1SDA071294R1

E6.2H 6300 Ekip Touch LI 3p FHR

Trade Price

£38,315.50

Per

1

Unit

EA

Pack Quantity

1

1SDA071294R1

Information

C.BREAKER SACE EMAX2 E6.2H 6300 FIXED THREE-POLE WITH TERMINALS REAR HORIZONTAL AND SOLID-STATE RELEASE IN AC EKIP/TOUCH-LI R 6300 FITTED WITH: 4 AUXILIARY CONTACT AND C.BREAKER IN POSITION OPEN-CLOSED

Technical Specifications

ABB EcoSolutions

Yes

Circular Design Principles Recyclability Rate

Design for Closing Resource Loops - Standard EN45555 - 77 %

Group Waste to Landfill Target

UL 2799 Zero Waste To Landfill Validation available

RoHS Status

Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019

SCIP

cc3bd6d1-3114-4929-9498-ad2ae77b9b5e Italy (IT)

Simplified SCIP

fd746f3c-d41d-4315-84f5-416f2d3b9084 Germany (DE)2b462966-444f-42d8-9fcb-1a4bc4a5d9a3 Germany (DE)f3e7d6dd-c1fd-4b31-821d-01e2e02cb40f Hungary (HU)9232bfa3-36ca-4d37-b717-ede253ee5c49 Portugal (PT)1d0b068a-8583-4f86-bdf1-1cc6903e6da3 Sweden (SE)5881c944-ea0a-4f2b-a476-56819f91002c Poland (PL)c6b2c573-dbd9-4ec9-8c8a-ff7b7afa146f Poland (PL)bfb0b4dc-f835-41ed-89a3-7e13a457d3ed Czech Republic (CZ)13060fd3-3417-4be7-9f75-dc2837866a9f Belgium (BE)a2d51d96-abd9-475e-b158-80ff60d1c558 Spain (ES)976ceba1-efad-4508-a65b-20a5ac38e70a France (FR)5c9eb462-fab8-44ae-badb-187681e9f0ff Poland (PL)75cf90c0-2b12-4c2f-9ae6-bec93b6a6af5 Norway (NO)55245274-c60c-4a51-ad21-a6b7da341d5e Hungary (HU)f4d5b993-02ae-475f-bc00-ab1f7a25d3fb Belgium (BE)8581d7c0-89a5-455b-9b1c-fcac617c178f Sweden (SE)aa29d88b-1496-46b8-80c1-11b7c0960b0e Estonia (EE)4d5299a9-ab2d-4fb7-a6a4-ad6645d989a5 Netherlands (NL)ae10de5a-093d-47e7-8961-d87c394fa68b France (FR)08a81759-193a-4767-917b-17303b3b6efb Greece (GR)a1f532ad-2a4c-49f1-9312-fd7e823dc2d3 Finland (FI)6fc91444-07d6-4bad-b0f1-863da86f9b9b Germany (DE)c0d87f7c-7b07-4715-a5e5-40c7903f1882 Croatia (HR)13fd5ae4-c434-4450-a0a4-d93ddf34faeb Germany (DE)efee113d-3b11-4132-a8b9-81d03f23d168 Bulgaria (BG)01927ec6-3c44-4481-a716-24611bc77a6a Denmark (DK)

Order Code US and Canada

Z6HYETBD000A000000XX

EAN

8015644751449

Minimum Order Quantity

1 piece

Customs Tariff Number

85362090

Product Net Width

762 mm

Product Net Height

371 mm

Product Net Depth / Length

270 mm

Product Net Weight

109 kg

Package Level 1 Units

box 1 piece

Package Level 1 Width

515 mm

Package Level 1 Height

610 mm

Package Level 1 Depth / Length

1000 mm

Package Level 1 Gross Weight

118 kg

Package Level 1 EAN

8015644751449

Current Type

AC

Electrical Durability

Ue =< 440 V 2000 cycleUe = 500 ... 690 V 2000 cycle10 cycles per hour

Mechanical Durability

12000 cycle60 cycles per hour

Number of Poles

3

Power Loss

767 W

Product Main Type

SACE Emax 2

Product Name

Air Circuit Breaker

Product Type

Air Circuit Breaker

Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics)

100 %

Rated Current (In)

6300 A

Rated Voltage (Ur)

690 V

Rated Impulse Withstand Voltage (Uimp)

acc. to IEC 60947-2 12 kV

Rated Insulation Voltage (Ui)

AC 1000 V

Rated Operational Voltage

690 V AC

Rated Service Short-Circuit Breaking Capacity (Ics)

(220 V AC) 100 kA(230 V AC) 100 kA(380 V AC) 100 kA(400 V AC) 100 kA(415 V AC) 100 kA(440 V AC) 100 kA(500 V AC) 100 kA(660 V AC) 100 kA(690 V AC) 100 kA

Rated Short-time Withstand Current Low Voltage (Icw)

for 1 s 100 kAfor 3 s 100 kA

Rated Ultimate Short-Circuit Breaking Capacity (Icu)

(400 V AC) 100 kA(415 V AC) 100 kA(440 V AC) 100 kA(500 V AC) 100 kA(525 V AC) 100 kA(690 V AC) 100 kA

Rated Uninterrupted Current (Iu)

6300 A

Recommended Screw Driver

Main Circuit M12

Release

Ekip Touch LI

Release Type

EL

Short-Circuit Performance Level

H

Standards

IEC

Sub-type

E6.2

Terminal Connection Type

Rear flat Horizontal

Terminal Type

Bolt

Tightening Torque

70 N·m

Version

F

ETIM 7

EC000228 - Power circuit-breaker for trafo/generator/installation protection

ETIM 8

EC000228 - Power circuit-breaker for trafo/generator/installation protection

ETIM 9

EC000228 - Power circuit-breaker for trafo/generator/installation protection

IDEA Granular Category Code (IGCC)

4926 >> Air circuit breakers

Object Classification Code

Q

UNSPSC

39121615

WEEE Category

4. Large Equipment (Any External Dimension More Than 50 cm)

eClass

V11.1 : 27370409

Document Links

Catalogue page