Trade Price
£9,419.17
Per
1
Unit
EA
Pack Quantity
1
C.BREAKER SACE EMAX2 E2.2S 1250 FIXED THREE-POLE WITH TERMINALS REAR HORIZONTAL AND SOLID-STATE RELEASE IN AC EKIP/HI-TOUCH-LSIG R 1250 FITTED WITH: 4 AUXILIARY CONTACT AND C.BREAKER IN POSITION OPEN-CLOSED
ABB EcoSolutions
Yes
Circular Design Principles Recyclability Rate
Design for Closing Resource Loops - Standard EN45555 - 79.1 %
Group Waste to Landfill Target
UL 2799 Zero Waste To Landfill Validation available
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
SCIP
93951f71-79f6-4cd1-80e4-c7909f9baa54 Italy (IT)
Simplified SCIP
bffca4b8-cc43-4760-9490-599d85598d59 Poland (PL)e66feb15-45a7-402a-885b-567ad390a6e3 Poland (PL)16400ca4-5e80-4420-982b-8573796a6059 Hungary (HU)d01d409d-835b-4eba-81f3-1a206a2f1b24 Belgium (BE)59f22650-15c6-4cf3-81e8-936fb8c114dc Spain (ES)2392a3fb-3f44-46f4-9dbe-35b3f18fd0a3 Czech Republic (CZ)d856b782-40d9-4d5f-9eaf-6ac5d42fe19e Poland (PL)283339fe-92aa-4860-af51-cda42672e306 Norway (NO)6fd0a2c2-40a6-4c1b-8891-da5cc7f79bf9 Hungary (HU)f434cbad-8c1f-492e-9765-c8f8167927d4 Estonia (EE)86d5c231-42f5-446b-a34e-43304d107673 Denmark (DK)53abf30e-bf07-4085-8cce-5c8cd62100af Germany (DE)dbf528bf-9554-4f30-b26a-02c4a26f0b00 Germany (DE)272adc79-6785-401e-80b5-e2b2e3cbcbcd Germany (DE)0fc4f35f-d13c-4c03-8f09-abc9a3437745 Germany (DE)6ac32107-d851-47e7-9702-8bef3e0e530d Sweden (SE)b7da3638-55c2-402e-8420-ae7abe843e93 Belgium (BE)9396dbfd-071e-4f90-b7df-2f924996de4f Netherlands (NL)80792894-4f83-4c20-9dab-294c74097336 France (FR)0e3108de-20ee-4ddb-9c12-180961e99ce3 Greece (GR)c028809b-13c3-4445-9c69-71828cb7c52f Finland (FI)a1694668-4cc1-476e-99ef-3e2f5b40eebb Bulgaria (BG)5e88e40e-524e-48d0-9f09-e7cf486a62a1 Croatia (HR)c50f5f90-efff-420c-bb42-c569d4703136 France (FR)3d9c4630-bd46-4103-bfa8-16d8631b5e9f Portugal (PT)dcc2e542-6ea2-40ce-a663-fd493265c721 Sweden (SE)
Order Code US and Canada
Z2SREHBK200A000000XX
EAN
8015644748197
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
276 mm
Product Net Height
371 mm
Product Net Depth / Length
270 mm
Product Net Weight
41 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
515 mm
Package Level 1 Height
610 mm
Package Level 1 Depth / Length
515 mm
Package Level 1 Gross Weight
46 kg
Package Level 1 EAN
8015644748197
Current Type
AC
Electrical Durability
Ue =< 440 V 15000 cycleUe = 500 ... 690 V 15000 cycle30 cycles per hour
Mechanical Durability
25000 cycle60 cycles per hour
Number of Poles
3
Power Loss
83 W
Product Main Type
SACE Emax 2
Product Name
Air Circuit Breaker
Product Type
Air Circuit Breaker
Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics)
100 %
Rated Current (In)
1250 A
Rated Voltage (Ur)
690 V
Rated Impulse Withstand Voltage (Uimp)
acc. to IEC 60947-2 12 kV
Rated Insulation Voltage (Ui)
AC 1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 85 kA(230 V AC) 85 kA(380 V AC) 85 kA(400 V AC) 85 kA(415 V AC) 85 kA(440 V AC) 85 kA(500 V AC) 66 kA(660 V AC) 66 kA(690 V AC) 66 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 66 kAfor 3 s 50 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(400 V AC) 85 kA(415 V AC) 85 kA(440 V AC) 85 kA(500 V AC) 66 kA(525 V AC) 66 kA(690 V AC) 66 kA
Rated Uninterrupted Current (Iu)
1250 A
Recommended Screw Driver
Main Circuit M12
Release
Ekip Hi-Touch LSIG
Release Type
EL
Short-Circuit Performance Level
S
Standards
IEC
Sub-type
E2.2
Terminal Connection Type
Rear flat Horizontal
Terminal Type
Bolt
Tightening Torque
70 N·m
Version
F
ETIM 7
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
IDEA Granular Category Code (IGCC)
4926 >> Air circuit breakers
Object Classification Code
Q
UNSPSC
39121615
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Datasheet