33255

NS1250H 4P Basic Frame Manually O

Trade Price

£4,171.10

Per

1

Unit

EA

Pack Quantity

1

33255

Information

This is a Compact NS1250H circuit breaker basic frame, 1250A, 70kA at 415 VAC 50/60 Hz, 4 poles . It is adapted for fixed devices manually operated, and it is an optimum choice for all standard applications. This basic frame is compatible with any type of trip unit which has to be ordered separately. It can be equipped with a variety of optional functions and accessories. The dimensions are 327mm (W) x 280mm (H) x 147mm (D). It ensures compliance with international standards (IEC 60947), CCC, EAC and marine specifications.

Technical Specifications

Range

ComPact

Range of product

ComPact NS630b...1600

Device short name

Compact NS1250H

Product or component type

Basic frame

Device application

Distribution

Number of poles

4P

Neutral position

Left

[In] rated current

1250 A at 50 °C

[Ue] rated operational voltage

690 V AC 50/60 Hz

Network type

AC

Network frequency

50/60 Hz

Suitability for isolation

Yes conforming to EN/IEC 60947-2

utilisation category

Category B

[Icu] rated ultimate short-circuit breaking capacity

85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2

Performance level

H 70 kA 415 V AC

Control type

Toggle Rotary handle

Mounting mode

Fixed

[Ui] rated insulation voltage

800 V AC 50/60 Hz conforming to IEC 60947-2

[Uimp] rated impulse withstand voltage

8 kV conforming to IEC 60947-2

[Ics] rated service short-circuit breaking capacity

30 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 (manual operation) 40 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 (manual operation) 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 (manual operation) 50 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 (manual operation) 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 (manual operation)

[Icw] rated short-time withstand current

19.2 kA 1 s conforming to IEC 60947-2

Integral instant protection

40 kA

Mechanical durability

10000 cycles conforming to IEC 60947-2

Electrical durability

2000 cycles 690 V AC 50/60 Hz In conforming to IEC 60947-2 3000 cycles 690 V AC 50/60 Hz In/2 conforming to IEC 60947-2 4000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947-2 5000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947-2

Power losses

44 W

mounting support

Backplate

Connection pitch

70 mm

Protection type

Without protection

Height (H)

327 mm

Width (W)

280 mm

Depth (D)

147 mm

standards

IEC 60947-2

product certifications

LCIE ASTA ASEFA

Pollution degree

3 conforming to IEC 60947

IP degree of protection

IP40 conforming to IEC 60529

IK degree of protection

IK07 conforming to EN 50102

Ambient air temperature for operation

-25…70 °C

Ambient air temperature for storage

-50…85 °C

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

37.0 cm

Package 1 Width

38.0 cm

Package 1 Length

30.0 cm

Package 1 Weight

14.731 kg

Warranty

18 months

Document Links

Catalogue page