33394

NS1000N 4P Basic Frame Electrically OP W

Trade Price

£4,388.41

Per

1

Unit

EA

Pack Quantity

1

33394

Information

This is a Compact NS1000N circuit breaker basic frame, 1000A, 50kA at 415 VAC 50/60 Hz, 4 poles . It is adapted for withdrawable devices electrically operated, and it is an optimum choice for all standard applications. This basic frame is compatible with any type of trip unit which has to be ordered separately. It can be equipped with a variety of optional functions and accessories. The dimensions are 327mm (W) x 280mm (H) x 147mm (D). It ensures compliance with international standards (IEC 60947), CCC, EAC and marine specifications.

Technical Specifications

Range

ComPact

Range of product

ComPact NS630b...1600

Device short name

Compact NS1000N

Product or component type

Basic frame

Device application

Distribution

Number of poles

4P

Neutral position

Left

[In] rated current

1000 A at 50 °C

[Ue] rated operational voltage

690 V AC 50/60 Hz

Network type

AC

Network frequency

50/60 Hz

Suitability for isolation

Yes conforming to EN/IEC 60947-2

utilisation category

Category B

[Icu] rated ultimate short-circuit breaking capacity

30 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2

Performance level

N 50 kA 415 V AC

Control type

Motor mechanism Motor mechanism with external connector

Mounting mode

Drawout

[Ui] rated insulation voltage

1000 V AC 50/60 Hz conforming to IEC 60947-2

[Uimp] rated impulse withstand voltage

8 kV conforming to IEC 60947-2

[Ics] rated service short-circuit breaking capacity

30 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 (electrical operation) 22 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 (electrical operation) 37 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 (electrical operation) 37 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 (electrical operation) 37 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 (electrical operation)

[Icw] rated short-time withstand current

19.2 kA 1 s conforming to IEC 60947-2

Integral instant protection

40 kA

Mechanical durability

10000 cycles conforming to IEC 60947-2

Electrical durability

2000 cycles 690 V AC 50/60 Hz In conforming to IEC 60947-2 4000 cycles 690 V AC 50/60 Hz In/2 conforming to IEC 60947-2 5000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947-2 6000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947-2

Power losses

50 W

mounting support

Backplate

Connection pitch

70 mm

Protection type

Without protection

Height (H)

327 mm

Width (W)

280 mm

Depth (D)

147 mm

standards

IEC 60947-2

product certifications

LCIE ASEFA ASTA

Pollution degree

3 conforming to IEC 60947

IP degree of protection

IP40 conforming to IEC 60529

IK degree of protection

IK07 conforming to EN 50102

Ambient air temperature for operation

-25…70 °C

Ambient air temperature for storage

-50…85 °C

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

40.0 cm

Package 1 Width

40.0 cm

Package 1 Length

30.0 cm

Package 1 Weight

18.43 kg

Warranty

18 months

Document Links

Catalogue page

Datasheet