Trade Price
£6,047.07
Per
1
Unit
EA
Pack Quantity
1
This is a Compact NS1600N circuit breaker basic frame, 1600A, 50kA at 415 VAC 50/60 Hz, 4 poles . It is adapted for withdrawable devices electrically operated, and it is an optimum choice for all standard applications. This basic frame is compatible with any type of trip unit which has to be ordered separately. It can be equipped with a variety of optional functions and accessories. The dimensions are 327mm (W) x 280mm (H) x 147mm (D). It ensures compliance with international standards (IEC 60947), CCC, EAC and marine specifications.
Range
ComPact
Range of product
ComPact NS630b...1600
Device short name
Compact NS1600N
Product or component type
Basic frame
Device application
Distribution
Number of poles
4P
Neutral position
Left
[In] rated current
1600 A at 50 °C
[Ue] rated operational voltage
690 V AC 50/60 Hz
Network type
AC
Network frequency
50/60 Hz
Suitability for isolation
Yes conforming to EN/IEC 60947-2
utilisation category
Category B
[Icu] rated ultimate short-circuit breaking capacity
30 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2
Performance level
N 50 kA 415 V AC
Control type
Motor mechanism with external connector Motor mechanism
Mounting mode
Drawout
[Ui] rated insulation voltage
1000 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage
8 kV conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity
30 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 (electrical operation) 22 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 (electrical operation) 37 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 (electrical operation) 37 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 (electrical operation) 37 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 (electrical operation)
[Icw] rated short-time withstand current
19.2 kA 1 s conforming to IEC 60947-2
Integral instant protection
40 kA
Mechanical durability
10000 cycles conforming to IEC 60947-2
Electrical durability
5000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947-2 1000 cycles 690 V AC 50/60 Hz In conforming to IEC 60947-2 2000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947-2 2000 cycles 690 V AC 50/60 Hz In/2 conforming to IEC 60947-2
Power losses
154 W
mounting support
Backplate
Connection pitch
70 mm
Protection type
Without protection
Height (H)
327 mm
Width (W)
280 mm
Depth (D)
147 mm
standards
IEC 60947-2
product certifications
ASEFA LCIE ASTA
Pollution degree
3 conforming to IEC 60947
IP degree of protection
IP40 conforming to IEC 60529
IK degree of protection
IK07 conforming to EN 50102
Ambient air temperature for operation
-25…70 °C
Ambient air temperature for storage
-50…85 °C
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
40.0 cm
Package 1 Width
40.0 cm
Package 1 Length
30.0 cm
Package 1 Weight
18.917 kg
Warranty
18 months
Datasheet