1SDA072330R1

E2.2H 1250 Ekip G Hi-Touch LSIG 3p WMP

Trade Price

£10,320.15

Per

1

Unit

EA

Pack Quantity

1

1SDA072330R1

Information

MOVING PART FOR C.BREAKER SACE EMAX2 E2.2H 1250 THREE-POLE WITH SOLID-STATE RELEASE IN AC EKIP/G/HI-TOUCH-LSIG R 1250 FITTED WITH: 4 AUXILIARY CONTACT AND C.BREAKER IN POSITION OPEN-CLOSED

Technical Specifications

ABB EcoSolutions

Yes

Circular Design Principles Recyclability Rate

Design for Closing Resource Loops - Standard EN45555 - 79.1 %

Group Waste to Landfill Target

UL 2799 Zero Waste To Landfill Validation available

RoHS Status

Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019

Order Code US and Canada

Z2HREHAQ200A000000XX

EAN

8015644761806

Minimum Order Quantity

1 piece

Customs Tariff Number

85362090

Product Net Width

317 mm

Product Net Height

425 mm

Product Net Depth / Length

383 mm

Product Net Weight

48 kg

Package Level 1 Units

box 1 piece

Package Level 1 Width

515 mm

Package Level 1 Height

610 mm

Package Level 1 Depth / Length

515 mm

Package Level 1 Gross Weight

53 kg

Package Level 1 EAN

8015644761806

Current Type

AC

Electrical Durability

Ue =< 440 V 15000 cycleUe = 500 ... 690 V 15000 cycle30 cycles per hour

Mechanical Durability

25000 cycle60 cycles per hour

Number of Poles

3

Power Loss

176 W

Product Main Type

SACE Emax 2

Product Name

Air Circuit Breaker

Product Type

Air Circuit Breaker

Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics)

100 %

Rated Current (In)

1250 A

Rated Voltage (Ur)

690 V

Rated Impulse Withstand Voltage (Uimp)

acc. to IEC 60947-2 12 kV

Rated Insulation Voltage (Ui)

AC 1000 V

Rated Operational Voltage

690 V AC

Rated Service Short-Circuit Breaking Capacity (Ics)

(220 V AC) 100 kA(230 V AC) 100 kA(380 V AC) 100 kA(400 V AC) 100 kA(415 V AC) 100 kA(440 V AC) 100 kA(500 V AC) 85 kA(660 V AC) 85 kA(690 V AC) 85 kA

Rated Short-time Withstand Current Low Voltage (Icw)

for 1 s 85 kAfor 3 s 66 kA

Rated Ultimate Short-Circuit Breaking Capacity (Icu)

(400 V AC) 100 kA(415 V AC) 100 kA(440 V AC) 100 kA(500 V AC) 85 kA(525 V AC) 85 kA(690 V AC) 85 kA

Rated Uninterrupted Current (Iu)

1250 A

Release

Ekip G Hi-Touch LSIG

Release Type

EL

Short-Circuit Performance Level

H

Standards

IEC

Sub-type

E2.2

Version

W

ETIM 7

EC000228 - Power circuit-breaker for trafo/generator/installation protection

ETIM 8

EC000228 - Power circuit-breaker for trafo/generator/installation protection

ETIM 9

EC000228 - Power circuit-breaker for trafo/generator/installation protection

IDEA Granular Category Code (IGCC)

4926 >> Air circuit breakers

Object Classification Code

Q

UNSPSC

39121615

WEEE Category

5. Small Equipment (No External Dimension More Than 50 cm)

eClass

V11.1 : 27370409

Document Links

Catalogue page

Datasheet