Trade Price
£11,253.84
Per
1
Unit
EA
Pack Quantity
1
C.BREAKER SACE EMAX2 E2.2S 2000 FIXED THREE-POLE WITH TERMINALS REAR HORIZONTAL AND SOLID-STATE RELEASE IN AC EKIP/HI-TOUCH-LSI R 2000 FITTED WITH: 4 AUXILIARY CONTACT AND C.BREAKER IN POSITION OPEN-CLOSED
ABB EcoSolutions
Yes
Circular Design Principles Recyclability Rate
Design for Closing Resource Loops - Standard EN45555 - 79.1 %
Group Waste to Landfill Target
UL 2799 Zero Waste To Landfill Validation available
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
SCIP
a2d89988-e42e-453e-931e-f6f37ca16dbc Italy (IT)
Simplified SCIP
272b19e5-9090-45b4-a731-36eb9624325f France (FR)90b595c3-4580-457b-b1d7-94eb505e15d1 Norway (NO)a3571a66-1b26-4637-9c15-0a7bcdd1fc95 Poland (PL)c6fcbf49-7da1-4b08-a86d-949283da7a46 Hungary (HU)d483a4ae-b9d7-4881-b60a-97c0c82650c3 France (FR)caa3faae-1b33-4dfa-bf38-3fc870813498 Bulgaria (BG)86930bc1-b812-41c9-9d8b-21466f096485 Germany (DE)3d389629-16df-4f19-9cef-164cb62ce371 Croatia (HR)1aab9b9d-b75e-43d8-b65c-46cfb0e66597 Germany (DE)26b9d7b5-79ea-4a33-bf5c-3a47b1177041 Belgium (BE)24cec120-1498-4180-af91-7ad1f823b958 Finland (FI)73f323cc-36e6-4903-a19f-145819b5322a Netherlands (NL)8ffce991-cb54-45f7-a72c-94ab125874d4 Greece (GR)76a6078f-2f16-4424-8460-d637d297d83e Estonia (EE)75aa3df6-9fa5-4a46-ac26-89ae890388eb Sweden (SE)ec904edf-fdb2-42cc-805b-3b2675a8550b Denmark (DK)004d0f09-728b-4702-bb9b-38c16eaf16d1 Germany (DE)99bdf4b9-4649-4101-8871-357ddf018578 Germany (DE)7cbba5e6-9283-4e69-8e35-a2ad642eb021 Czech Republic (CZ)3111b641-c6ed-4c82-8cc1-31f48ea4d678 Poland (PL)e588a2f1-909e-4525-b8c9-66454945e8a9 Poland (PL)254575ec-e22e-4060-b43c-14b62a0e8e82 Portugal (PT)b296f33e-c991-4520-9cbe-699977166925 Sweden (SE)bf2ab24a-5eb6-4711-aa27-a0f910b2022e Hungary (HU)7585c40a-aa7e-4236-8f8c-ff0c45e39e73 Belgium (BE)29dfe5ec-0583-4cbe-8885-fa6446627923 Spain (ES)
Order Code US and Canada
Z2STEKBJ200A000000XX
EAN
8015644748982
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
276 mm
Product Net Height
371 mm
Product Net Depth / Length
270 mm
Product Net Weight
41 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
515 mm
Package Level 1 Height
610 mm
Package Level 1 Depth / Length
515 mm
Package Level 1 Gross Weight
46 kg
Package Level 1 EAN
8015644748982
Current Type
AC
Electrical Durability
Ue =< 440 V 10000 cycleUe = 500 ... 690 V 8000 cycle30 cycles per hour
Mechanical Durability
25000 cycle60 cycles per hour
Number of Poles
3
Power Loss
212 W
Product Main Type
SACE Emax 2
Product Name
Air Circuit Breaker
Product Type
Air Circuit Breaker
Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics)
100 %
Rated Current (In)
2000 A
Rated Voltage (Ur)
690 V
Rated Impulse Withstand Voltage (Uimp)
acc. to IEC 60947-2 12 kV
Rated Insulation Voltage (Ui)
AC 1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 85 kA(230 V AC) 85 kA(380 V AC) 85 kA(400 V AC) 85 kA(415 V AC) 85 kA(440 V AC) 85 kA(500 V AC) 66 kA(660 V AC) 66 kA(690 V AC) 66 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 66 kAfor 3 s 50 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(400 V AC) 85 kA(415 V AC) 85 kA(440 V AC) 85 kA(500 V AC) 66 kA(525 V AC) 66 kA(690 V AC) 66 kA
Rated Uninterrupted Current (Iu)
2000 A
Recommended Screw Driver
Main Circuit M12
Release
Ekip Hi-Touch LSI
Release Type
EL
Short-Circuit Performance Level
S
Standards
IEC
Sub-type
E2.2
Terminal Connection Type
Rear flat Horizontal
Terminal Type
Bolt
Tightening Torque
70 N·m
Version
F
ETIM 7
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
IDEA Granular Category Code (IGCC)
4926 >> Air circuit breakers
Object Classification Code
Q
UNSPSC
39121615
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Datasheet