Trade Price
£7,109.43
Per
1
Unit
EA
Pack Quantity
1
C.BREAKER SACE EMAX2 E2.2H 1600 FIXED THREE-POLE WITH TERMINALS REAR HORIZONTAL AND SOLID-STATE RELEASE IN AC EKIP/TOUCH-LSIG R 1600 FITTED WITH: 4 AUXILIARY CONTACT AND C.BREAKER IN POSITION OPEN-CLOSED
ABB EcoSolutions
Yes
Circular Design Principles Recyclability Rate
Design for Closing Resource Loops - Standard EN45555 - 79.1 %
Group Waste to Landfill Target
UL 2799 Zero Waste To Landfill Validation available
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
SCIP
9e5cbd43-8fb6-48e1-87cd-5dc8217a7ed5 Italy (IT)
Simplified SCIP
cbbf5660-8aec-4f9d-bd93-65424b50f482 Czech Republic (CZ)5eec0a7b-1b8a-4597-b0d2-f2f478a84612 Poland (PL)3a621390-ded4-4f1c-841c-6e0288708bcc Poland (PL)a12322e9-7240-4516-b932-a048a617ecc2 Sweden (SE)20d143b6-24c8-42de-80c2-9e119a9ec66e Portugal (PT)96e160e5-08d1-40c6-bf96-287f4cafbf53 Germany (DE)08d5b93e-6d01-4b99-af21-b3acb89fa4bc Germany (DE)26f21a60-8d6d-45e1-9f33-36bf27343e50 Estonia (EE)ac293c58-794e-49c0-a775-f5cabffe41cc Sweden (SE)b2d4066f-3e86-44c0-9c78-7bb72a5fca8a Netherlands (NL)62a6762e-af58-4cdc-9377-b109d5eac976 Finland (FI)501536a2-042a-4cf6-8e86-9270988b32f1 France (FR)66ec730b-6b23-4d90-8a49-c8c2e67b476d Germany (DE)b334c2f4-86b9-4b81-8fa5-07ef5e9d3dba Denmark (DK)a74f6877-11ff-4720-b29b-804dc13107c6 Germany (DE)7ab8f0c3-a583-45a0-96b7-5f64e1e73fb9 Bulgaria (BG)32f24a6a-f419-4096-afa2-2962fe43c208 Hungary (HU)cecbb30a-74df-4350-93a1-5251a8bdc2ba Poland (PL)15f57b43-b133-48b3-b251-ea357c32226e Norway (NO)5796e567-fb2a-414a-b8f9-62cf125d3722 Hungary (HU)52512f79-1ac0-4d65-86f7-0b1528842155 Spain (ES)c9527207-a4d6-47f6-9f5e-a1d4c2336fd8 Belgium (BE)f3512ede-9632-4c68-b8e0-78a46ff7d740 France (FR)05a9b3a8-84be-45bd-8415-3186be21907c Croatia (HR)2a7c92c7-d771-49db-b7e9-9ee7bb2b00b6 Belgium (BE)37889732-ab93-4f52-acf0-ce7977b39cab Greece (GR)
Order Code US and Canada
Z2HSEJBF000A000000XX
EAN
8015644748661
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
276 mm
Product Net Height
371 mm
Product Net Depth / Length
270 mm
Product Net Weight
41 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
515 mm
Package Level 1 Height
610 mm
Package Level 1 Depth / Length
515 mm
Package Level 1 Gross Weight
46 kg
Package Level 1 EAN
8015644748661
Current Type
AC
Electrical Durability
Ue =< 440 V 12000 cycleUe = 500 ... 690 V 10000 cycle30 cycles per hour
Mechanical Durability
25000 cycle60 cycles per hour
Number of Poles
3
Power Loss
136 W
Product Main Type
SACE Emax 2
Product Name
Air Circuit Breaker
Product Type
Air Circuit Breaker
Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics)
100 %
Rated Current (In)
1600 A
Rated Voltage (Ur)
690 V
Rated Impulse Withstand Voltage (Uimp)
acc. to IEC 60947-2 12 kV
Rated Insulation Voltage (Ui)
AC 1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA(230 V AC) 100 kA(380 V AC) 100 kA(400 V AC) 100 kA(415 V AC) 100 kA(440 V AC) 100 kA(500 V AC) 85 kA(660 V AC) 85 kA(690 V AC) 85 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 85 kAfor 3 s 66 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(400 V AC) 100 kA(415 V AC) 100 kA(440 V AC) 100 kA(500 V AC) 85 kA(525 V AC) 85 kA(690 V AC) 85 kA
Rated Uninterrupted Current (Iu)
1600 A
Recommended Screw Driver
Main Circuit M12
Release
Ekip Touch LSIG
Release Type
EL
Short-Circuit Performance Level
H
Standards
IEC
Sub-type
E2.2
Terminal Connection Type
Rear flat Horizontal
Terminal Type
Bolt
Tightening Torque
70 N·m
Version
F
ETIM 7
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
IDEA Granular Category Code (IGCC)
4926 >> Air circuit breakers
Object Classification Code
Q
UNSPSC
39121615
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Datasheet