FAZ-D50/1N

MCB, 50A, D-type, SP&N, 15kA

Trade Price

£66.99

Per

1

Unit

EACH

Pack Quantity

1

FAZ-D50/1N
FAZ-D50/1N
FAZ-D50/1N
FAZ-D50/1N

Information

Eaton Moeller series xEffect - FAZ MCB. FAZ, 1-pole+N, tripping characteristic: D, rated current In: 50 A, rated switching capacity (IEC/EN 60947-2): 15 kA

Technical Specifications

Product Length/Depth

80 mm

Product Height

75.5 mm

Product Width

36 mm

Product Weight

0.245 kg

Compliances

RoHS conform

Certifications

EN45545-2

IEC 61373

Application

Switchgear for industrial and advanced commercial applications

xEffect - Switchgear for industrial and advanced commercial applications

Number of poles

Single-pole + N

Number of poles (total)

2

Number of poles (protected)

1

Tripping characteristic

D

Release characteristic

D

Amperage Rating

50 A

Type

FAZ

Miniature circuit breaker

Voltage type

AC

Rated operational voltage (Ue) - max

230 V

Rated insulation voltage (Ui)

440 V

Rated impulse withstand voltage (Uimp)

4 kV

Frequency rating - min

50 Hz

Frequency rating - max

60 Hz

Rated switching capacity (IEC/EN 60947-2)

15 kA

Rated short-circuit breaking capacity (EN 60898) at 230 V

10 kA

Rated short-circuit breaking capacity (EN 60898) at 400 V

10 kA

Rated short-circuit breaking capacity (IEC 60947-2) at 230 V

10 kA

Rated short-circuit breaking capacity (IEC 60947-2) at 400 V

10 kA

Overvoltage category

III

Pollution degree

2

Width in number of modular spacings

2

Built-in depth

70.5 mm

Degree of protection

IP20

Connectable conductor cross section (solid-core) - min

1 mm²

Connectable conductor cross section (solid-core) - max

25 mm²

Connectable conductor cross section (multi-wired) - min

1 mm²

Connectable conductor cross section (multi-wired) - max

25 mm²

Rated operational current for specified heat dissipation (In)

50 A

Heat dissipation per pole, current-dependent

0 W

Equipment heat dissipation, current-dependent

4.9 W

Static heat dissipation, non-current-dependent

0 W

Heat dissipation capacity

0 W

Ambient operating temperature - min

-25 °C

Ambient operating temperature - max

75 °C

Current limiting class

3

Features

Concurrently switching N-neutral

Additional equipment possible

Special features

Ambient temperature hint: Starting at 70 °C a 1 °C increase results in a 0.5% linear reduction of current carrying capacity

Used with

FAZ

Miniature circuit breaker

Document Links

Datasheet