Trade Price
£1,518.52
Per
1
Unit
EA
Pack Quantity
1
Micrologic 5.0 is an electronic trip unit used on Compact NS630b to NS3200 circuit breakers. This control unit has a selective protection and is designed to protect power circuits and loads. It embeds adjustable long time protection against overloads. It provides also adjustable short-time protection and instantaneous protection against short-circuits. Micrologic 5.0 indicates overloads with an Alarm LED. This trip unit can be associated with Compact NS basic frame.
Range
ComPact
Range of product
ComPact NS1600b...3200 ComPact NS630b...1600
Product or component type
Trip unit
Trip unit name
MicroLogic 5.0
Trip unit technology
Electronic
Range compatibility
ComPact NS1600b...3200 ComPact NS630b...1600
Device application
Distribution
Number of poles
4P 3P
Protected poles description
3t 3t + N/2 4t
Trip unit protection functions
Selective protection
Protection type
for short time short-circuit protection for overload protection (long time) for instantaneous short-circuit protection
Trip unit rating
630 A at 50 °C 800 A at 50 °C 1000 A at 50 °C 1250 A at 50 °C 1600 A at 50 °C 2000 A at 50 °C 2500 A at 50 °C 3200 A at 50 °C
Network type
AC
Network frequency
50/60 Hz
Circuit breaker mounting mode
Drawout Fixed
Long-time pick-up adjustment type Ir (thermal protection)
Adjustable 9 settings
[Ir] long-time protection pick-up adjustment range
0.4...1 x In
Long-time protection delay adjustment type tr
Adjustable 9 settings
[tr] long-time protection delay adjustment range
0.7…16.6 s at 7.2 x Ir 0.5…24 s at 6 x Ir 12.5…600 s at 1.5 x Ir
Thermal memory
20 mn
Short-time protection pick-up adjustment type Isd
Adjustable 9 settings
[Isd] Short-time protection pick-up adjustment range
1.5...10 x Ir
Short-time protection delay adjustment type tsd
Adjustable
[tsd] Short-time protection delay adjustment range
0…0.4 s I²t=off 0.1…0.4 s I²t=on
Instantaneous protection pick-up adjustment type Ii
Adjustable 9 settings
[Ii] instantaneous protection pick-up adjustment range
2...15 x In Off
earth-leakage protection
Without
Zone selective interlocking ZSI
Without
Local signalling
3 LEDs (red) for electrical fault 1 LED (red) for internal error
Ambient air temperature for operation
-25…70 °C
Ambient air temperature for storage
-50…85 °C
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
6.9 cm
Package 1 Width
8.0 cm
Package 1 Length
21.5 cm
Package 1 Weight
190.0 g
Warranty
18 months
Datasheet