Trade Price
£6,994.76
Per
1
Unit
EA
Pack Quantity
1
C.BREAKER SACE EMAX2 E2.2S 800 FIXED FOUR-POLE WITH TERMINALS REAR HORIZONTAL AND SOLID-STATE RELEASE IN AC EKIP/DIP-LSI R 800 FITTED WITH: 4 AUXILIARY CONTACT AND C.BREAKER IN POSITION OPEN-CLOSED
ABB EcoSolutions
Yes
Circular Design Principles Recyclability Rate
Design for Closing Resource Loops - Standard EN45555 - 79.1 %
Group Waste to Landfill Target
UL 2799 Zero Waste To Landfill Validation available
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
SCIP
84f8dfe7-711e-4d4d-8f0b-e824a2b9ba8d Italy (IT)
Simplified SCIP
dfeb3946-e2fa-4bd1-8cf5-4e546482e5b1 Hungary (HU)de688f59-8694-4860-9edc-f0c9c3c19183 France (FR)84071ae8-e0d3-4d8c-8523-bf94bd09b8f9 Poland (PL)07dc78c5-a1f6-4539-a07d-fdfde35bdc4f Norway (NO)e4902301-9d7a-465c-bcbd-4650894fa15b France (FR)b8bc456f-51d4-44ad-8210-7b7d244728d1 Bulgaria (BG)81f7fef0-6386-4be3-ac9f-524e10747a4d Germany (DE)22773161-a11a-4b7e-a5aa-ca5dcf86944d Croatia (HR)3e2680e1-9680-453d-bf51-49b9e11fb6ee Germany (DE)62556683-181b-4c0a-b97f-9d383f1c14aa Greece (GR)ace59c25-250e-4e4b-a8e3-fb4a11661072 Estonia (EE)add19853-fbb7-4e17-857e-ecc6b048e4ae Netherlands (NL)f5883339-18b7-4875-9edc-b717bc29cc7d Finland (FI)03683074-d424-41b9-992d-b66d6b4daac1 Belgium (BE)a8324fc2-ce58-4f15-94c0-f55b21a5e391 Sweden (SE)c64ff1be-4cf0-4ada-836d-612b682e4679 Germany (DE)f1004802-c0bd-42d2-bef3-ac41c0a8b8f9 Denmark (DK)da0f5283-a3f2-4313-8689-7d616a3877f2 Germany (DE)d713fdd2-c9aa-49b0-93c1-dd1ee52df475 Poland (PL)8f01a78e-125f-48c8-a1ac-6a941ba5847a Poland (PL)626e48b6-2594-4137-907e-ae995f0d9fda Czech Republic (CZ)8a7c7e5c-730a-4fe7-8192-198c959fa5fd Sweden (SE)f3ff6b7b-2973-46fd-a78a-28510f0117f7 Portugal (PT)6448626b-bd9b-4d1d-888e-8c899eb07f56 Spain (ES)b4698cb9-2d08-491d-812e-5a5a0d6c7826 Belgium (BE)9450675c-3de9-42df-8287-84ea34cb2f44 Hungary (HU)
Order Code US and Canada
ZBSPEFBB000A000000XX
EAN
8015644753825
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
366 mm
Product Net Height
371 mm
Product Net Depth / Length
270 mm
Product Net Weight
53 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
515 mm
Package Level 1 Height
610 mm
Package Level 1 Depth / Length
615 mm
Package Level 1 Gross Weight
58 kg
Package Level 1 EAN
8015644753825
Current Type
AC
Electrical Durability
Ue =< 440 V 15000 cycleUe = 500 ... 690 V 15000 cycle30 cycles per hour
Mechanical Durability
25000 cycle60 cycles per hour
Neutral Pole Current ([%Iu])
100 %
Number of Poles
4
Power Loss
34 W
Product Main Type
SACE Emax 2
Product Name
Air Circuit Breaker
Product Type
Air Circuit Breaker
Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics)
100 %
Rated Current (In)
800 A
Rated Voltage (Ur)
690 V
Rated Impulse Withstand Voltage (Uimp)
acc. to IEC 60947-2 12 kV
Rated Insulation Voltage (Ui)
AC 1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 85 kA(230 V AC) 85 kA(380 V AC) 85 kA(400 V AC) 85 kA(415 V AC) 85 kA(440 V AC) 85 kA(500 V AC) 66 kA(660 V AC) 66 kA(690 V AC) 66 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 66 kAfor 3 s 50 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(400 V AC) 85 kA(415 V AC) 85 kA(440 V AC) 85 kA(500 V AC) 66 kA(525 V AC) 66 kA(690 V AC) 66 kA
Rated Uninterrupted Current (Iu)
800 A
Recommended Screw Driver
Main Circuit M12
Release
Ekip Dip LSI
Release Type
EL
Short-Circuit Performance Level
S
Standards
IEC
Sub-type
E2.2
Terminal Connection Type
Rear flat Horizontal
Terminal Type
Bolt
Tightening Torque
70 N·m
Version
F
ETIM 7
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
IDEA Granular Category Code (IGCC)
4926 >> Air circuit breakers
Object Classification Code
Q
UNSPSC
39121615
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409