Trade Price
£11,630.64
Per
1
Unit
EA
Pack Quantity
1
C.BREAKER SACE EMAX2 E2.2B 2000 FIXED FOUR-POLE WITH TERMINALS REAR HORIZONTAL AND SOLID-STATE RELEASE IN AC EKIP/HI-TOUCH-LSI R 2000 FITTED WITH: 4 AUXILIARY CONTACT AND C.BREAKER IN POSITION OPEN-CLOSED
ABB EcoSolutions
Yes
Circular Design Principles Recyclability Rate
Design for Closing Resource Loops - Standard EN45555 - 79.1 %
Group Waste to Landfill Target
UL 2799 Zero Waste To Landfill Validation available
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
SCIP
667c4a37-79ce-45c2-8ca3-b471370de1be Italy (IT)
Simplified SCIP
64d7ee9f-0eb5-4c2c-81cf-617babdfebf0 Belgium (BE)b339dda8-caf7-47f4-87fe-ba9d0bac1c1e Spain (ES)fc62015f-7a95-49b5-b916-7fde5f4776cd Hungary (HU)ba7674ce-42b8-4278-8217-bdc0fad7a466 Bulgaria (BG)6a43f144-d0ec-47b8-8562-03562ff41320 France (FR)a8be6f10-8cf9-4d2d-a9f3-1ece9ba93ec7 Croatia (HR)1830d748-22c8-4287-b334-9381a8c041fe Hungary (HU)3125c58b-c945-4554-bd04-a37c91a1659b Poland (PL)75cce31e-7708-4640-8b67-fce9550548a8 Norway (NO)d0445ad0-dee6-4558-a283-d19ecb192691 Czech Republic (CZ)9f7f0d71-ff9a-4225-8a7c-ca24be918d7b Netherlands (NL)b1c4dddc-7237-4a6c-ad93-a5075d7b5569 Finland (FI)e77b3cfd-f229-4a67-8728-ace277c26c48 Estonia (EE)32a49850-cb22-40ff-8251-2053f1f53f9e Greece (GR)0bb319d8-e9df-4203-be84-c8d5e5996126 France (FR)36e3e386-793f-4ff3-b4c2-999e00c6a1b1 Sweden (SE)1b53b463-38bc-4f96-8d14-3874de078acf Belgium (BE)0b20c1cd-154b-4c7d-8c04-fd2c9bedc5fc Germany (DE)1b65553e-fdea-4b4e-a871-a579cf31cc4a Germany (DE)e50b2ec0-c1d4-43c9-83e4-c54bcbac60de Germany (DE)42ee380e-d56b-48ed-b5f0-a7f9fd251ecf Germany (DE)782b575b-77d9-4949-9cc9-665b61fe57cc Denmark (DK)cb274626-f649-402f-9295-8cd578c10742 Poland (PL)7b56795d-fdcc-48d7-b80a-5314286b5b52 Poland (PL)3071c3b1-c8c7-47e0-97eb-075381187c3a Sweden (SE)33e98cee-0054-4629-bdea-ad215c19c860 Portugal (PT)
Order Code US and Canada
ZBBTEKBJ200A000000XX
EAN
8015644755089
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
366 mm
Product Net Height
371 mm
Product Net Depth / Length
270 mm
Product Net Weight
53 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
515 mm
Package Level 1 Height
610 mm
Package Level 1 Depth / Length
615 mm
Package Level 1 Gross Weight
58 kg
Package Level 1 EAN
8015644755089
Current Type
AC
Electrical Durability
Ue =< 440 V 10000 cycleUe = 500 ... 690 V 8000 cycle30 cycles per hour
Mechanical Durability
25000 cycle60 cycles per hour
Neutral Pole Current ([%Iu])
100 %
Number of Poles
4
Power Loss
212 W
Product Main Type
SACE Emax 2
Product Name
Air Circuit Breaker
Product Type
Air Circuit Breaker
Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics)
100 %
Rated Current (In)
2000 A
Rated Voltage (Ur)
690 V
Rated Impulse Withstand Voltage (Uimp)
acc. to IEC 60947-2 12 kV
Rated Insulation Voltage (Ui)
AC 1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 42 kA(230 V AC) 42 kA(380 V AC) 42 kA(400 V AC) 42 kA(415 V AC) 42 kA(440 V AC) 42 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 42 kAfor 3 s 42 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(400 V AC) 42 kA(415 V AC) 42 kA(440 V AC) 42 kA(500 V AC) 42 kA(525 V AC) 42 kA(690 V AC) 42 kA
Rated Uninterrupted Current (Iu)
2000 A
Recommended Screw Driver
Main Circuit M12
Release
Ekip Hi-Touch LSI
Release Type
EL
Short-Circuit Performance Level
B
Standards
IEC
Sub-type
E2.2
Terminal Connection Type
Rear flat Horizontal
Terminal Type
Bolt
Tightening Torque
70 N·m
Version
F
ETIM 7
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
IDEA Granular Category Code (IGCC)
4926 >> Air circuit breakers
Object Classification Code
Q
UNSPSC
39121615
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Datasheet