Trade Price
£89.11
Per
1
Unit
EA
Pack Quantity
1
This Acti9 iC60L is a low voltage miniature circuit breaker (MCB). It has 1P with 1 protected pole, rated current 4A and Z tripping curve. The rated short circuit breaking capacity goes up to 100kA at 220VAC to 240VAC conforming to EN/IEC 60947-2 standard and 15000A at 230VAC conforming to EN/IEC 60898-1 standard. It complies with both industrial standard EN/IEC 60898-1 and residential standard EN/IEC 60947-2. This miniature circuit breaker is for protection against short circuit and overload current in all applications. Its unique VisiTrip indicator reduces intervention time by showing the faulty circuit. Its VisiSafe green strip guarantees the physical opening of the contacts to allow downstream maintenance. Its fast closing mechanism independent of manual operation improves its service life. It has an electrical endurance going up to 10000 cycles and a mechanical endurance going up to 20000 cycles. The Ui rated insulation voltage is 500VAC. Its limitation class 3 (according to EN/IEC60898-1) improves downstream circuit protection cost. It is DIN rail mountable. Its width is 2 pitches of 9mm. Pollution degree is 3. Overvoltage category is IV. The product colour is white (RAL9003). The dimensions are (W) 18mm x (H) 85mm x (D) 78.5mm. The weight is 0.215kg. According to IEC 60529 standard, the degree of protection is IP20 and IP40 in enclosure. The operating temperature is -35°C to 70°C. The storage temperature is -40°C to 85°C.
Device application
Distribution
Range
Acti9
Product name
Acti9 iC60
Product or component type
Miniature circuit-breaker
Device short name
iC60L
Poles description
1P
Number of protected poles
1
[In] rated current
4 A
Network type
DC AC
Trip unit technology
Thermal-magnetic
Curve code
Z
Breaking capacity
15000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1 100 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 100 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 100 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 60...72 V DC conforming to EN/IEC 60947-2 25 kA Icu at 12...60 V DC conforming to EN/IEC 60947-2
Utilisation category
Category A conforming to EN 60947-2 Category A conforming to IEC 60947-2
Suitability for isolation
Yes conforming to EN 60947-2 Yes conforming to IEC 60947-2
standards
IEC 60947-2 EN 60947-2
Network frequency
50/60 Hz
Magnetic tripping limit
3 x In +/- 20 %
[Ics] rated service breaking capacity
100 kA 100 % conforming to EN 60947-2 - 12...60 V AC 50/60 Hz 100 kA 100 % conforming to EN 60947-2 - 220...240 V AC 50/60 Hz 100 kA 100 % conforming to IEC 60947-2 - 12...60 V AC 50/60 Hz 100 kA 100 % conforming to IEC 60947-2 - 220...240 V AC 50/60 Hz 100 kA 100 % conforming to EN 60947-2 - 100...133 V AC 50/60 Hz 100 kA 100 % conforming to IEC 60947-2 - 100...133 V AC 50/60 Hz 20 kA 100 % conforming to EN 60947-2 - 72 V DC 20 kA 100 % conforming to IEC 60947-2 - 72 V DC 25 kA 100 % conforming to EN 60947-2 - 12...60 V DC 25 kA 100 % conforming to IEC 60947-2 - 12...60 V DC
Limitation class
3 conforming to EN 60898-1 3 conforming to IEC 60898-1
[Ui] rated insulation voltage
500 V AC 50/60 Hz conforming to EN 60947-2 500 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage
6 kV conforming to EN 60947-2 6 kV conforming to IEC 60947-2
Contact position indicator
Yes
Control type
Toggle
Local signalling
Trip indicator
Mounting mode
Fixed
mounting support
DIN rail
Comb busbar and distribution block compatibility
Top or bottom: YES
9 mm pitches
2
height
85 mm
Width
18 mm
Depth
78.5 mm
Net weight
0.215 kg
Colour
White
Mechanical durability
20000 cycles
Electrical durability
10000 cycles
Connections - terminals
Single terminal (top or bottom) 1…25 mm² rigid Single terminal (top or bottom) 1…16 mm² flexible
Wire stripping length
14 mm for top or bottom connection
Tightening torque
2 N.m top or bottom
earth-leakage protection
Without
IP degree of protection
IP20 conforming to IEC 60529 IP20 conforming to EN 60529
Pollution degree
3 conforming to EN 60947-2 3 conforming to IEC 60947-2
Overvoltage category
IV
Tropicalisation
2 conforming to IEC 60068-1
Relative humidity
95 % at 55 °C
Operating altitude
0...2000 m
Ambient air temperature for operation
-35…70 °C
Ambient air temperature for storage
-40…85 °C
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
1.8 cm
Package 1 Width
7.5 cm
Package 1 Length
9.5 cm
Package 1 Weight
110.0 g
Unit Type of Package 2
BB1
Number of Units in Package 2
12
Package 2 Height
8.0 cm
Package 2 Width
10.0 cm
Package 2 Length
22.5 cm
Package 2 Weight
1.381 kg
Unit Type of Package 3
S03
Number of Units in Package 3
132
Package 3 Height
30.0 cm
Package 3 Width
30.0 cm
Package 3 Length
40.0 cm
Package 3 Weight
15.722 kg
Warranty
18 months
Datasheet