Trade Price
£6,552.47
Per
1
Unit
EA
Pack Quantity
1
C.BREAKER SACE EMAX2 E2.2H 1000 FIXED THREE-POLE WITH TERMINALS REAR HORIZONTAL AND SOLID-STATE RELEASE IN AC EKIP/DIP-LSIG R 1000 FITTED WITH: 4 AUXILIARY CONTACT AND C.BREAKER IN POSITION OPEN-CLOSED
ABB EcoSolutions
Yes
Circular Design Principles Recyclability Rate
Design for Closing Resource Loops - Standard EN45555 - 79.1 %
Group Waste to Landfill Target
UL 2799 Zero Waste To Landfill Validation available
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
SCIP
3524ebd0-506e-4842-a980-5debc7b3c0d7 Italy (IT)
Simplified SCIP
5c288ab6-fd2a-47c3-969e-be7d20e5a2f0 Spain (ES)5b0456d4-4d16-4b5c-9353-e3f07feb2fe7 Belgium (BE)3a601751-e3ea-4ec3-8911-c58671e8d0a3 Hungary (HU)e177d9fc-afb7-400f-b216-a8c6a960a2ed Germany (DE)7e5b07da-fe01-4014-a920-ac4d28208e74 Croatia (HR)94a74485-0f86-4abb-8327-839ba8e7fe7a Bulgaria (BG)3cea7eb8-ec05-4a2a-b9c2-1e9d0614e279 Germany (DE)a5f85d71-3aec-4ba1-819b-d3202a3cdf8c Estonia (EE)705be766-e203-4cec-88a3-94c33c87334d Germany (DE)cec22d4e-37e1-4e4c-828e-2cf065d01ec0 Germany (DE)969f9bf4-8dfe-4e08-afbf-58fb3df03a0a Denmark (DK)660053e0-176b-48ee-9137-44b24cc5b52e France (FR)2f6e5966-4136-4401-8150-60bceeed5ab6 Greece (GR)ca98a39c-17fe-4866-8839-0a0a91e1490f Finland (FI)12d9cf51-8ecc-4ab7-8d20-5505bbb56257 Netherlands (NL)82e6c02d-d6b2-42cd-a453-3228b82d582b Belgium (BE)082efb1d-3516-44a9-b885-3f692be1f338 Sweden (SE)a53c5ef4-0562-47fa-8516-bb3b586f36a4 Hungary (HU)ed87ce75-0144-47f2-bbed-677fdc310f79 Norway (NO)ed901245-02c5-4c60-a781-2e21236023a3 Poland (PL)2754cb36-aecf-4f86-b564-4aa5f75f78cb France (FR)0494ba2a-a17f-4f46-8495-04269c13d748 Poland (PL)590f0ef7-8d8c-4dc9-b3af-a16fb4392c74 Czech Republic (CZ)49503878-ff53-48c0-baad-f11891d0b73f Poland (PL)918f0d0e-e541-4d77-8830-71fe86d5d81e Portugal (PT)632f9036-a5cb-4562-bc51-2349a110ce0e Sweden (SE)
Order Code US and Canada
Z2HQEGBC000A000000XX
EAN
8015644747930
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
276 mm
Product Net Height
371 mm
Product Net Depth / Length
270 mm
Product Net Weight
41 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
515 mm
Package Level 1 Height
610 mm
Package Level 1 Depth / Length
515 mm
Package Level 1 Gross Weight
46 kg
Package Level 1 EAN
8015644747930
Current Type
AC
Electrical Durability
Ue =< 440 V 15000 cycleUe = 500 ... 690 V 15000 cycle30 cycles per hour
Mechanical Durability
25000 cycle60 cycles per hour
Number of Poles
3
Power Loss
53 W
Product Main Type
SACE Emax 2
Product Name
Air Circuit Breaker
Product Type
Air Circuit Breaker
Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics)
100 %
Rated Current (In)
1000 A
Rated Voltage (Ur)
690 V
Rated Impulse Withstand Voltage (Uimp)
acc. to IEC 60947-2 12 kV
Rated Insulation Voltage (Ui)
AC 1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA(230 V AC) 100 kA(380 V AC) 100 kA(400 V AC) 100 kA(415 V AC) 100 kA(440 V AC) 100 kA(500 V AC) 85 kA(660 V AC) 85 kA(690 V AC) 85 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 85 kAfor 3 s 66 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(400 V AC) 100 kA(415 V AC) 100 kA(440 V AC) 100 kA(500 V AC) 85 kA(525 V AC) 85 kA(690 V AC) 85 kA
Rated Uninterrupted Current (Iu)
1000 A
Recommended Screw Driver
Main Circuit M12
Release
Ekip Dip LSIG
Release Type
EL
Short-Circuit Performance Level
H
Standards
IEC
Sub-type
E2.2
Terminal Connection Type
Rear flat Horizontal
Terminal Type
Bolt
Tightening Torque
70 N·m
Version
F
ETIM 7
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
IDEA Granular Category Code (IGCC)
4926 >> Air circuit breakers
Object Classification Code
Q
UNSPSC
39121615
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Datasheet