Trade Price
POA
Per
1
Unit
Pack Quantity
Range of produc
Altivar
Product or component type
Line choke
Product compatibility
ATV61HD18M3X - line choke - 1 per drive ATV61HD22M3X - line choke - 1 per drive ATV61HD30M3X - line choke - 1 per drive ATV61HD37M3X - line choke - 1 per drive ATV61HD45M3X - line choke - 1 per drive ATV61HD75N4 - line choke - 1 per drive ATV61WD75N4 - line choke - 1 per drive ATV61WD75N4C - line choke - 1 per drive ATV71HD18M3X - line choke - 1 per drive ATV71HD22M3X - line choke - 1 per drive ATV71HD30M3X - line choke - 1 per drive ATV71HD37M3X - line choke - 1 per drive ATV71HD45M3X - line choke - 1 per drive
number of phases
Three phase
Range compatibility
Altivar 61 Altivar 71
Device application
Reduction of current harmonics
Value of inductance
0.15 mH
[In] rated current
230 A
Thermal losses
400 W
Electrical connection
Bare wires diameter: 9 mm
power supply frequency
50...60 Hz
Max current
1.65 x nominal current (duration = 60 s)
Maximum voltage drop at rated load
5 %
Electrical insulation class
Class F
Minimum clearance distance
5.5 mm IEC 60664
Leakage distance
11.5 mm conforming to IEC 60664
Net weight
45 kg
Width
320 mm
height
340 mm
Depth
240 mm
Standards
IEC 60076 (with HD398) EN 50178 VDE 0160 level 1
IP degree of protection
Choke: IP00 Terminals: IP00
Environmental characteristic
3B1 conforming to IEC 721-3-3 3C2 conforming to IEC 721-3-3 3S1 conforming to IEC 721-3-3
Pollution degree
2 conforming to EN 50178
Vibration resistance
1 gn (f= 13…200 Hz) conforming to IEC 60068-2-6 1.5 mm peak to peak (f= 3…13 Hz) conforming to IEC 60068-2-6
Shock resistance
15 gn for 11 ms conforming to IEC 60068-2-27
Relative humidity
0…95 %
Ambient air temperature for operation
45…55 °C (with current derating of 2 % per °C) 0…45 °C (without current derating)
Ambient air temperature for storage
-25…70 °C
Operating altitude
<= 1000 m without current derating 1000...3000 m with current derating 1 % per 100 m
Warranty
18 months
Datasheet