Trade Price
£6,372.26
Per
1
Unit
EA
Pack Quantity
1
MOVING PART FOR C.BREAKER SWITCH-DISCONNECTOR SACE EMAX2 E2.2H/MS 1250 FOUR-POLE
ABB EcoSolutions
Yes
Circular Design Principles Recyclability Rate
Design for Closing Resource Loops - Standard EN45555 - 79.1 %
Group Waste to Landfill Target
UL 2799 Zero Waste To Landfill Validation available
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Order Code US and Canada
ZBHR00A00000000000XX
EAN
8015644773809
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
407 mm
Product Net Height
425 mm
Product Net Depth / Length
383 mm
Product Net Weight
55 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
515 mm
Package Level 1 Height
610 mm
Package Level 1 Depth / Length
615 mm
Package Level 1 Gross Weight
60 kg
Package Level 1 EAN
8015644773809
Current Type
AC
Electrical Durability
Ue =< 440 V 15000 cycleUe = 500 ... 690 V 15000 cycle30 cycles per hour
Mechanical Durability
25000 cycle60 cycles per hour
Neutral Pole Current ([%Iu])
100 %
Number of Poles
4
Power Loss
176 W
Product Main Type
SACE Emax 2
Product Name
Switch Disconnector
Product Type
Switch Disconnector
Rated Current (In)
1250 A
Rated Voltage (Ur)
690 V
Rated Impulse Withstand Voltage (Uimp)
12 kV
Rated Insulation Voltage (Ui)
AC 1000 V
Rated Operational Voltage
690 V AC
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 85 kAfor 3 s 66 kA
Rated Uninterrupted Current (Iu)
1250 A
Short-Circuit Performance Level
H
Standards
IEC
Sub-type
E2.2
Version
W
ETIM 7
EC000216 - Switch disconnector
ETIM 8
EC000216 - Switch disconnector
ETIM 9
EC000216 - Switch disconnector (low voltage)
IDEA Granular Category Code (IGCC)
5293 >> Switch disconnector
Object Classification Code
Q
UNSPSC
39122233
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27371403