Trade Price
£30,534.47
Per
1
Unit
EA
Pack Quantity
1
MOVING PART FOR C.BREAKER SACE EMAX2 E6.2H/f 4000 FOUR-POLE FULL SIZE NEUTRAL WITH SOLID-STATE RELEASE IN AC EKIP/G/HI/TOUCH-LSIG R 4000 FITTED WITH: 4 AUXILIARY CONTACT AND C.BREAKER IN POSITION OPEN-CLOSED
ABB EcoSolutions
Yes
Circular Design Principles Recyclability Rate
Design for Closing Resource Loops - Standard EN45555 - 77 %
Group Waste to Landfill Target
UL 2799 Zero Waste To Landfill Validation available
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Order Code US and Canada
ZEHWERAQ200A000000XX
EAN
8015644771607
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
1069 mm
Product Net Height
425 mm
Product Net Depth / Length
383 mm
Product Net Weight
148 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
515 mm
Package Level 1 Height
610 mm
Package Level 1 Depth / Length
1257 mm
Package Level 1 Gross Weight
159 kg
Package Level 1 EAN
8015644771607
Current Type
AC
Electrical Durability
Ue =< 440 V 4000 cycleUe = 500 ... 690 V 4000 cycle10 cycles per hour
Mechanical Durability
12000 cycle60 cycles per hour
Neutral Pole Current ([%Iu])
100 %
Number of Poles
4 / f
Power Loss
544 W
Product Main Type
SACE Emax 2
Product Name
Air Circuit Breaker
Product Type
Air Circuit Breaker
Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics)
100 %
Rated Current (In)
4000 A
Rated Voltage (Ur)
690 V
Rated Impulse Withstand Voltage (Uimp)
acc. to IEC 60947-2 12 kV
Rated Insulation Voltage (Ui)
AC 1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA(230 V AC) 100 kA(380 V AC) 100 kA(400 V AC) 100 kA(415 V AC) 100 kA(440 V AC) 100 kA(500 V AC) 100 kA(660 V AC) 100 kA(690 V AC) 100 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 100 kAfor 3 s 100 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(400 V AC) 100 kA(415 V AC) 100 kA(440 V AC) 100 kA(500 V AC) 100 kA(525 V AC) 100 kA(690 V AC) 100 kA
Rated Uninterrupted Current (Iu)
4000 A
Release
Ekip G Hi-Touch LSIG
Release Type
EL
Short-Circuit Performance Level
H
Standards
IEC
Sub-type
E6.2
Version
W
ETIM 7
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
WEEE Category
4. Large Equipment (Any External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Datasheet