DILM225A/22(RAC240)

Contactor, comfort 3pole +2M2B, 110kW

Trade Price

£906.59

Per

1

Unit

EACH

Pack Quantity

1

DILM225A/22(RAC240)
DILM225A/22(RAC240)
DILM225A/22(RAC240)
DILM225A/22(RAC240)

Information

Eaton Moeller® series DILM Contactor, 380 V 400 V 110 kW, 2 N/O, 2 NC, RAC 240: 190 - 240 V 50/60 Hz, AC operation, Screw connection

Technical Specifications

Product Length/Depth

158 mm

Product Height

190 mm

Product Width

140 mm

Product Weight

3.54 kg

Certifications

UL File No.: E29096

UL

VDE 0660

CSA

CSA Class No.: 3211-04

IEC/EN 60947

UL Category Control No.: NLDX

CSA File No.: 2389068

CE

IEC/EN 60947-4-1

CSA-C22.2 No. 60947-4-1-14

UL 60947-4-1

Catalog Notes

Contacts according to EN 50012

Also tested according to AC-3e up to 500 V.

Also suitable for motors with efficiency class IE3.

Accessories

Fitting options auxiliary contacts: on the side: 2 x DILM1000-XHI(V)11-SI; 2 x DILM1000-XHI11-SA

Application

Contactors for Motors

Connection

Screw terminals

Degree of protection

IP00

Electromagnetic compatibility

Designed for operation in industrial environments. Its use in residential environments may cause radio-frequency interference, requiring additional noise suppression.

Fitted with:

Suppressor circuit in actuating electronics

Lifespan, electrical

100,000 Operations (at Condensor operation)

Lifespan, mechanical

10,000,000 Operations (AC operated)

Operating frequency

3000 mechanical Operations/h (AC operated)

200 Operations/h

Overvoltage category

III

Pollution degree

3

Product category

Contactors

Protection

Finger and back-of-hand proof with terminal shroud or terminal block, Protection against direct contact when actuated from front (EN 50274)

Rated impulse withstand voltage (Uimp)

8000 V AC

Shock resistance

10 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms

10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms

8 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms

Utilization category

AC-3: Normal AC induction motors: starting, switch off during running

AC-4: Normal AC induction motors: starting, plugging, reversing, inching

AC-1: Non-inductive or slightly inductive loads, resistance furnaces

Ambient operating temperature - min

-40 °C

Ambient operating temperature - max

60 °C

Ambient operating temperature (enclosed) - min

40 °C

Ambient operating temperature (enclosed) - max

40 °C

Ambient storage temperature - min

40 °C

Ambient storage temperature - max

80 °C

Climatic proofing

Damp heat, constant, to IEC 60068-2-78

Damp heat, cyclic, to IEC 60068-2-30

Terminal capacity (busbar)

32 mm width, Main connection

Terminal capacity (copper band)

Fixing with flat cable terminal or cable terminal blocks; See terminal capacity for cable terminal blocks

Terminal capacity (flexible with cable lug)

50 - 185 mm²

Terminal capacity (flexible with ferrule)

2 x (0.75 - 2.5) mm², Control circuit cables

1 x (0.75 - 2.5) mm², Control circuit cables

Terminal capacity (solid)

2 x (0.75 - 2.5) mm², Control circuit cables

1 x (0.75 - 2.5) mm², Control circuit cables

Terminal capacity (solid/stranded AWG)

18 - 14, Control circuit cables

2/0 - 250 MCM, Main cables

Terminal capacity (stranded with cable lug)

70 - 185 mm²

Width across flats

16 mm

Screw size

M3.5, Terminal screw, Control circuit cables

M10, Terminal screw, Main connections

Screwdriver size

2, Terminal screw, Control circuit cables, Pozidriv screwdriver

Tightening torque

1.2 Nm, Screw terminals, Control circuit cables

24 Nm, Main cable connection screw/bolt

Inrush current

Max. 30 x Ie (peak)

Rated breaking capacity at 220/230 V

2250 A

Rated breaking capacity at 380/400 V

2250 A

Rated breaking capacity at 500 V

2250 A

Rated breaking capacity at 660/690 V

2250 A

Rated breaking capacity at 1000 V

760 A

Rated insulation voltage (Ui)

