Trade Price
£276.57
Per
1
Unit
EA
Pack Quantity
1
This Compact INS250-160 is a 3 poles non-automatic switch-disconnector with black rotary handle. It is suitable for isolation with positive contact indication, as defined by IEC 60947-1 and IEC60947-3 standards. The operational current is 160A at 415VAC in categories AC22A and AC23A. The rated voltage is 690VAC 50/60Hz or 250VDC. The black rotary handle is designed to offer easy operation and high performance in interruption of currents. Compact INS250-160 is a class II insulation level front-face device as per IEC 60664 standard.
Range
ComPact
Product or component type
Switch disconnector
Product name
ComPacT INS
Poles description
3P
Network type
DC AC
Network frequency
50/60 Hz
[Ie] rated operational current
AC-22A: 200 A AC 50/60 Hz 220/240 V AC-22A: 200 A AC 50/60 Hz 380/415 V AC-22A: 200 A AC 50/60 Hz 440/480 V AC-22A: 200 A AC 50/60 Hz 480 V NEMA AC-22A: 200 A AC 50/60 Hz 500/525 V AC-22A: 200 A AC 50/60 Hz 660/690 V AC-23A: 200 A AC 50/60 Hz 220/240 V AC-23A: 200 A AC 50/60 Hz 380/415 V AC-23A: 200 A AC 50/60 Hz 440/480 V AC-23A: 200 A AC 50/60 Hz 480 V NEMA AC-23A: 200 A AC 50/60 Hz 500/525 V AC-23A: 200 A AC 50/60 Hz 660/690 V DC-22A: 200 A DC 125 V 2 poles in series DC-23A: 200 A DC 125 V 2 poles in series
[Ui] rated insulation voltage
750 V AC 50/60 Hz
[Ith] conventional free air thermal current
200 A at 60 °C
[Icm] rated short-circuit making capacity
30 kA switch-disconnector alone 690 V AC at 50/60 Hz 330 kA with upstream protection circuit breaker 690 V AC at 50/60 Hz
[Ue] rated operational voltage
125 V DC 690 V AC 50/60 Hz
Suitability for isolation
Yes
Contact position indicator
Yes
Visible break
No
Pollution degree
3
Control type
Direct front rotary handle
handle colour
Black
Mounting mode
Fixed
mounting support
Plate Rail
Upside connection
Front
downside connection
Front
Maximum power
AC-23: 110 kW at 440 V AC 50/60 Hz AC-23: 110 kW at 480 V AC 50/60 Hz (NEMA) AC-23: 132 kW at 500/525 V AC 50/60 Hz AC-23: 160 kW at 660/690 V AC 50/60 Hz AC-23: 55 kW at 220/240 V AC 50/60 Hz AC-23: 55 kW at 230 V AC 50/60 Hz (NEMA) AC-23: 90 kW at 380/415 V AC 50/60 Hz
Rated duty
Uninterrupted
[Icw] rated short-time withstand current
1.8 kA during 30 s conforming to IEC 60947-3 2.2 kA during 20 s conforming to IEC 60947-3 4.9 kA during 3 s conforming to IEC 60947-3 8.5 kA during 1 s conforming to IEC 60947-3
Mechanical durability
15000 cycles
Electrical durability
AC-22A: 1500 cycles 440 V AC 50/60 Hz AC-22A: 1500 cycles 500 V AC 50/60 Hz AC-22A: 1500 cycles 690 V AC 50/60 Hz AC-23A: 1500 cycles 440 V AC 50/60 Hz AC-23A: 1500 cycles 500 V AC 50/60 Hz AC-23A: 1500 cycles 690 V AC 50/60 Hz DC-22A: 1500 cycles 125 V DC 2 poles in series DC-23A: 1500 cycles 125 V DC 2 poles in series
Connection pitch
35 mm
height
136 mm
Width
140 mm
Depth
96 mm
Net weight
2 kg
standards
IEC 60947-1 IEC 60947-3
product certifications
CCC KEMA-KEUR
IP degree of protection
IP40 conforming to IEC 60529
IK degree of protection
IK07 conforming to EN 50102
Ambient air temperature for operation
-25…70 °C
Ambient air temperature for storage
-50…85 °C
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
16.5 cm
Package 1 Width
13.5 cm
Package 1 Length
16.0 cm
Package 1 Weight
2.242 kg
Unit Type of Package 2
S04
Number of Units in Package 2
9
Package 2 Height
30.0 cm
Package 2 Width
40.0 cm
Package 2 Length
60.0 cm
Package 2 Weight
20.8 kg
Warranty
18 months
Datasheet