Trade Price
£6,310.25
Per
1
Unit
EA
Pack Quantity
1
Range
MasterPact
Range of product
MasterPact NT
Product or component type
Control unit
Trip unit name
MicroLogic 7.0 H
Trip unit technology
Electronic
Range compatibility
Masterpact NT06...16
Device application
Distribution
Number of poles
4P 3P
Protected poles description
4t 3t 3t + N/2
Trip unit protection functions
Selective + earth-leakage protection
Protection type
for overload protection (long time) for short time short-circuit protection for instantaneous short-circuit protection for earth-leakage protection
Trip unit rating
630 A at 50 °C 800 A at 50 °C 1000 A at 50 °C 1250 A at 50 °C 1600 A at 50 °C
Network type
AC
Network frequency
50/60 Hz
Circuit breaker mounting mode
Drawout
Long-time pick-up adjustment type Ir (thermal protection)
Adjustable 9 settings
[Ir] long-time protection pick-up adjustment range
0.4...1 x In
Long-time protection delay adjustment type tr
Adjustable 9 settings
[tr] long-time protection delay adjustment range
0.7…16.6 s at 7.2 x Ir 0.7…24 s at 6 x Ir 12.5…600 s at 1.5 x Ir
Thermal memory
20 mn
Short-time protection pick-up adjustment type Isd
Adjustable 9 settings
[Isd] Short-time protection pick-up adjustment range
1.5...10 x Ir
Short-time protection delay adjustment type tsd
Adjustable
[tsd] Short-time protection delay adjustment range
0…0.4 s I²t=off 0.1…0.4 s I²t=on
Instantaneous protection pick-up adjustment type Ii
Adjustable 9 settings
[Ii] instantaneous protection pick-up adjustment range
Off 2...15 x In
earth-leakage protection
Integrated
Earth-leakage protection sensitity adjustment type IΔn
Adjustable 9 settings
[IΔn] earth-leakage protection sensitivity adjustment range
0.5…30 A
Earth-leakage sensitivity
10 A for class A 30 A for class AC
Earth-leakage protection time delay adjustement type Δt
Adjustable 5 settings
[Δt] Earth-leakage protection time delay adjustment range
60…800 ms
Zone selective interlocking ZSI
With
Local signalling
3 LEDs (red) for electrical fault 1 LED (red) for internal error
Display type
Digital display
Type of measurement
Harmonics meter Power meter
communication of data
Measurement readout Protection and alarm settings Maintenance indicators
Ambient air temperature for operation
-25…70 °C
Ambient air temperature for storage
-40…85 °C
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
8.0 cm
Package 1 Width
6.0 cm
Package 1 Length
20.0 cm
Package 1 Weight
2.112 kg
Warranty
18 months
Datasheet