Trade Price
£5,362.77
Per
1
Unit
EA
Pack Quantity
1
Micrologic 5.0H (Harmonics) is an electronic control unit used on Masterpact NW 08 to 63 drawout circuit breakers. This control unit has a selective protection (LSI) and is designed to protect power circuits and loads. It embeds adjustable long time protection against overloads. It provides also adjustable short-time protection and instantaneous protection against short-circuits. Micrologic 5.0H indicates overloads with an Alarm LED. It is able to display the trip cause through 3 others LEDs. Micrologic 5.0H is equipped with a digital LCD screen that displays power measurement and current/voltage harmonics. This control unit can be associated with drawout Masterpact NW basic frame.
Range
MasterPact
Range of product
MasterPact NW
Product or component type
Control unit
Trip unit name
MicroLogic 5.0 H
Trip unit technology
Electronic
Range compatibility
Masterpact NW08...40 Masterpact NW40b...63 Masterpact NW H10 Masterpact NW H2 corrosion protection
Device application
Distribution
Number of poles
4P 3P
Protected poles description
4t 3t 3t + N/2
Trip unit protection functions
Selective protection
Protection type
for short time short-circuit protection for overload protection (long time) for instantaneous short-circuit protection
Trip unit rating
800 A at 50 °C 1000 A at 50 °C 1250 A at 50 °C 1600 A at 50 °C 2000 A at 50 °C 2500 A at 50 °C 3200 A at 50 °C 4000 A at 50 °C 5000 A at 50 °C 6300 A at 50 °C
Network type
AC
Network frequency
50/60 Hz
Circuit breaker mounting mode
Drawout
Long-time pick-up adjustment type Ir (thermal protection)
Adjustable 9 settings
[Ir] long-time protection pick-up adjustment range
0.4...1 x In
Long-time protection delay adjustment type tr
Adjustable 9 settings
[tr] long-time protection delay adjustment range
0.7…16.6 s at 7.2 x Ir 0.7…24 s at 6 x Ir 12.5…600 s at 1.5 x Ir
Thermal memory
20 mn
Short-time protection pick-up adjustment type Isd
Adjustable 9 settings
[Isd] Short-time protection pick-up adjustment range
1.5...10 x Ir
Short-time protection delay adjustment type tsd
Adjustable
[tsd] Short-time protection delay adjustment range
0…0.4 s I²t=off 0.1…0.4 s I²t=on
Instantaneous protection pick-up adjustment type Ii
Adjustable 9 settings
[Ii] instantaneous protection pick-up adjustment range
2...15 x In Off
earth-leakage protection
Without
Zone selective interlocking ZSI
With
Local signalling
3 LEDs (red) for electrical fault 1 LED (red) for internal error
Display type
Digital display
Type of measurement
Harmonics meter Power meter
communication of data
Measurement readout Protection and alarm settings Maintenance indicators
Ambient air temperature for operation
-25…70 °C
Ambient air temperature for storage
-40…85 °C
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
7.0 cm
Package 1 Width
8.0 cm
Package 1 Length
22.0 cm
Package 1 Weight
1.117 kg
Warranty
18 months