Information

MOVING PART FOR C.BREAKER SACE EMAX2 E6.2X 6300 THREE-POLE WITH SOLID-STATE RELEASE IN AC EKIP/DIP-LI R 6300 FITTED WITH: 4 AUXILIARY CONTACT AND C.BREAKER IN POSITION OPEN-CLOSED

Technical Specifications

ABB EcoSolutions

Yes

Circular Design Principles Recyclability Rate

Design for Closing Resource Loops - Standard EN45555 - 77 %

Group Waste to Landfill Target

UL 2799 Zero Waste To Landfill Validation available

RoHS Status

Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019

SCIP

705d9e32-6673-4987-b0e6-cd136a410f57 Italy (IT)

Simplified SCIP

93d67595-de07-4606-b4b3-ff17accd84dc Portugal (PT)b7ea1698-b3a6-428e-b638-58e2020ad3c6 Czech Republic (CZ)ae7fbb19-754b-49b7-83ee-0e3ba18190a7 Poland (PL)d8f676f1-bef8-400b-aad0-ca8ae089e0c1 Poland (PL)3b80fb75-d2ff-46e5-8d0b-a68d5440bdb1 Bulgaria (BG)7417565a-69fe-489a-a077-6af36e901f6e Hungary (HU)4ebbbd2a-15eb-4823-ab51-8c7553fbd0f4 Spain (ES)b1818283-a40b-4a4e-9dd6-2fc73d79f0a5 Belgium (BE)f5f45c91-4433-4d1c-9b2b-fe75b3bae814 France (FR)e6bf070f-c268-428a-8ad1-2f72ce0d05a2 Netherlands (NL)387a1c0e-64c0-4012-8142-71800e646c8f Hungary (HU)16c183ab-b905-4845-8a4c-99ce48c6910c Norway (NO)89d3c287-d010-42a1-abf1-77dba9f884f6 Poland (PL)d3babbff-7e7d-4e7c-944b-a4af88044bf7 France (FR)7695fd48-8b5c-41e7-9441-c62d77e49b3e Croatia (HR)246087ba-948d-473f-9871-71bcf8832ae0 Germany (DE)5d8b64e2-18ea-445a-ac1c-ebfdb159b311 Germany (DE)6477407a-8734-463b-b71f-02caed432b82 Germany (DE)2c4c7487-7e5b-4b32-9fb2-3d7892b1f901 Denmark (DK)d1e912fc-ef63-4185-a7ca-5836668f5099 Germany (DE)683faade-43d3-464b-81dc-67e5857251e3 Belgium (BE)c3cf97e7-ac4f-4187-b128-b935b6c82ede Sweden (SE)697f908f-45d8-447f-af71-d11f085454d3 Finland (FI)f0928dd8-649a-44e2-b521-f12cc760f771 Greece (GR)cdd7bad3-5dc3-4077-b246-5a144a7e5f35 Estonia (EE)555805eb-ad84-4703-91ad-77a49b6f0b2c Sweden (SE)

EAN

8015644765118

Minimum Order Quantity

1 piece

Customs Tariff Number

85362090

Product Net Width

803 mm

Product Net Height

425 mm

Product Net Depth / Length

383 mm

Product Net Weight

120 kg

Package Level 1 Units

box 1 piece

Package Level 1 Width

515 mm

Package Level 1 Height

610 mm

Package Level 1 Depth / Length

1000 mm

Package Level 1 Gross Weight

129 kg

Package Level 1 EAN

8015644765118

Current Type

AC

Electrical Durability

Ue =< 440 V 2000 cycleUe = 500 ... 690 V 2000 cycle10 cycles per hour

Mechanical Durability

12000 cycle60 cycles per hour

Number of Poles

3

Power Loss

1550 W

Product Main Type

SACE Emax 2

Product Name

Air Circuit Breaker

Product Type

Air Circuit Breaker

Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics)

100 %

Rated Current (In)

6300 A

Rated Voltage (Ur)

690 V

Rated Impulse Withstand Voltage (Uimp)

acc. to IEC 60947-2 12 kV

Rated Insulation Voltage (Ui)

AC 1000 V

Rated Operational Voltage

690 V AC

Rated Service Short-Circuit Breaking Capacity (Ics)

(220 V AC) 200 kA(230 V AC) 200 kA(380 V AC) 200 kA(400 V AC) 200 kA(415 V AC) 200 kA(440 V AC) 200 kA(500 V AC) 130 kA(660 V AC) 120 kA(690 V AC) 120 kA

Rated Short-time Withstand Current Low Voltage (Icw)

for 1 s 120 kAfor 3 s 100 kA

Rated Ultimate Short-Circuit Breaking Capacity (Icu)

(440 V AC) 200 kA

Rated Uninterrupted Current (Iu)

6300 A

Release

Ekip Dip LI

Release Type

EL

Short-Circuit Performance Level

X

Standards

IEC

Sub-type

E6.2

Version

W

ETIM 7

EC000228 - Power circuit-breaker for trafo/generator/installation protection

ETIM 8

EC000228 - Power circuit-breaker for trafo/generator/installation protection

ETIM 9

EC000228 - Power circuit-breaker for trafo/generator/installation protection

Object Classification Code

Q

WEEE Category

4. Large Equipment (Any External Dimension More Than 50 cm)

eClass

V11.1 : 27370409

Document Links

Catalogue page

Datasheet