Trade Price
£2,782.40
Per
1
Unit
EA
Pack Quantity
1
MOVING PART FOR C.BREAKER SACE EMAX2 E1.2C 630 THREE-POLE WITH SOLID-STATE RELEASE IN AC EKIP/DIP-LSI R 630 FITTED WITH: 4 AUXILIARY CONTACT AND C.BREAKER IN POSITION OPEN-CLOSED
ABB EcoSolutions
Yes
Circular Design Principles Recyclability Rate
Design for Closing Resource Loops - Standard EN45555 - 76.4 %
Group Waste to Landfill Target
UL 2799 Zero Waste To Landfill Validation available
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
SCIP
72e59724-c663-4e32-96da-9046e6041459 Italy (IT)
Simplified SCIP
b5c4b82f-9016-4cae-8f39-7ce8afe52ad7 Sweden (SE)b1418205-a79a-4775-8143-541ae0973409 Poland (PL)4791b573-aba7-4d91-ae03-2e245d926e23 Belgium (BE)35b15014-7265-4d2a-b737-4eac590db788 Norway (NO)bd565c6c-7d25-4a1c-a655-896059ec6721 Poland (PL)25a0d197-85f4-4b70-8de5-64a9ff9335db France (FR)5faaa75d-4be1-4c4f-b46d-60bd6aa4c1a5 Croatia (HR)3e3d0ec5-61b3-4f55-8926-536cbbaf2c0e Sweden (SE)e35780f5-0a12-40e8-ab30-695800767c24 Finland (FI)caf3fc7d-3462-4e47-a304-dc154c632e04 Germany (DE)996eb4e9-7f44-4e48-807d-f0a22f38eeeb France (FR)21704a53-4fd0-43bd-aaf0-f20cb4218df3 Germany (DE)09b27337-f7fb-42cc-965e-b8d309480394 Germany (DE)4a7dc21c-cca6-4646-814b-b688d90a6dac Netherlands (NL)db8c63ce-5cef-44d0-bf4f-13af802fa9e5 Belgium (BE)407c92ee-8952-46d4-a084-836a3d53c3c5 Czech Republic (CZ)ca5466d1-37df-4c66-9548-022cd4ec4abe Poland (PL)f68feded-7410-49fe-9567-ddc730ada469 Hungary (HU)8873b133-0eb2-400c-8d61-93a088be52d4 Spain (ES)47dbca06-e25f-4ee5-8926-4d15e93a9e2c Germany (DE)b4154a5a-3288-4044-bd2e-6288dc735cb5 Portugal (PT)ee4ad8a5-a5e2-4d72-afd5-b257d5d70a9b Bulgaria (BG)24148717-8f3c-4b1d-b4ee-3113fed94607 Denmark (DK)7e014499-6ae3-4a0a-ae34-f836a4538712 Estonia (EE)28f77918-c9c5-4476-bfb2-476021ad5d21 Greece (GR)ba9ce17e-080d-442b-8f86-859b4ac3bd0e Hungary (HU)
Order Code US and Canada
Z1CNEEAB000A000000XX
EAN
8015644759124
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
278 mm
Product Net Height
363.5 mm
Product Net Depth / Length
271 mm
Product Net Weight
18 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
270 mm
Package Level 1 Height
350 mm
Package Level 1 Depth / Length
330 mm
Package Level 1 Gross Weight
20 kg
Package Level 1 EAN
8015644759124
Current Type
AC
Electrical Durability
Ue =< 440 V 8000 cycleUe = 500 ... 690 V 8000 cycle30 cycles per hour
Mechanical Durability
20000 cycle60 cycles per hour
Number of Poles
3
Power Loss
62 W
Product Main Type
SACE Emax 2
Product Name
Air Circuit Breaker
Product Type
Air Circuit Breaker
Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics)
100 %
Rated Current (In)
630 A
Rated Voltage (Ur)
690 V
Rated Impulse Withstand Voltage (Uimp)
acc. to IEC 60947-2 12 kV
Rated Insulation Voltage (Ui)
AC 1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 50 kA(230 V AC) 50 kA(380 V AC) 50 kA(400 V AC) 50 kA(415 V AC) 50 kA(440 V AC) 50 kA(500 V AC) 42 kA(660 V AC) 42 kA(690 V AC) 42 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 42 kAfor 3 s 24 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(400 V AC) 50 kA(415 V AC) 50 kA(440 V AC) 50 kA(500 V AC) 42 kA(525 V AC) 42 kA(690 V AC) 42 kA
Rated Uninterrupted Current (Iu)
630 A
Release
Ekip Dip LSI
Release Type
EL
Short-Circuit Performance Level
C
Standards
IEC
Sub-type
E1.2
Version
W
ETIM 7
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
IDEA Granular Category Code (IGCC)
4926 >> Air circuit breakers
Object Classification Code
Q
UNSPSC
39121615
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Datasheet