Trade Price
£3,642.40
Per
1
Unit
EA
Pack Quantity
1
MOVING PART FOR C.BREAKER SACE EMAX2 E1.2C 1600 THREE-POLE WITH SOLID-STATE RELEASE IN AC EKIP/DIP-LI R 1600 FITTED WITH: 4 AUXILIARY CONTACT AND C.BREAKER IN POSITION OPEN-CLOSED
ABB EcoSolutions
Yes
Circular Design Principles Recyclability Rate
Design for Closing Resource Loops - Standard EN45555 - 76.4 %
Group Waste to Landfill Target
UL 2799 Zero Waste To Landfill Validation available
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
SCIP
db963041-0b5f-4fbf-9732-72373e7d01bc Italy (IT)
Simplified SCIP
516f8cdb-1e52-49fe-9d92-bcd60f6359a1 Poland (PL)b6dd9043-fcde-464b-a7b0-bf20490cdb0c Poland (PL)07f0cc50-936b-4311-9730-d3c2c2841cda Czech Republic (CZ)086a6eda-3e3e-4c3a-8b46-5bf87693bc22 Portugal (PT)07add197-52b2-4190-bbdb-c08fc89cf30c Bulgaria (BG)8e6dbbc9-1357-4929-a2b0-c7f324b2543e Sweden (SE)fa1e6d1b-6482-4c97-adde-370326165dde Belgium (BE)b83eb728-6f95-448d-bc9d-c8dea752c1a0 Spain (ES)70f9e7c9-243b-4ad7-90d2-f7e034729b42 Hungary (HU)e7ddd871-49d4-4878-9b0e-e73199b42db3 Poland (PL)52ca09bd-46ca-4ef9-94de-a3b84c7136b5 Norway (NO)f3ea1491-4bbc-494b-aa65-3ac22aa2dbec Germany (DE)ac41343b-e4b8-488f-8870-bc40599b81d5 Croatia (HR)0049aa51-ba89-4c5a-8ba6-0f1f33ccd576 Germany (DE)ea4a85b9-07fc-4e7e-abe1-228c038d56c6 Germany (DE)b74db57b-6d4a-4263-8b97-ac79f228d5d2 Germany (DE)e4610b46-c16b-4abb-84fc-a7cf915d97fe Denmark (DK)fefa0613-8212-4579-b97b-37bc963a153e Belgium (BE)2e9c2fb8-f428-4aae-b7df-b2ed68659b15 Estonia (EE)cbbe2aa1-898d-4b7d-ab59-0bdb4fd00abd Netherlands (NL)09dbe8a3-862f-4f5a-8927-d17c9c5a2757 Finland (FI)e3edfea4-1427-4762-b495-a8820818adf0 Greece (GR)a2a925bc-4e11-4fa8-b27e-11ad24eabb81 France (FR)51458665-f47c-428d-9979-87c84ab80cb5 Sweden (SE)e8116ff8-fdb9-4ed6-8779-86810ef1f2cb France (FR)ddbc78f1-2249-45e1-9c6a-8e3020c08d28 Hungary (HU)
Order Code US and Canada
Z1CSEJAA000A000000XX
EAN
8015644760717
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
278 mm
Product Net Height
363.5 mm
Product Net Depth / Length
271 mm
Product Net Weight
18 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
270 mm
Package Level 1 Height
350 mm
Package Level 1 Depth / Length
330 mm
Package Level 1 Gross Weight
20 kg
Package Level 1 EAN
8015644760717
Current Type
AC
Electrical Durability
Ue =< 440 V 3000 cycleUe = 500 ... 690 V 6500 cycle30 cycles per hour
Mechanical Durability
20000 cycle60 cycles per hour
Number of Poles
3
Power Loss
400 W
Product Main Type
SACE Emax 2
Product Name
Air Circuit Breaker
Product Type
Air Circuit Breaker
Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics)
100 %
Rated Current (In)
1600 A
Rated Voltage (Ur)
690 V
Rated Impulse Withstand Voltage (Uimp)
acc. to IEC 60947-2 12 kV
Rated Insulation Voltage (Ui)
AC 1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 50 kA(230 V AC) 50 kA(380 V AC) 50 kA(400 V AC) 50 kA(415 V AC) 50 kA(440 V AC) 50 kA(500 V AC) 42 kA(660 V AC) 42 kA(690 V AC) 42 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 42 kAfor 3 s 24 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(400 V AC) 50 kA(415 V AC) 50 kA(440 V AC) 50 kA(500 V AC) 42 kA(525 V AC) 42 kA(690 V AC) 42 kA
Rated Uninterrupted Current (Iu)
1600 A
Release
Ekip Dip LI
Release Type
EL
Short-Circuit Performance Level
C
Standards
IEC
Sub-type
E1.2
Version
W
ETIM 7
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
IDEA Granular Category Code (IGCC)
4926 >> Air circuit breakers
Object Classification Code
Q
UNSPSC
39121615
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409