Trade Price
£250.65
Per
1
Unit
EA
Pack Quantity
1
Range
VigiPacT
Device short name
RH10M
Product or component type
Residual current protection relay
Relay application
Protection relay
mounting support
DIN rail
Earth-leakage protection class
Type A
Type of setting
None
Residual earth-leakage sensitity adjustment type
Fixed
Earth-leakage sensitivity
0.1 A
Earth-leakage time delay
Instantaneous
Current sensors compatibility
VigiPacT TOA earth leakage current sensor VigiPacT A earth leakage current sensor VigiPacT L earth leakage current sensor
[Ithe] conventional enclosed thermal current
8 A
Minimum load
10 mA at 12 V
[Us] rated supply voltage
110...130 V AC 50/60 Hz 55...110 %
Power consumption in VA
4 VA
Monitored distribution system
1000 V - AC at 50/60 Hz (maximum) 1000 V - AC at 400 Hz (maximum)
Earthing system
IT TN-S TT
[Uimp] rated impulse withstand voltage
8 kV
Reset
Manual reset
Test function
Remote test Local
Monitoring
Electronics (continuous) Power supply (continuous) Relay/sensor link (continuous)
Type of measurement
Earth fault current internal measurement, range: 80...100 %
Tamperproof of settings
Protected by sealable cover
Connections - terminals
Auxiliary power supply: terminal block cable(s) 0.2…2.5 mm² flexible AWG 24...AWG 12 Auxiliary power supply: terminal block cable(s) 0.2…2.5 mm² rigid AWG 24...AWG 12 Auxiliary power supply: terminal block cable(s) 0.25…2.5 mm² flexible AWG 24...AWG 12 Fault: screw terminal cable(s) 0.2…2.5 mm² flexible AWG 24...AWG 12 Fault: screw terminal cable(s) 0.2…4 mm² rigid AWG 24...AWG 12 Fault: screw terminal cable(s) 0.25…2.5 mm² flexible AWG 24...AWG 12 Relay test and fault reset: screw terminal cable(s) 0.14…1 mm² flexible AWG 26...AWG 16 Relay test and fault reset: screw terminal cable(s) 0.14…1.5 mm² rigid AWG 26...AWG 16 Relay test and fault reset: screw terminal cable(s) 0.25…0.5 mm² flexible AWG 26...AWG 16 Sensor: screw terminal cable(s) 0.14…1 mm² flexible AWG 26...AWG 16 Sensor: screw terminal cable(s) 0.14…1.5 mm² rigid AWG 26...AWG 16 Sensor: screw terminal cable(s) 0.25…0.5 mm² flexible AWG 26...AWG 16 Voltage presence: screw terminal cable(s) 0.2…2.5 mm² flexible AWG 24...AWG 12 Voltage presence: screw terminal cable(s) 0.2…4 mm² rigid AWG 24...AWG 12 Voltage presence: screw terminal cable(s) 0.25…2.5 mm² flexible AWG 24...AWG 12
Wire stripping length
Auxiliary power supply: 7 mm for top connection Fault: 8 mm for bottom connection Relay test and fault reset: 5 mm for bottom connection Sensor: 5 mm for top connection Voltage presence: 8 mm for bottom connection
Tightening torque
Auxiliary power supply: 0.6 N.m top Fault: 0.6 N.m bottom Relay test and fault reset: 0.25 N.m bottom Sensor: 0.25 N.m top Voltage presence: 0.6 N.m bottom
9 mm pitches
6
Width
54 mm
height
81 mm
Depth
74 mm
Net weight
0.3 kg
IP degree of protection
IP40 on front face: conforming to EN/IEC 60529 IP30 on side parts: conforming to EN/IEC 60529 IP20 on connection terminals: conforming to EN/IEC 60529
IK degree of protection
IK07 conforming to EN 50102
Mechanical robustness
Fire resistance conforming to IEC 60695-2-1 IK protection 2 joules: IK07 conforming to EN 50102 Vibrations 13.2...100 Hz: 0.7 g Vibrations 2...13.2 Hz: +/- 1 mm
Overvoltage category
IV
Electrical shock protection class
Class II
Electromagnetic compatibility
Conducted and radiated emissions: , B, conforming to CISPR 11 Conducted radio-frequency immunity test: , 3, conforming to IEC 61000-4-6 Electrostatic discharge immunity test: , 4, conforming to IEC 61000-4-2 High-energy conducted susceptibility: , 4, conforming to IEC 61000-4-5 Low-energy conducted susceptibility: , 4, conforming to IEC 61000-4-4 Radiated susceptibility: , 3, conforming to IEC 61000-4-3
Relative humidity
95 % at 55 °C
Pollution degree
3 conforming to IEC 60664-1
Ambient air temperature for operation
-35…70 °C
Ambient air temperature for storage
-55…85 °C
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
0.1 cm
Package 1 Width
8 cm
Package 1 Length
8 cm
Package 1 Weight
3 kg
Warranty
18 months