Trade Price
POA
Per
1
Unit
EA
Pack Quantity
1
This Altivar Process ATV600 variable speed drive can feed 3-phase synchronous and asynchronous power motors. This variable speed drive features an integrated EMC filter with 25m cable conforming to category C3. It works at a rated supply voltage from 500V to 690VAC. This drive provides up to 30% energy saving when on standby due to the innovative ‘‘Stop and Go’’operation without additional costs. It is suitable for motors with power rating up to 30kW/40hp for applications requiring slight overload (up to 120%). It is suitable for motors with power rating up to 22kW/30HP for applications requiring significant overload (up to 150%). Its dimensions are 246mm (width) x 242mm (depth) x 420mm (height). It weighs 22kg. This drive is focused on fluids management processing and energy saving, it offers extensive flexibility in water and wastewater, mining, minerals and metals, oil and gas and food and beverage applications. This product is certified by CE, CSA and TUV. It meets UL 508C, EN/IEC 61800-3, EN/IEC 61800-5-1, IEC 61000-3-12, IEC 60721-3, IEC 61508 and IEC 13849-1 standards. Accessories (fan kit, graphic display terminal) and options (line chokes, dv/dt filter, sinus filter, EMC filter) are available with Altivar Process ATV600 drives, depending on the drive rating. It is designed to be mounted in vertical position (+/- 10 °) on a wall. This new concept of drives meets the major needs of process and utilities in terms of equipment efficiency and total cost of ownership by supporting the energy management, asset management and also the overall performance of the process.
Range of product
Altivar Process ATV600
Product or component type
Variable speed drive
Product specific application
Process and utilities
Device short name
ATV630
Variant
Standard version
Product destination
Asynchronous motors Synchronous motors
EMC filter
Integrated with 25 m conforming to EN/IEC 61800-3 category C3
IP degree of protection
IP00 conforming to IEC 61800-5-1 IP00 conforming to IEC 60529 IP20 (with kit VW3A9706) conforming to IEC 61800-5-1 IP20 (with kit VW3A9706) conforming to IEC 60529
[Us] rated supply voltage
500...690 V - 15...10 %
Type of cooling
Forced convection
Supply frequency
50...60 Hz - 5...5 %
Motor power kW
22 kW at 500 V (normal duty) 18.5 kW at 500 V (heavy duty) 30 kW at 690 V (normal duty) 22 kW at 690 V (heavy duty)
Motor power hp
30 hp at 500 V normal duty 25 hp at 500 V heavy duty 40 hp at 690 V normal duty 30 hp at 690 V heavy duty
Line current
32.1 A at 500 V (normal duty) 32.8 A at 690 V (normal duty) 27.6 A at 500 V (heavy duty) 26 A at 690 V (heavy duty)
Prospective line Isc
70 kA
Apparent power
39.2 kVA at 690 V (normal duty) 31.1 kVA at 690 V (heavy duty)
Continuous output current
34 A at 4 kHz for normal duty 29 A at 4 kHz for heavy duty
Asynchronous motor control profile
Constant torque standard Optimized torque mode Variable torque standard
Synchronous motor control profile
Permanent magnet motor Synchronous reluctance motor
Speed drive output frequency
0.1…500 Hz
Nominal switching frequency
4 kHz
Switching frequency
2...8 kHz adjustable 4...8 kHz with derating factor
Safety function
STO (safe torque off) SIL 3
Discrete input logic
Positive logic (source) (DI1...DI8), < 5 V (state 0), > 11 V (state 1) Negative logic (sink) (DI1...DI8), > 16 V (state 0), < 10 V (state 1)
Communication port protocol
Ethernet Modbus serial Modbus TCP
Option card
Slot A: communication module, Profibus DP V1 Slot A: communication module, PROFINET Slot A: communication module, DeviceNet Slot A: communication module, Modbus TCP/EtherNet/IP Slot A: communication module, CANopen daisy chain RJ45 Slot A: communication module, CANopen SUB-D 9 Slot A: communication module, CANopen screw terminals Slot A/slot B: digital and analog I/O extension module Slot A/slot B: output relay extension module Slot A: communication module, Ethernet IP/Modbus TCP/MD-Link Communication module, BACnet MS/TP Communication module, Ethernet Powerlink
