Trade Price
£132.10
Per
1
Unit
EA
Pack Quantity
1
This Acti9 iC60 is a modular residual current breaker with overcurrent protection (RCBO). Other RCBO options available Fast installation with click-in busbar The Icn rated short circuit breaking capacity is up to 10000A according IEC 61009-2-2 standard. Its unique Visitrip indicator reduces intervention time by showing the faulty circuit. Its Visisafe green strip guarantees the physical opening of the contacts to allow downstream maintenance. Its fast closing mechanism independent of manual operation improves its service life. This product is compliant with IEC 61009-1 and IEC 61009-2-2 standards. It has an electrical endurance going up to 10000 cycles and a mechanical endurance going up to 20000 cycles. The Ue operational voltage is 150VAC to 230VAC. The Ui rated insulation voltage is 400VAC. The Uimp rated impulse withstand voltage is 4kV. The frequency is 50Hz. It is DIN rail mountable. The width in 9mm pitches is 2. The product color is white (RAL9003). The dimensions are (W) 18mm x (H) 93mm x (D) 70mm. The weight is 136g. It has an IP20 degree of protection. It becomes IP40 once in modular enclosure according to IEC/EN 60529 standard. The operating temperature is from -25°C to 55°C. The storage temperature is from -30°C to 70°C.
circuit breaker application
Distribution
Range
Acti9
Product name
Acti9 iC60 RCBO
Product or component type
Residual current breaker with overcurrent protection (RCBO)
Device short name
iC60N RCBO
Poles description
1P + Ns
[In] rated current
45 A at 30 °C
Curve code
B
Earth-leakage sensitivity
30 mA
Breaking capacity
10000 A Icn at 150...230 V AC 50 Hz
Neutral position
Left
Number of protected poles
1
Network frequency
50 Hz
Network type
AC
Trip unit technology
Thermal-magnetic
[Ue] rated operational voltage
150...230 V AC 50 Hz
Residual current tripping technology
Voltage dependent
earth-leakage protection time delay
Instantaneous
Earth-leakage protection class
Type A
[Icw] rated short-time withstand current
Icw: 250 A during 8/20 µs impulse withstand
Electrical insulation class
Class III
Limitation class
3
[Ui] rated insulation voltage
400 V AC 50 Hz
[Uimp] rated impulse withstand voltage
4 kV
Surge current
250 A
Suitability for isolation
Yes
Contact position indicator
Yes
Control type
Toggle
Local signalling
ON/OFF indication
Mounting mode
Clip-on
mounting support
DIN rail
Comb busbar and distribution block compatibility
YES
9 mm pitches
2
height
117 mm
Width
18 mm
Depth
70 mm
Net weight
136 g
Colour
White
Mechanical durability
20000 cycles
Electrical durability
10000 cycles
Provision for padlocking
Padlockable
Locking options description
By padlocks
Connections - terminals
Screw clamp terminal (upstream) 1…16 mm² rigid Screw clamp terminal (upstream) 1…16 mm² flexible Screw clamp terminal (downstream) 1…10 mm² rigid Screw clamp terminal (downstream) 1…10 mm² flexible
Wire stripping length
14 mm for upstream connection 11 mm for downstream connection
Tightening torque
2 N.m upstream 2 N.m downstream
earth-leakage protection
Integrated
Targeted country
UK
standards
IEC 61009-1 IEC 61009-2-2
product certifications
SNI
IP degree of protection
IP20
Tropicalisation
2
Relative humidity
95 % at 55 °C
Ambient air temperature for operation
-25…55 °C
Ambient air temperature for storage
-30…70 °C
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
3.0 cm
Package 1 Width
11.0 cm
Package 1 Length
14.0 cm
Package 1 Weight
260.0 g
Unit Type of Package 2
S02
Number of Units in Package 2
34
Package 2 Height
15.0 cm
Package 2 Width
30.0 cm
Package 2 Length
40.0 cm
Package 2 Weight
9.061 kg
Unit Type of Package 3
P06
Number of Units in Package 3
544
Package 3 Height
75.0 cm
Package 3 Width
80.0 cm
Package 3 Length
60.0 cm
Package 3 Weight
160.0 kg
Warranty
18 months
Datasheet