MOVING PART FOR C.BREAKER SACE EMAX2 E1.2N 630 THREE-POLE WITH SOLID-STATE RELEASE IN AC EKIP/TOUCH-LSIG R 630 FITTED WITH: 4 AUXILIARY CONTACT AND C.BREAKER IN POSITION OPEN-CLOSED
ABB EcoSolutions
Yes
Circular Design Principles Recyclability Rate
Design for Closing Resource Loops - Standard EN45555 - 76.4 %
Group Waste to Landfill Target
UL 2799 Zero Waste To Landfill Validation available
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
SCIP
3ce22cc5-4f6a-4e28-b411-0ad3bf4c07ae Italy (IT)
Simplified SCIP
19041a08-6dde-41ab-b990-514ba89ec219 Hungary (HU)19c195a7-6629-468d-94bb-8104b83fc619 Belgium (BE)e1a3a3ea-edb8-4f3c-ab8d-3e33d648b67b Spain (ES)eec1cfe5-4c66-4cd3-b733-b646b8e10b10 Hungary (HU)173a9455-c4dd-4de2-bb7d-ba89e9c572be Norway (NO)c90a8576-4fbf-4d4e-ac76-2040af781eba Poland (PL)04af3b8d-21ff-47b5-87d6-8234da86eaf5 Greece (GR)2e3e3faf-e3d9-42e1-ac08-9f6a917060e4 Finland (FI)6107f667-aebf-4545-b9e7-dc50aeb649eb Netherlands (NL)3471ff3f-2a68-46ee-abfa-f875ab8cee14 France (FR)2ccdfe02-1ad1-4063-8d77-e3386100a4ee Sweden (SE)82cec120-23a7-40d3-80fb-67ed84cdd6a7 Estonia (EE)f7550928-9105-4878-bfc7-2e78e672ae94 Germany (DE)46d2ba64-f598-4b8c-b2f9-5de52ea127db Belgium (BE)d20c043e-6049-431f-a548-170b04e7b202 Denmark (DK)d0a7f520-2ba5-4165-b396-d102aca3d96d Germany (DE)bef03dda-6881-45d5-9515-d799cebaab26 France (FR)4de6cc58-a33b-4d7b-86f1-a20d778a8bfd Croatia (HR)428e0cbb-eaf2-4a49-a2d0-7680de6da9a3 Germany (DE)adb975de-8674-4e41-b6d9-db0fd64a554b Germany (DE)58fa8876-2779-4be3-8f27-3a5cc0bc6534 Bulgaria (BG)48f8dea5-e709-4870-8fec-7e0383a01b74 Portugal (PT)284fa083-c96c-478f-82db-dd56cf43e8c4 Sweden (SE)9cddc12c-3f6a-4213-bc33-23f379b4bbde Czech Republic (CZ)a15ff459-361e-4db2-bbeb-7503af2f9289 Poland (PL)cd9bb8a6-d9f1-47bb-81af-96b60a119a71 Poland (PL)
Order Code US and Canada
Z1NNEEAF000A000000XX
EAN
8015644759261
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
278 mm
Product Net Height
363.5 mm
Product Net Depth / Length
271 mm
Product Net Weight
18 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
270 mm
Package Level 1 Height
350 mm
Package Level 1 Depth / Length
330 mm
Package Level 1 Gross Weight
20 kg
Package Level 1 EAN
8015644759261
Current Type
AC
Electrical Durability
Ue =< 440 V 8000 cycleUe = 500 ... 690 V 8000 cycle30 cycles per hour
Mechanical Durability
20000 cycle60 cycles per hour
Number of Poles
3
Power Loss
62 W
Product Main Type
SACE Emax 2
Product Name
Air Circuit Breaker
Product Type
Air Circuit Breaker
Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics)
100 %
Rated Current (In)
630 A
Rated Voltage (Ur)
690 V
Rated Impulse Withstand Voltage (Uimp)
acc. to IEC 60947-2 12 kV
Rated Insulation Voltage (Ui)
AC 1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 66 kA(230 V AC) 66 kA(380 V AC) 66 kA(400 V AC) 50 kA(415 V AC) 50 kA(440 V AC) 50 kA(500 V AC) 50 kA(660 V AC) 50 kA(690 V AC) 50 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 50 kAfor 3 s 30 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(400 V AC) 66 kA(415 V AC) 66 kA(440 V AC) 66 kA(500 V AC) 50 kA(525 V AC) 50 kA(690 V AC) 50 kA
Rated Uninterrupted Current (Iu)
630 A
Release
Ekip Touch LSIG
Release Type
EL
Short-Circuit Performance Level
N
Standards
IEC
Sub-type
E1.2
Version
W
ETIM 7
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
IDEA Granular Category Code (IGCC)
4926 >> Air circuit breakers
Object Classification Code
Q
UNSPSC
39121615
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409