Trade Price
£6,492.25
Per
1
Unit
EA
Pack Quantity
1
MOVING PART FOR C.BREAKER SACE EMAX2 E1.2N 1600 THREE-POLE WITH SOLID-STATE RELEASE IN AC EKIP/TOUCH-LSIG R 1600 FITTED WITH: 4 AUXILIARY CONTACT AND C.BREAKER IN POSITION OPEN-CLOSED
ABB EcoSolutions
Yes
Circular Design Principles Recyclability Rate
Design for Closing Resource Loops - Standard EN45555 - 76.4 %
Group Waste to Landfill Target
UL 2799 Zero Waste To Landfill Validation available
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
SCIP
a5491858-a664-4778-87ee-3357be5f8bcd Italy (IT)
Simplified SCIP
e4a8a3a8-30c9-418e-b88f-82a0409b0021 Hungary (HU)c949be3b-f6a6-4adc-9756-b27b533b7a7e Poland (PL)8bec01f9-08c4-4cad-b44b-a4d69ac5b61e Czech Republic (CZ)08bdef96-93ce-4c34-aa5e-4f427b658e75 Bulgaria (BG)d153d035-fb07-4114-b08b-ad0e8fdb3631 Poland (PL)702f2faa-f2ee-451a-81fb-7699f90b36af Sweden (SE)44cb2c17-84cf-47c7-b254-700072e1d2d6 Portugal (PT)53333415-7a97-4db5-beba-2b538d7758cb Norway (NO)ac653024-ef88-49a2-8cc3-4e6354491bd9 Poland (PL)ef5dd609-df3e-4dbf-83da-32243ae4772e Hungary (HU)6b8b02bd-8d6a-476c-aca9-efe0a36db641 Germany (DE)3f5c8031-44ef-49ce-a237-fe005823a584 Denmark (DK)fd2cfcf3-45f4-43c9-bcf7-14535ba9d814 Belgium (BE)ae40d3ca-d5f0-4849-bc63-13e49baf2050 Greece (GR)18b7d600-6ad3-4c52-8a55-3887fa955f95 France (FR)b920982a-b2d3-4942-bc3d-6ce99c556630 Netherlands (NL)bc4c2026-c45d-4d46-a31a-de14f6853be7 Sweden (SE)95f84fb9-fdc9-4d5f-9739-8c3456ec6aca Estonia (EE)a2dee400-7e79-42ec-94a0-a24e50b9d530 Finland (FI)163e6e03-5a69-4eb5-8fbe-b910996f26bc France (FR)181cd06c-f1e8-474a-8328-5805af18f384 Croatia (HR)b6aff261-7205-4f09-a936-dcff290370ad Germany (DE)54d471af-f9d5-4adc-9f46-1e121b6d8ec6 Germany (DE)92903ab9-238c-4fea-b4e5-f1268db299d4 Germany (DE)296ac09d-9f33-4cea-90fc-4b8914deb567 Spain (ES)3a0eb27a-3790-4625-b001-e4658c6312d5 Belgium (BE)
Order Code US and Canada
Z1NSEJAF000A000000XX
EAN
8015644760861
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
278 mm
Product Net Height
363.5 mm
Product Net Depth / Length
271 mm
Product Net Weight
18 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
270 mm
Package Level 1 Height
350 mm
Package Level 1 Depth / Length
330 mm
Package Level 1 Gross Weight
20 kg
Package Level 1 EAN
8015644760861
Current Type
AC
Electrical Durability
Ue =< 440 V 3000 cycleUe = 500 ... 690 V 6500 cycle30 cycles per hour
Mechanical Durability
20000 cycle60 cycles per hour
Number of Poles
3
Power Loss
400 W
Product Main Type
SACE Emax 2
Product Name
Air Circuit Breaker
Product Type
Air Circuit Breaker
Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics)
100 %
Rated Current (In)
1600 A
Rated Voltage (Ur)
690 V
Rated Impulse Withstand Voltage (Uimp)
acc. to IEC 60947-2 12 kV
Rated Insulation Voltage (Ui)
AC 1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 66 kA(230 V AC) 66 kA(380 V AC) 66 kA(400 V AC) 50 kA(415 V AC) 50 kA(440 V AC) 50 kA(500 V AC) 50 kA(660 V AC) 50 kA(690 V AC) 50 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 50 kAfor 3 s 30 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(400 V AC) 66 kA(415 V AC) 66 kA(440 V AC) 66 kA(500 V AC) 50 kA(525 V AC) 50 kA(690 V AC) 50 kA
Rated Uninterrupted Current (Iu)
1600 A
Release
Ekip Touch LSIG
Release Type
EL
Short-Circuit Performance Level
N
Standards
IEC
Sub-type
E1.2
Version
W
ETIM 7
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
IDEA Granular Category Code (IGCC)
4926 >> Air circuit breakers
Object Classification Code
Q
UNSPSC
39121615
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Datasheet