1000 V

Rated making capacity (cos phi to IEC/EN 60947)

2700 A

Rated operational current (Ie)

220 A at up to 525 V (Individual compensation, three-phase capacitors, open)

133 A at 690 V (Individual compensation, three-phase capacitors, open)

Rated operational current (Ie) at AC-1, 380 V, 400 V, 415 V

356 A

Rated operational current (Ie) at AC-3, 220 V, 230 V, 240 V

225 A

Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V

225 A

Rated operational current (Ie) at AC-3, 440 V

225 A

Rated operational current (Ie) at AC-3, 500 V

225 A

Rated operational current (Ie) at AC-3, 660 V, 690 V

160 A

Rated operational current (Ie) at AC-3, 1000 V

76 A

Rated operational current (Ie) at AC-4, 220 V, 230 V, 240 V

164 A

Rated operational current (Ie) at AC-4, 440 V

164 A

Rated operational current (Ie) at AC-4, 500 V

164 A

Rated operational current (Ie) at AC-4, 660 V, 690 V

120 A

Rated operational current (Ie) at AC-4, 1000 V

55 A

Rated operational power at AC-3, 240 V, 50 Hz

75 kW

Rated operational power at AC-3, 380/400 V, 50 Hz

110 kW

Rated operational power at AC-3, 415 V, 50 Hz

132 kW

Rated operational power at AC-3, 1000 V, 50 Hz

108 kW

Rated operational power at AC-4, 220/230 V, 50 Hz

51 kW

Rated operational power at AC-4, 240 V, 50 Hz

54 kW

Rated operational power at AC-4, 415 V, 50 Hz

96 kW

Rated operational power at AC-4, 440 V, 50 Hz

102 kW

Rated operational power at AC-4, 500 V, 50 Hz

116 kW

Rated operational power at AC-4, 660/690 V, 50 Hz

110 kW

Rated operational voltage (Ue) at AC - max

1000 V

Rated operational power at AC-4, 1000 V, 50 Hz

77 kW

Safe isolation

1000 V AC, Between coil and contacts, According to EN 61140

Special purpose rating of definite purpose rating

336 A, FLA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)

1680 A, LRA 600 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)

2016 A, LRA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)

280 A, FLA 600 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)

Short-circuit current rating (basic rating)

700 A, max. Fuse, SCCR (UL/CSA)

600 A, max. CB, SCCR (UL/CSA)

10 kA, SCCR (UL/CSA)

Short-circuit current rating (high fault at 480 V)

600 A, Class J, max. Fuse, SCCR (UL/CSA)

65 kA, CB, SCCR (UL/CSA)

350 A, max. CB, SCCR (UL/CSA)

100 kA, Fuse, SCCR (UL/CSA)

Short-circuit current rating (high fault at 600 V)

50 kA, CB, SCCR (UL/CSA)

350 A, max. CB, SCCR (UL/CSA)

600 A, Class J, max. Fuse, SCCR (UL/CSA)

100 kA, Fuse, SCCR (UL/CSA)

Short-circuit protection rating (type 1 coordination) at 1000 V

200 A gG/gL

Short-circuit protection rating (type 1 coordination) at 400 V

400 A gG/gL

Short-circuit protection rating (type 1 coordination) at 690 V

315 A gG/gL

Short-circuit protection rating (type 2 coordination) at 1000 V

160 A gG/gL

Short-circuit protection rating (type 2 coordination) at 400 V

315 A gG/gL

Short-circuit protection rating (type 2 coordination) at 690 V

250 A gG/gL

Conventional thermal current ith (1-pole, enclosed)

688 A

Conventional thermal current ith (3-pole, enclosed)

275 A

Conventional thermal current ith at 55°C (3-pole, open)

329 A

Conventional thermal current ith of main contacts (1-pole, open)

788 A

Switching capacity (main contacts, general use)

250 A, Maximum motor rating (UL/CSA)

Switching capacity (auxiliary contacts, general use)

15 A, 600 V AC, (UL/CSA)

1 A, 250 V DC, (UL/CSA)

Switching capacity (auxiliary contacts, pilot duty)

A600, AC operated (UL/CSA)

