1SDA071221R1

E4.2V 4000 Ekip Dip LI 3p FHR

Trade Price

£23,146.56

Per

1

Unit

EA

Pack Quantity

1

1SDA071221R1

Information

C.BREAKER SACE EMAX2 E4.2V 4000 FIXED THREE-POLE WITH TERMINALS REAR HORIZONTAL AND SOLID-STATE RELEASE IN AC EKIP/DIP-LI R 4000 FITTED WITH: 4 AUXILIARY CONTACT AND C.BREAKER IN POSITION OPEN-CLOSED

Technical Specifications

ABB EcoSolutions

Yes

Circular Design Principles Recyclability Rate

Design for Closing Resource Loops - Standard EN45555 - 79.3 %

Group Waste to Landfill Target

UL 2799 Zero Waste To Landfill Validation available

RoHS Status

Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019

SCIP

3bc060e7-331b-4845-9578-43281338fad7 Italy (IT)

Simplified SCIP

9668a536-c52e-4a7d-9f8e-db8919e7cbfa Poland (PL)52319acc-f753-4102-aef8-036a88d129e4 Poland (PL)fe7c270c-478c-4126-9bd8-60e958bfdef0 Czech Republic (CZ)34a54260-5b83-4728-b875-6555eb9b63d4 Sweden (SE)03b8af72-3cec-420d-a13f-36c25da53f21 Portugal (PT)7be4ba70-b98d-4c75-9027-ff95aaa462cc Belgium (BE)b1b81fbb-e154-4b29-899c-ba99f31e467d Spain (ES)8091c1fd-2aa2-4e25-907c-9c27ec34c2dc Hungary (HU)dfe95a3c-7fab-49f4-9570-e47857a771a1 Norway (NO)f0969fc5-4e9f-4cee-a445-9c3f7209edb2 Poland (PL)aec79f5e-aeb0-4633-a820-588845b43b1b Bulgaria (BG)e1a8c640-14bf-4b10-ac51-3a84a588518a Germany (DE)b9c2e1a2-4604-45bc-aab4-1f6798d9ae95 Germany (DE)8033ee67-cee6-431c-8d6d-51675d222a97 Croatia (HR)cc3dc7df-b4c6-4ea1-9513-54d9055cdd1c Denmark (DK)8c3a1773-d9c2-4044-a112-6381ab1f2630 Germany (DE)0fbca3c1-dfb4-4d36-b5c8-9bf327f7df7e Germany (DE)56b7f8d7-b486-4565-aee3-bae6dd71c783 Sweden (SE)26f6b73d-11b2-400e-a474-af64f3a0432e Belgium (BE)1e47c9f1-e8ce-44f1-a5b8-24632d9f4c5f Estonia (EE)3271c045-d8ba-458f-bc1a-52a299c34de5 Netherlands (NL)6cf4a534-a345-428f-ac45-e8fe91a8a032 Finland (FI)dc3aa9d8-547c-426e-bcf4-59f8b49a0110 Greece (GR)badf12d3-3013-44f1-86a0-92dadbfbe89a France (FR)ad904118-be52-4035-8d02-a95dab4d8e64 France (FR)20786fcd-b845-44d3-b834-bc41c7188db3 Hungary (HU)

Order Code US and Canada

Z4VWERBA000A000000XX

EAN

8015644750718

Minimum Order Quantity

1 piece

Customs Tariff Number

85362090

Product Net Width

384 mm

Product Net Height

371 mm

Product Net Depth / Length

270 mm

Product Net Weight

56 kg

Package Level 1 Units

box 1 piece

Package Level 1 Width

515 mm

Package Level 1 Height

610 mm

Package Level 1 Depth / Length

615 mm

Package Level 1 Gross Weight

63 kg

Package Level 1 EAN

8015644750718

Current Type

AC

Electrical Durability

Ue =< 440 V 5000 cycleUe = 500 ... 690 V 4000 cycle20 cycles per hour

Mechanical Durability

15000 cycle60 cycles per hour

Number of Poles

3

Power Loss

465 W

Product Main Type

SACE Emax 2

Product Name

Air Circuit Breaker

Product Type

Air Circuit Breaker

Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics)

100 %

Rated Current (In)

4000 A

Rated Voltage (Ur)

690 V

Rated Impulse Withstand Voltage (Uimp)

acc. to IEC 60947-2 12 kV

Rated Insulation Voltage (Ui)

AC 1000 V

Rated Operational Voltage

690 V AC

Rated Service Short-Circuit Breaking Capacity (Ics)

(220 V AC) 150 kA(230 V AC) 150 kA(380 V AC) 150 kA(400 V AC) 150 kA(415 V AC) 150 kA(440 V AC) 150 kA(500 V AC) 100 kA(660 V AC) 100 kA(690 V AC) 100 kA

Rated Short-time Withstand Current Low Voltage (Icw)

for 1 s 100 kAfor 3 s 75 kA

Rated Ultimate Short-Circuit Breaking Capacity (Icu)

(400 V AC) 150 kA(415 V AC) 150 kA(440 V AC) 150 kA(500 V AC) 100 kA(525 V AC) 100 kA(690 V AC) 100 kA

Rated Uninterrupted Current (Iu)

4000 A

Recommended Screw Driver

Main Circuit M12

Release

Ekip Dip LI

Release Type

EL

Short-Circuit Performance Level

V

Standards

IEC

Sub-type

E4.2

Terminal Connection Type

Rear flat Horizontal

Terminal Type

Bolt

Tightening Torque

70 N·m

Version

F

ETIM 7

EC000228 - Power circuit-breaker for trafo/generator/installation protection

ETIM 8

EC000228 - Power circuit-breaker for trafo/generator/installation protection

ETIM 9

EC000228 - Power circuit-breaker for trafo/generator/installation protection

IDEA Granular Category Code (IGCC)

4926 >> Air circuit breakers

Object Classification Code

Q

UNSPSC

39121615

WEEE Category

5. Small Equipment (No External Dimension More Than 50 cm)

eClass

V11.1 : 27370409

Document Links

Catalogue page

Datasheet