56293

RH99P 220/240 V AC 50/60 Hz

Trade Price

£353.24

Per

1

Unit

EA

Pack Quantity

1

56293

Information

VigiPacT RH99P is a DIN rail mounting residual current monitoring relay. It monitor drops in electrical insulation due to ageing of cables or extensions in the installation. It measures the earth leakage current in an electrical installation via its associated toroid. A control signal is issued by the relay when the residual-current operating threshold is overrun. The operational supply voltage is 220/240VAC 50/60Hz. It is a type A earth-leakage protection class. The current sensitivity is selectable with 9 thresholds from 30 mA to 30 A. The time delay is selectable with 9 settings from instantaneous to 4.5s. There is an automatic reset after a fault clearance. The monitored distribution system voltage is up to 1000 VAC 50/60/400 Hz. It is installed on a front panel switchboard and the protection degree is IP40. It must be associated with a compatible Schneider Electric type A toroid or rectangular sensor.

Technical Specifications

Range

VigiPacT

Device short name

RH99P

Product or component type

Monitoring relay

Relay application

Monitoring relay

mounting support

Front panel

Type of setting

Selector

Residual earth-leakage sensitity adjustment type

Adjustable 9 settings

Earth-leakage sensitivity

0.03…30 A

Earth-leakage time delay

Instantaneous for 0.03 A Adjustable 9 settings 0…4.5 s for 0.03…30 A

Threshold setting

0.03...30 A alarm

Current sensors compatibility

VigiPacT TOA earth leakage current sensor VigiPacT A earth leakage current sensor VigiPacT L earth leakage current sensor

[Ithe] conventional enclosed thermal current

8 A

Minimum load

10 mA at 12 V

[Us] rated supply voltage

220...240 V AC 50/60 Hz 70...110 %

Power consumption in VA

4 VA

Monitored distribution system

1000 V - AC at 50/60 Hz (maximum) 1000 V - AC at 400 Hz (maximum)

Earthing system

TN-S TT

[Uimp] rated impulse withstand voltage

8 kV

Test function

Local Remote test

Monitoring

Electronics (continuous) Power supply (continuous) Relay/sensor link (continuous)

Type of measurement

Earth fault current internal measurement, range: 80...100 %

Tamperproof of settings

Protected by sealable cover

Connections - terminals

Auxiliary power supply: terminal block cable(s) 0.2…2.5 mm² flexible AWG 24...AWG 12 Auxiliary power supply: terminal block cable(s) 0.2…2.5 mm² rigid AWG 24...AWG 12 Auxiliary power supply: terminal block cable(s) 0.25…2.5 mm² flexible with ferrule AWG 24...AWG 12 Fault: terminal block cable(s) 0.2…2.5 mm² flexible AWG 24...AWG 12 Fault: terminal block cable(s) 0.2…2.5 mm² rigid AWG 24...AWG 12 Fault: terminal block cable(s) 0.25…2.5 mm² flexible with ferrule AWG 24...AWG 12 Relay test and fault reset: terminal block cable(s) 0.2…2.5 mm² flexible AWG 24...AWG 12 Relay test and fault reset: terminal block cable(s) 0.2…2.5 mm² rigid AWG 24...AWG 12 Relay test and fault reset: terminal block cable(s) 0.25…2.5 mm² flexible with ferrule AWG 24...AWG 12 Sensor: terminal block cable(s) 0.2…2.5 mm² flexible AWG 24...AWG 12 Sensor: terminal block cable(s) 0.2…2.5 mm² rigid AWG 24...AWG 12 Sensor: terminal block cable(s) 0.25…2.5 mm² flexible with ferrule AWG 24...AWG 12 Voltage presence: terminal block cable(s) 0.2…2.5 mm² flexible AWG 24...AWG 12 Voltage presence: terminal block cable(s) 0.2…2.5 mm² rigid AWG 24...AWG 12 Voltage presence: terminal block cable(s) 0.25…2.5 mm² flexible with ferrule AWG 24...AWG 12

Wire stripping length

Auxiliary power supply: 7 mm Fault: 7 mm Relay test and fault reset: 7 mm Sensor: 7 mm Voltage presence: 7 mm

Tightening torque

Auxiliary power supply: 0.6 N.m Fault: 0.6 N.m Relay test and fault reset: 0.6 N.m Sensor: 0.6 N.m Voltage presence: 0.6 N.m

Width

72 mm

height

72 mm

Depth

78 mm

Cut-out dimensions

68 x 68 mm

Net weight

0.3 kg

IP degree of protection

IP40 on front face: conforming to EN/IEC 60529 IP30 on side parts: conforming to EN/IEC 60529 IP20 on connection terminals: conforming to EN/IEC 60529

IK degree of protection

IK07 conforming to EN 50102

Mechanical robustness

Fire resistance conforming to IEC 60695-2-1 IK protection 2 joules: IK07 conforming to EN 50102 Vibrations 13.2...100 Hz: 0.7 g Vibrations 2...13.2 Hz: +/- 1 mm

Overvoltage category

IV

Electrical shock protection class

Class II

Electromagnetic compatibility

Conducted and radiated emissions: , B, conforming to CISPR 11 Conducted radio-frequency immunity test: , 3, conforming to IEC 61000-4-6 Electrostatic discharge immunity test: , 4, conforming to IEC 61000-4-2 High-energy conducted susceptibility: , 4, conforming to IEC 61000-4-5 Low-energy conducted susceptibility: , 4, conforming to IEC 61000-4-4 Radiated susceptibility: , 3, conforming to IEC 61000-4-3

Relative humidity

95 % at 55 °C

Pollution degree

3 conforming to IEC 60664-1

Ambient air temperature for operation

-35…70 °C

Ambient air temperature for storage

-55…85 °C

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

7.800 cm

Package 1 Width

8.700 cm

Package 1 Length

9.300 cm

Package 1 Weight

306.000 g

Unit Type of Package 2

S02

Number of Units in Package 2

12

Package 2 Height

15.000 cm

Package 2 Width

30.000 cm

Package 2 Length

40.000 cm

Package 2 Weight

4.159 kg

Warranty

18 months