Trade Price
£15,168.95
Per
1
Unit
EA
Pack Quantity
1
MOVING PART FOR C.BREAKER SACE EMAX2 E4.2V 2500 THREE-POLE WITH SOLID-STATE RELEASE IN AC EKIP/DIP-LSIG R 2500 FITTED WITH: 4 AUXILIARY CONTACT AND C.BREAKER IN POSITION OPEN-CLOSED
ABB EcoSolutions
Yes
Circular Design Principles Recyclability Rate
Design for Closing Resource Loops - Standard EN45555 - 79.3 %
Group Waste to Landfill Target
UL 2799 Zero Waste To Landfill Validation available
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
SCIP
f3968384-0f4f-4c3d-afcc-53f151e6111c Italy (IT)
Simplified SCIP
74647065-b709-422b-9876-4bac7328fcaa Portugal (PT)d884c23f-165c-4ebd-b704-f2f0c60bf555 Bulgaria (BG)3f3172c6-a7a7-42e1-a997-7852f5c01105 Sweden (SE)b644b533-c462-4f99-931b-1b46fab4b49b Poland (PL)3444d560-c924-4028-8748-2ab998ec97ab Germany (DE)2011b6da-cfaa-4c51-8943-e98e3e626bca Netherlands (NL)c28bd9c3-393f-4445-a40d-fd15b58cb186 Belgium (BE)08945ed1-d805-468f-9a68-8a688c8437e2 Spain (ES)0ba0931d-a247-4cd1-870a-24883fe65cb4 Hungary (HU)637f541e-8be3-441a-9c67-19f25fc7fdd3 Poland (PL)da757ff7-73df-4a34-aa3a-40e9dd7c4e68 Germany (DE)0be41550-73a8-4f12-a896-620efc6133ad France (FR)7893478e-d9bf-4139-a39a-8beae0eacc96 Germany (DE)df1edd6d-7732-41a0-a410-354e807cf52a Germany (DE)bf65b85c-bffb-4053-8825-2dc9a022dc29 Sweden (SE)5f9967d9-8736-4265-8ce0-ab63a787d3ce Czech Republic (CZ)969a627c-af38-407a-b9d3-42c2f303a31c Croatia (HR)d0efec28-10d0-4bd3-8e9f-288202520d36 Belgium (BE)2a216f6c-7eee-4dde-bdae-50acfa9b25da Finland (FI)dd770008-5753-4aaf-91d4-90cd2c602465 France (FR)983e0ac5-b7a8-476f-ab61-70f29f7ddd15 Norway (NO)14a0fd68-a640-4b3d-af5a-778757555936 Poland (PL)47efc25f-ca78-4740-a4bb-0bdf948d51ae Hungary (HU)270c202b-342d-433f-8596-3956b0392289 Estonia (EE)8d14a51c-2de5-45d0-94b4-c438939106cf Greece (GR)9d81148b-b8ad-48ad-b1a7-4ee5443dbab3 Denmark (DK)
Order Code US and Canada
Z4VUELAC000A000000XX
EAN
8015644763237
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
425 mm
Product Net Height
425 mm
Product Net Depth / Length
383 mm
Product Net Weight
60 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
515 mm
Package Level 1 Height
610 mm
Package Level 1 Depth / Length
615 mm
Package Level 1 Gross Weight
67 kg
Package Level 1 EAN
8015644763237
Current Type
AC
Electrical Durability
Ue =< 440 V 8000 cycleUe = 500 ... 690 V 8000 cycle20 cycles per hour
Mechanical Durability
20000 cycle60 cycles per hour
Number of Poles
3
Power Loss
743 W
Product Main Type
SACE Emax 2
Product Name
Air Circuit Breaker
Product Type
Air Circuit Breaker
Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics)
100 %
Rated Current (In)
2500 A
Rated Voltage (Ur)
690 V
Rated Impulse Withstand Voltage (Uimp)
acc. to IEC 60947-2 12 kV
Rated Insulation Voltage (Ui)
AC 1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 150 kA(230 V AC) 150 kA(380 V AC) 150 kA(400 V AC) 150 kA(415 V AC) 150 kA(440 V AC) 150 kA(500 V AC) 100 kA(660 V AC) 100 kA(690 V AC) 100 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 100 kAfor 3 s 75 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(400 V AC) 150 kA(415 V AC) 150 kA(440 V AC) 150 kA(500 V AC) 100 kA(525 V AC) 100 kA(690 V AC) 100 kA
Rated Uninterrupted Current (Iu)
2500 A
Release
Ekip Dip LSIG
Release Type
EL
Short-Circuit Performance Level
V
Standards
IEC
Sub-type
E4.2
Version
W
ETIM 7
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
IDEA Granular Category Code (IGCC)
4926 >> Air circuit breakers
Object Classification Code
Q
UNSPSC
39121615
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Datasheet