P300, DC operated (UL/CSA)

Drop-out voltage

AC operated: 0.25 x US max - 0.6 x US min, AC operated

AC operated: 0.2 x US max - 0.4 x US min, AC operated

Duty factor

100 %

Pick-up voltage

0.8 - 1.15 V AC x Us

Power consumption

110 kW

Power consumption, pick-up, 50 Hz

180 W, Pull-in power, Coil in a cold state and 1.0 x Us

210 VA, Pull-in power, Coil in a cold state and 1.0 x Us

Power consumption, pick-up, 60 Hz

180 W, Pull-in power, Coil in a cold state and 1.0 x Us

210 VA, Pull-in power, Coil in a cold state and 1.0 x Us

Power consumption, sealing, 50 Hz

2.6 VA, Coil in a cold state and 1.0 x Us

2.1 W, Coil in a cold state and 1.0 x Us

Power consumption, sealing, 60 Hz

2.1 W, Coil in a cold state and 1.0 x Us

2.6 VA, Coil in a cold state and 1.0 x Us

Rated control supply voltage (Us) at AC, 50 Hz - min

190 V

Rated control supply voltage (Us) at AC, 50 Hz - max

240 V

Rated control supply voltage (Us) at AC, 60 Hz - min

190 V

Rated control supply voltage (Us) at AC, 60 Hz - max

240 V

Rated control supply voltage (Us) at DC - min

0 V

Rated control supply voltage (Us) at DC - max

0 V

Switching time (AC operated, make contacts, closing delay) - max

60 ms

Switching time (AC operated, make contacts, opening delay) - max

40 ms

Assigned motor power at 200/208 V, 60 Hz, 3-phase

60 HP

Assigned motor power at 230/240 V, 60 Hz, 3-phase

75 HP

Assigned motor power at 460/480 V, 60 Hz, 3-phase

150 HP

Assigned motor power at 575/600 V, 60 Hz, 3-phase

200 HP

Number of auxiliary contacts (normally closed contacts)

2

Number of auxiliary contacts (normally open contacts)

2

Number of contacts (normally closed contacts)

2

Number of contacts (normally open contacts)

2

Equipment heat dissipation, current-dependent Pvid

0 W

Heat dissipation capacity Pdiss

0 W

Heat dissipation per pole, current-dependent Pvid

7.67 W

Rated operational current for specified heat dissipation (In)

225 A

Static heat dissipation, non-current-dependent Pvs

2.1 W

10.2.2 Corrosion resistance

Meets the product standard's requirements.

10.2.3.1 Verification of thermal stability of enclosures

Meets the product standard's requirements.

10.2.3.2 Verification of resistance of insulating materials to normal heat

Meets the product standard's requirements.

10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects

Meets the product standard's requirements.

10.2.4 Resistance to ultra-violet (UV) radiation

Meets the product standard's requirements.

10.2.5 Lifting

Does not apply, since the entire switchgear needs to be evaluated.

10.2.6 Mechanical impact

Does not apply, since the entire switchgear needs to be evaluated.

10.2.7 Inscriptions

Meets the product standard's requirements.

10.3 Degree of protection of assemblies

Does not apply, since the entire switchgear needs to be evaluated.

10.4 Clearances and creepage distances

Meets the product standard's requirements.

10.5 Protection against electric shock

Does not apply, since the entire switchgear needs to be evaluated.

10.6 Incorporation of switching devices and components

Does not apply, since the entire switchgear needs to be evaluated.

10.7 Internal electrical circuits and connections

Is the panel builder's responsibility.

10.8 Connections for external conductors

Is the panel builder's responsibility.

10.9.2 Power-frequency electric strength

Is the panel builder's responsibility.

10.9.3 Impulse withstand voltage

Is the panel builder's responsibility.

10.9.4 Testing of enclosures made of insulating material

Is the panel builder's responsibility.

10.10 Temperature rise

The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.

10.11 Short-circuit rating

Is the panel builder's responsibility. The specifications for the switchgear must be observed.

10.12 Electromagnetic compatibility

Is the panel builder's responsibility. The specifications for the switchgear must be observed.

10.13 Mechanical function

The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Document Links

Datasheet