Trade Price
£6,355.89
Per
1
Unit
EA
Pack Quantity
1
C.BREAKER SACE EMAX2 E2.2B 1600 FIXED FOUR-POLE WITH TERMINALS REAR HORIZONTAL AND SOLID-STATE RELEASE IN AC EKIP/TOUCH-LI R 1600 FITTED WITH: 4 AUXILIARY CONTACT AND C.BREAKER IN POSITION OPEN-CLOSED
ABB EcoSolutions
Yes
Circular Design Principles Recyclability Rate
Design for Closing Resource Loops - Standard EN45555 - 79.1 %
Group Waste to Landfill Target
UL 2799 Zero Waste To Landfill Validation available
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
SCIP
b76917b2-3118-4ae8-ab6c-c9b187febfa6 Italy (IT)
Simplified SCIP
c2b30478-6474-46dd-b4b6-a00d4ec5a3b9 Poland (PL)f2774f31-c183-46bb-8542-f73eb7ac6da4 Hungary (HU)ae934500-898a-46a2-a034-8846a9ab861b Spain (ES)14baefdb-66da-4641-8039-562cc11d94ff Belgium (BE)f10db918-0aff-4b52-81ff-fdbc162112b7 France (FR)7dd93e35-c0c9-4503-aea3-d680aa23ce58 Finland (FI)65d39d35-3aa0-4c80-89f5-36a25472bb86 Netherlands (NL)b9971b0d-963d-450b-9253-71c836049e9d Poland (PL)fc96341e-7731-492c-88a2-26015e451d4f Norway (NO)fb4d8f21-d2eb-4fbb-a8c6-282d1f685311 Hungary (HU)f6db9496-b6e3-45e9-a662-c8d5d348db69 Sweden (SE)4ed7775f-f4c6-4574-af96-c07f319b0dec Greece (GR)bf0ff894-6577-4e6c-be69-23309283ad58 Estonia (EE)deb315dd-ded4-48bc-8229-8c8b3ff97349 Germany (DE)a9385cf2-5650-4140-a4af-dea15d786d26 Bulgaria (BG)21db4c19-032e-4de6-81c7-0fcda57bd3f6 Belgium (BE)80b2a29b-6108-4942-b26f-a9d2ec646c8d Germany (DE)334179a4-1c48-4df4-8233-97808e3a3add Denmark (DK)3ef1fcc9-d97f-49e3-8fb2-08125f50be1f Germany (DE)5790bf8f-cd8d-4738-b7a3-2bcdb91f84b8 Germany (DE)5d547f13-6757-413b-a56e-6061ca23dfe1 France (FR)c389bb78-5d26-4788-b332-d6a9d27a65ee Croatia (HR)376bbc87-4e71-4d70-b0f6-e3a486337723 Poland (PL)ac8bdc07-7735-4b63-946c-9eb901df7885 Sweden (SE)a7eb9686-583c-4d70-9dc9-7103942efb13 Portugal (PT)53addd3d-9b41-4260-a04b-435aee12e385 Czech Republic (CZ)
Order Code US and Canada
ZBBSEJBD000A000000XX
EAN
8015644754648
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
366 mm
Product Net Height
371 mm
Product Net Depth / Length
270 mm
Product Net Weight
53 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
515 mm
Package Level 1 Height
610 mm
Package Level 1 Depth / Length
615 mm
Package Level 1 Gross Weight
58 kg
Package Level 1 EAN
8015644754648
Current Type
AC
Electrical Durability
Ue =< 440 V 12000 cycleUe = 500 ... 690 V 10000 cycle30 cycles per hour
Mechanical Durability
25000 cycle60 cycles per hour
Neutral Pole Current ([%Iu])
100 %
Number of Poles
4
Power Loss
136 W
Product Main Type
SACE Emax 2
Product Name
Air Circuit Breaker
Product Type
Air Circuit Breaker
Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics)
100 %
Rated Current (In)
1600 A
Rated Voltage (Ur)
690 V
Rated Impulse Withstand Voltage (Uimp)
acc. to IEC 60947-2 12 kV
Rated Insulation Voltage (Ui)
AC 1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 42 kA(230 V AC) 42 kA(380 V AC) 42 kA(400 V AC) 42 kA(415 V AC) 42 kA(440 V AC) 42 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 42 kAfor 3 s 42 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(400 V AC) 42 kA(415 V AC) 42 kA(440 V AC) 42 kA(500 V AC) 42 kA(525 V AC) 42 kA(690 V AC) 42 kA
Rated Uninterrupted Current (Iu)
1600 A
Recommended Screw Driver
Main Circuit M12
Release
Ekip Touch LI
Release Type
EL
Short-Circuit Performance Level
B
Standards
IEC
Sub-type
E2.2
Terminal Connection Type
Rear flat Horizontal
Terminal Type
Bolt
Tightening Torque
70 N·m
Version
F
ETIM 7
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
IDEA Granular Category Code (IGCC)
4926 >> Air circuit breakers
Object Classification Code
Q
UNSPSC
39121615
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Datasheet