Trade Price
£141.41
Per
1
Unit
EA
Pack Quantity
1
This Acti9 iC60 is a modular residual current breaker with overcurrent protection (RCBO). It is a 1P+Ns circuit breaker with 1 protected pole, 20A In rated current and C tripping curve. The earth leakage protection class is A type with a sensitivity of 30mA. The earth-leakage protection time delay is instantaneous. The Icn rated short circuit breaking capacity is up to 10000A according IEC 61009-2-2 standard. Its unique Visitrip indicator reduces intervention time by showing the faulty circuit. Its Visisafe green strip guarantees the physical opening of the contacts to allow downstream maintenance. Its fast closing mechanism independent of manual operation improves its service life. This product is compliant with AS/NZS 61009.1 and IEC 61009-1 standards. It has an electrical endurance going up to 5000 cycles and a mechanical endurance going up to 20000 cycles. The Ue operational voltage is 240VAC. The Ui rated insulation voltage is 400VAC. The Uimp rated impulse withstand voltage is 4kV. The frequency is 50Hz. It is DIN rail mountable. The width in 9mm pitches is 2. The product color is white (RAL9003). The dimensions are (W) 18mm x (H) 110mm x (D) 77.5mm. The weight is 205g. According to IEC 60529 standard, the degree of protection is IP20 and IP40 in enclosure. The operating temperature is from -15°C to 60°C. The storage temperature is from -40°C to 85°C.
circuit breaker application
Distribution
Range
Acti9
Product name
Acti9 iC60 RCBO
Product or component type
Residual current breaker with overcurrent protection (RCBO)
Device short name
iC60H RCBO
Poles description
1P + Ns
[In] rated current
20 A at 50 °C
Earthing system
TN
Curve code
C
Earth-leakage sensitivity
30 mA
Breaking capacity
10000 A Icn at 230/240 V AC 50/60 Hz
Neutral position
Left
Number of protected poles
1
device location in system
Outgoer
Network frequency
50 Hz
Network type
AC
Trip unit technology
Thermal-magnetic
[Ue] rated operational voltage
230/240 V AC 50/60 Hz
Residual current tripping technology
Voltage dependent
earth-leakage protection time delay
Instantaneous
Earth-leakage protection class
Type A
[Icw] rated short-time withstand current
Icw: 250 A during 8/20 µs impulse withstand
[Ics] rated service breaking capacity
7500 A at 230/240 V AC 50/60 Hz
Limitation class
3
[Ui] rated insulation voltage
400 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage
4 kV
Surge current
250 A
Suitability for isolation
Yes
Contact position indicator
Yes
Control type
Toggle
Local signalling
ON/OFF indication
Mounting mode
Clip-on
Mounting support
DIN rail
Comb busbar and distribution block compatibility
NO
9 mm pitches
2
Height
110 mm
Width
18 mm
Depth
77.5 mm
Net weight
205 g
Colour
White
Mechanical durability
20000 cycles
Electrical durability
5000 cycles
Provision for padlocking
Padlockable with padlock Ø 4 mm
Locking options description
ON/OFF locking facilities
Connections - terminals
Screw clamp terminal (top) 1…25 mm² rigid without cable end Screw clamp terminal (top) 1…16 mm² flexible Screw clamp terminal (bottom) 1…16 mm² rigid without cable end Screw clamp terminal (bottom) 1…10 mm² flexible
Wire stripping length
Power circuit: 13 mm for bottom connection Power circuit: 14 mm for top connection
Tightening torque
Power circuit: 3.5 N.m top Power circuit: 2 N.m bottom
earth-leakage protection
Integrated
Standards
AS/NZS 61009.1 IEC 61009-1 BS EN 61009-1 IEC 61009-2-2
IP degree of protection
IP20
Tropicalisation
2
Relative humidity
95 % at 55 °C
Ambient air temperature for operation
-15…60 °C
Ambient air temperature for storage
-40…85 °C
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
13.6 cm
Package 1 Width
11.1 cm
Package 1 Length
2.7 cm
Package 1 Weight
219 g
Unit Type of Package 2
S02
Number of Units in Package 2
34
Package 2 Height
15 cm
Package 2 Width
30 cm
Package 2 Length
40 cm
Package 2 Weight
7.764 kg
Unit Type of Package 3
P12
Number of Units in Package 3
1088
Package 3 Height
80 cm
Package 3 Width
80 cm
Package 3 Length
120 cm
Package 3 Weight
264.8 kg
Warranty
18 months