Trade Price
£6,126.58
Per
1
Unit
EA
Pack Quantity
1
C.BREAKER SACE EMAX2 E2.2N 1000 FIXED FOUR-POLE WITH TERMINALS REAR HORIZONTAL AND SOLID-STATE RELEASE IN AC EKIP/DIP-LI R 1000 FITTED WITH: 4 AUXILIARY CONTACT AND C.BREAKER IN POSITION OPEN-CLOSED
ABB EcoSolutions
Yes
Circular Design Principles Recyclability Rate
Design for Closing Resource Loops - Standard EN45555 - 79.1 %
Group Waste to Landfill Target
UL 2799 Zero Waste To Landfill Validation available
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
SCIP
a1a36d57-736d-484b-9eb7-6e6849cf9646 Italy (IT)
Simplified SCIP
b3b9903f-575f-43c0-af10-410a6825e15c Hungary (HU)0a315ff0-4fc3-49a0-b14b-bae5cf5eec23 Belgium (BE)6ca57a7b-0401-443c-a420-26abe7b5620c Spain (ES)fdc9c0b9-b9d1-456f-8875-26f7cbbbca9b Norway (NO)76cb3f1c-6192-4acd-a5a2-cd327b3e1f7b Poland (PL)0bf9acfa-f965-42ac-8496-dbce9a9f5c88 Hungary (HU)d8da7285-1b55-4d7f-9d52-2d54ffbb4bda Germany (DE)beeb9f45-c5f6-4499-9b32-7799fa0a9907 Denmark (DK)ca62c5de-5cd0-4118-a4e3-fa3efd215242 Germany (DE)7a4282f7-fa21-437a-865a-aaa9ce864703 Belgium (BE)2e7dc358-ac4b-4e6c-8c8c-12efddd3b36e Sweden (SE)94b5a21d-01bd-4852-b113-e4e715a9acea Estonia (EE)43dd7adf-1c24-413b-bc2f-ec79861c2ff9 France (FR)d79ec58b-1596-4ba4-a182-9da43645249f Finland (FI)61a4ef4a-163a-41ea-abcf-41db5a4ba739 Netherlands (NL)4bebc7ee-dd1a-4e94-b719-45e47577ad11 Greece (GR)e71c8f96-adc5-489b-a180-1c155154d162 Germany (DE)6d6e8b2c-b2be-47ba-8ccb-0cdde92fee56 Germany (DE)f514cc91-6800-4aa2-9a78-8da5bd915d93 Croatia (HR)c17cd921-824a-4a5b-87fa-ffe304fdd0e2 Bulgaria (BG)525e4fe7-3715-4d54-8e64-4567fd09af6c France (FR)22d649e8-b98a-4ab6-9ae7-9b2a3413da89 Poland (PL)8c3743e9-7ac2-4f9a-aa1f-da5e8948d218 Poland (PL)2f3d467a-0da4-43cf-8379-4fa24bd54490 Sweden (SE)2b9f46ff-a3c5-4ab2-bf9d-c57c3ad5d09f Portugal (PT)c518f5b4-3463-4344-8187-d3a36ad6c664 Czech Republic (CZ)
Order Code US and Canada
ZBNQEGBA000A000000XX
EAN
8015644754013
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
366 mm
Product Net Height
371 mm
Product Net Depth / Length
270 mm
Product Net Weight
53 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
515 mm
Package Level 1 Height
610 mm
Package Level 1 Depth / Length
615 mm
Package Level 1 Gross Weight
58 kg
Package Level 1 EAN
8015644754013
Current Type
AC
Electrical Durability
Ue =< 440 V 15000 cycleUe = 500 ... 690 V 15000 cycle30 cycles per hour
Mechanical Durability
25000 cycle60 cycles per hour
Neutral Pole Current ([%Iu])
100 %
Number of Poles
4
Power Loss
53 W
Product Main Type
SACE Emax 2
Product Name
Air Circuit Breaker
Product Type
Air Circuit Breaker
Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics)
100 %
Rated Current (In)
1000 A
Rated Voltage (Ur)
690 V
Rated Impulse Withstand Voltage (Uimp)
acc. to IEC 60947-2 12 kV
Rated Insulation Voltage (Ui)
AC 1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 66 kA(230 V AC) 66 kA(380 V AC) 66 kA(400 V AC) 66 kA(415 V AC) 66 kA(440 V AC) 66 kA(500 V AC) 66 kA(660 V AC) 66 kA(690 V AC) 66 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 66 kAfor 3 s 50 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(400 V AC) 66 kA(415 V AC) 66 kA(440 V AC) 66 kA(500 V AC) 66 kA(525 V AC) 66 kA(690 V AC) 66 kA
Rated Uninterrupted Current (Iu)
1000 A
Recommended Screw Driver
Main Circuit M12
Release
Ekip Dip LI
Release Type
EL
Short-Circuit Performance Level
N
Standards
IEC
Sub-type
E2.2
Terminal Connection Type
Rear flat Horizontal
Terminal Type
Bolt
Tightening Torque
70 N·m
Version
F
ETIM 7
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
IDEA Granular Category Code (IGCC)
4926 >> Air circuit breakers
Object Classification Code
Q
UNSPSC
39121615
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Datasheet