °C
Ambient air temperature for storage
-40…85 °C
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
6.7 cm
Package 1 Width
7.9 cm
Package 1 Length
21.5 cm
Package 1 Weight
428.0 g
Warranty
18 months