A9F95216

ACTI9 IC60L 2P 16A K MCB

Trade Price

£133.64

Per

1

Unit

EA

Pack Quantity

1

A9F95216

Information

This Acti9 iC60L is a low voltage miniature circuit breaker (MCB). It has 2P with 2 protected poles, rated current 16A and K tripping curve. The rated short circuit breaking capacity goes up to 50kA at 220VAC to 240VAC conforming to EN/IEC 60947-2 standard and 15000A at 400VAC conforming to EN/IEC 60898-1 standard. It complies with both industrial standard EN/IEC 60898-1 and residential standard EN/IEC 60947-2. This miniature circuit breaker is for protection against short circuit and overload current in all applications. Its unique VisiTrip indicator reduces intervention time by showing the faulty circuit. Its VisiSafe green strip guarantees the physical opening of the contacts to allow downstream maintenance. Its fast closing mechanism independent of manual operation improves its service life. It has an electrical endurance going up to 10000 cycles and a mechanical endurance going up to 20000 cycles. The Ui rated insulation voltage is 500VAC. Its limitation class 3 (according to EN/IEC60898-1) improves downstream circuit protection cost. It is DIN rail mountable. Its width is 4 pitches of 9mm. Pollution degree is 3. Overvoltage category is IV. The product colour is white (RAL9003). The dimensions are (W) 36mm x (H) 85mm x (D) 78.5mm. The weight is 0.25kg. According to IEC 60529 standard, the degree of protection is IP20 and IP40 in enclosure. The operating temperature is -35°C to 70°C. The storage temperature is -40°C to 85°C.

Technical Specifications

Device application

Distribution

Range

Acti9

Product name

Acti9 iC60

Product or component type

Miniature circuit-breaker

Device short name

iC60L

Poles description

2P

Number of protected poles

2

[In] rated current

16 A

Network type

DC AC

Trip unit technology

Thermal-magnetic

Curve code

K

Breaking capacity

15000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1 50 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 70 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 70 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at <= 125 V DC conforming to EN/IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 25 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2

Utilisation category

Category A conforming to EN 60947-2 Category A conforming to IEC 60947-2

Suitability for isolation

Yes conforming to EN 60947-2 Yes conforming to IEC 60947-2

Standards

IEC 60947-2 EN 60947-2

Network frequency

50/60 Hz

Magnetic tripping limit

12 x In +/- 20 %

[Ics] rated service breaking capacity

12.5 kA 50 % conforming to EN 60947-2 - 380...415 V AC 50/60 Hz 10 kA 50 % conforming to EN 60947-2 - 440 V AC 50/60 Hz 12.5 kA 50 % conforming to IEC 60947-2 - 380...415 V AC 50/60 Hz 10 kA 50 % conforming to IEC 60947-2 - 440 V AC 50/60 Hz 25 kA 50 % conforming to EN 60947-2 - 220...240 V AC 50/60 Hz 25 kA 50 % conforming to IEC 60947-2 - 220...240 V AC 50/60 Hz 35 kA 50 % conforming to EN 60947-2 - 12...133 V AC 50/60 Hz 35 kA 50 % conforming to IEC 60947-2 - 12...133 V AC 50/60 Hz 20 kA 100 % conforming to EN 60947-2 - 72...125 V DC 20 kA 100 % conforming to IEC 60947-2 - 72...125 V DC

Limitation class

3 conforming to EN 60898-1 3 conforming to IEC 60898-1

[Ui] rated insulation voltage

500 V AC 50/60 Hz conforming to EN 60947-2 500 V AC 50/60 Hz conforming to IEC 60947-2

[Uimp] rated impulse withstand voltage

6 kV conforming to EN 60947-2 6 kV conforming to IEC 60947-2

Contact position indicator

Yes

Control type

Toggle

Local signalling

Trip indicator

Mounting mode

Fixed

Mounting support

DIN rail

Comb busbar and distribution block compatibility

Top or bottom: YES

9 mm pitches

4

Height

85 mm

Width

36 mm

Depth

78.5 mm

Net weight

0.25 kg

Colour

White

Mechanical durability

20000 cycles

Electrical durability

10000 cycles

Connections - terminals

Single terminal (top or bottom) 1…25 mm² rigid Single terminal (top or bottom) 1…16 mm² flexible

Wire stripping length

14 mm for top or bottom connection

Tightening torque

2 N.m top or bottom

earth-leakage protection

Separate block

IP degree of protection

IP20 conforming to IEC 60529 IP20 conforming to EN 60529

Pollution degree

3 conforming to EN 60947-2 3 conforming to IEC 60947-2

Overvoltage category

IV

Tropicalisation

2 conforming to IEC 60068-1

Relative humidity

95 % at 55 °C

Operating altitude

0...2000 m

Ambient air temperature for operation

-35…70 °C

Ambient air temperature for storage

-40…85 °C

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

7.5 cm

Package 1 Width

3.6 cm

Package 1 Length

9.5 cm

Package 1 Weight

230.0 g

Unit Type of Package 2

BB1

Number of Units in Package 2

6

Package 2 Height

8.0 cm

Package 2 Width

9.8 cm

Package 2 Length

22.5 cm

Package 2 Weight

1.385 kg

Unit Type of Package 3

S03

Number of Units in Package 3

66

Package 3 Height

30.0 cm

Package 3 Width

30.0 cm

Package 3 Length

40.0 cm

Package 3 Weight

15.992 kg

Warranty

18 months

Document Links

Datasheet