33511

Micrologic Control Unit 5.0

Trade Price

£1,518.52

Per

1

Unit

EA

Pack Quantity

1

33511

Information

Micrologic 5.0 is an electronic trip unit used on Compact NS630b to NS3200 circuit breakers. This control unit has a selective protection and is designed to protect power circuits and loads. It embeds adjustable long time protection against overloads. It provides also adjustable short-time protection and instantaneous protection against short-circuits. Micrologic 5.0 indicates overloads with an Alarm LED. This trip unit can be associated with Compact NS basic frame.

Technical Specifications

Range

ComPact

Range of product

ComPact NS1600b...3200 ComPact NS630b...1600

Product or component type

Trip unit

Trip unit name

MicroLogic 5.0

Trip unit technology

Electronic

Range compatibility

ComPact NS1600b...3200 ComPact NS630b...1600

Device application

Distribution

Number of poles

4P 3P

Protected poles description

3t 3t + N/2 4t

Trip unit protection functions

Selective protection

Protection type

for short time short-circuit protection for overload protection (long time) for instantaneous short-circuit protection

Trip unit rating

630 A at 50 °C 800 A at 50 °C 1000 A at 50 °C 1250 A at 50 °C 1600 A at 50 °C 2000 A at 50 °C 2500 A at 50 °C 3200 A at 50 °C

Network type

AC

Network frequency

50/60 Hz

Circuit breaker mounting mode

Drawout Fixed

Long-time pick-up adjustment type Ir (thermal protection)

Adjustable 9 settings

[Ir] long-time protection pick-up adjustment range

0.4...1 x In

Long-time protection delay adjustment type tr

Adjustable 9 settings

[tr] long-time protection delay adjustment range

0.7…16.6 s at 7.2 x Ir 0.5…24 s at 6 x Ir 12.5…600 s at 1.5 x Ir

Thermal memory

20 mn

Short-time protection pick-up adjustment type Isd

Adjustable 9 settings

[Isd] Short-time protection pick-up adjustment range

1.5...10 x Ir

Short-time protection delay adjustment type tsd

Adjustable

[tsd] Short-time protection delay adjustment range

0…0.4 s I²t=off 0.1…0.4 s I²t=on

Instantaneous protection pick-up adjustment type Ii

Adjustable 9 settings

[Ii] instantaneous protection pick-up adjustment range

2...15 x In Off

earth-leakage protection

Without

Zone selective interlocking ZSI

Without

Local signalling

3 LEDs (red) for electrical fault 1 LED (red) for internal error

Ambient air temperature for operation

-25…70 °C

Ambient air temperature for storage

-50…85 °C

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

6.9 cm

Package 1 Width

8.0 cm

Package 1 Length

21.5 cm

Package 1 Weight

190.0 g

Warranty

18 months

Document Links

Catalogue page

Datasheet