Trade Price
£7,846.55
Per
1
Unit
EA
Pack Quantity
1
C.BREAKER SACE EMAX2 E2.2S 1250 FIXED FOUR-POLE WITH TERMINALS REAR HORIZONTAL AND SOLID-STATE RELEASE IN AC EKIP/DIP-LSIG R 1250 FITTED WITH: 4 AUXILIARY CONTACT AND C.BREAKER IN POSITION OPEN-CLOSED
ABB EcoSolutions
Yes
Circular Design Principles Recyclability Rate
Design for Closing Resource Loops - Standard EN45555 - 79.1 %
Group Waste to Landfill Target
UL 2799 Zero Waste To Landfill Validation available
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
SCIP
29c37f5a-b440-45f3-b0c4-9e622fb748b7 Italy (IT)
Simplified SCIP
cd826518-8419-4522-b504-00b96fb8119f Portugal (PT)99441ae1-905c-4e1a-883a-4a67176f242c Poland (PL)5eec17ba-532e-4f74-a1b1-2fb487e34e3e Sweden (SE)543a5edd-170d-42de-8101-1aa3bae93d59 Bulgaria (BG)49b83d92-3a0f-4ec1-a586-fe8b675e031a Norway (NO)9cf9b9e1-2ecd-49c2-b950-713b82452adf Croatia (HR)38df7ed5-70be-46d6-b58b-625e9757da6d Germany (DE)8051fc9c-91ea-4f3a-9cdd-6a4a62f83958 Hungary (HU)c49da207-7576-44fb-b197-d9ab0a7c5b83 Spain (ES)f0b59262-5d6f-49eb-ac95-ea13129a985d Poland (PL)70b62eed-9c32-4d19-a3ee-2faa20f88280 Netherlands (NL)cf66247c-591b-48e2-823f-914270b4d400 Belgium (BE)1c8ecb39-db36-474d-9f34-9a49f6ffb388 Sweden (SE)71253637-fde0-4641-94d0-ddc36d4f3ae9 Czech Republic (CZ)ea4dec27-8f0a-4f43-9ae8-0036246dffc3 Finland (FI)4023e5b4-6fff-46ed-b2f6-34856c29276e Belgium (BE)02ab67ff-179e-4137-9a84-8ec9f4f95656 Poland (PL)f1cb6016-c800-45c2-ad29-619ea2c6c680 France (FR)7a805709-bc33-4510-8e75-01820f93e483 France (FR)bf857d56-440c-421f-8c0a-a921d4ea552a Germany (DE)a918252f-f4f2-422c-aba8-8630105bb910 Germany (DE)44c06979-c60e-4d75-a0ab-fb2d185d55ca Germany (DE)fae371a8-03ba-4ce8-96a3-a3a299d88511 Greece (GR)3e481200-185d-4c80-8ed0-e24725a250ec Estonia (EE)5a14ba64-c460-406e-863d-baaa88131771 Hungary (HU)2f1b81e0-2409-49af-beaf-01a4d44f480f Denmark (DK)
Order Code US and Canada
ZBSREHBC000A000000XX
EAN
8015644754433
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
366 mm
Product Net Height
371 mm
Product Net Depth / Length
270 mm
Product Net Weight
53 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
515 mm
Package Level 1 Height
610 mm
Package Level 1 Depth / Length
615 mm
Package Level 1 Gross Weight
58 kg
Package Level 1 EAN
8015644754433
Current Type
AC
Electrical Durability
Ue =< 440 V 15000 cycleUe = 500 ... 690 V 15000 cycle30 cycles per hour
Mechanical Durability
25000 cycle60 cycles per hour
Neutral Pole Current ([%Iu])
100 %
Number of Poles
4
Power Loss
83 W
Product Main Type
SACE Emax 2
Product Name
Air Circuit Breaker
Product Type
Air Circuit Breaker
Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics)
100 %
Rated Current (In)
1250 A
Rated Voltage (Ur)
690 V
Rated Impulse Withstand Voltage (Uimp)
acc. to IEC 60947-2 12 kV
Rated Insulation Voltage (Ui)
AC 1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 85 kA(230 V AC) 85 kA(380 V AC) 85 kA(400 V AC) 85 kA(415 V AC) 85 kA(440 V AC) 85 kA(500 V AC) 66 kA(660 V AC) 66 kA(690 V AC) 66 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 66 kAfor 3 s 50 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(400 V AC) 85 kA(415 V AC) 85 kA(440 V AC) 85 kA(500 V AC) 66 kA(525 V AC) 66 kA(690 V AC) 66 kA
Rated Uninterrupted Current (Iu)
1250 A
Recommended Screw Driver
Main Circuit M12
Release
Ekip Dip LSIG
Release Type
EL
Short-Circuit Performance Level
S
Standards
IEC
Sub-type
E2.2
Terminal Connection Type
Rear flat Horizontal
Terminal Type
Bolt
Tightening Torque
70 N·m
Version
F
ETIM 7
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
IDEA Granular Category Code (IGCC)
4926 >> Air circuit breakers
Object Classification Code
Q
UNSPSC
39121615
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Datasheet