Mounting mode
Wall mount
Maximum transient current
37.4 A during 60 s (normal duty) 43.5 A during 60 s (heavy duty)
Network number of phases
3 phases
Discrete output number
0
Discrete output type
Relay outputs R1A, R1B, R1C 250 V AC 3000 mA Relay outputs R1A, R1B, R1C 30 V DC 3000 mA Relay outputs R2A, R2C 250 V AC 5000 mA Relay outputs R2A, R2C 30 V DC 5000 mA Relay outputs R3A, R3C 250 V AC 5000 mA Relay outputs R3A, R3C 30 V DC 5000 mA
Output voltage
<= power supply voltage
Permissible temporary current boost
1.1 x In during 60 s (normal duty) 1.5 x In during 60 s (heavy duty)
Motor slip compensation
Not available in permanent magnet motor law Can be suppressed Adjustable Automatic whatever the load
Acceleration and deceleration ramps
S, U or customized Linear adjustable separately from 0.01...9999 s
Physical interface
Ethernet 2-wire RS 485
Braking to standstill
By DC injection
Protection type
Thermal protection: motor Safe torque off: motor Motor phase break: motor Thermal protection: drive Safe torque off: drive Overheating: drive Overcurrent between output phases and earth: drive Overload of output voltage: drive Short-circuit protection: drive Motor phase break: drive Overvoltages on the DC bus: drive Line supply overvoltage: drive Line supply undervoltage: drive Line supply phase loss: drive Overspeed: drive Break on the control circuit: drive
Transmission rate
10, 100 Mbits 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps
Frequency resolution
Display unit: 0.1 Hz Analog input: 0.012/50 Hz
Transmission frame
RTU
Electrical connection
Control: removable screw terminals 0.5...1.5 mm²/AWG 20...AWG 16 Motor: screw terminal 10 mm²/AWG 8 Line side: screw terminal 10 mm²/AWG 8
Connector type
RJ45 (on the remote graphic terminal) for Ethernet/Modbus TCP RJ45 (on the remote graphic terminal) for Modbus serial
Data format
8 bits, configurable odd, even or no parity
Type of polarization
No impedance
Exchange mode
Half duplex, full duplex, autonegotiation Ethernet/Modbus TCP
Number of addresses
1…247 for Modbus serial
Method of access
Slave Modbus TCP
Supply
External supply for digital inputs: 24 V DC (19…30 V), <1.25 mA, protection type: overload and short-circuit protection Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 mA, protection type: overload and short-circuit protection Internal supply for digital inputs and STO: 24 V DC (21…27 V), <200 mA, protection type: overload and short-circuit protection
Local signalling
3 LEDs for local diagnostic 3 LEDs (dual colour) for embedded communication status 4 LEDs (dual colour) for communication module status 1 LED (red) for presence of voltage
Width
246 mm
height
420 mm
Depth
242 mm
Net weight
22 kg
analogue input number
3
Analogue input type
AI1, AI2, AI3 software-configurable voltage: 0...10 V DC, impedance: 31.5 kOhm, resolution 12 bits AI1, AI2, AI3 software-configurable current: 0...20 mA, impedance: 250 Ohm, resolution 12 bits AI2 voltage analog input: - 10...10 V DC, impedance: 31.5 kOhm, resolution 12 bits
Discrete input number
8
Discrete input type
DI7, DI8 programmable as pulse input: 0…30 kHz, 24 V DC (<= 30 V)
Input compatibility
DI1...DI6: discrete input level 1 PLC conforming to EN/IEC 61131-2 DI5, DI6: discrete input level 1 PLC conforming to IEC 65A-68 STOA, STOB: discrete input level 1 PLC conforming to EN/IEC 61131-2
analogue output number
2
Analogue output type
Software-configurable voltage AQ1, AQ2: 0...10 V DC impedance 470 Ohm, resolution 10 bits Software-configurable current AQ1, AQ2: 0...20 mA, resolution 10 bits Software-configurable current DQ-, DQ+: 30 V DC Software-configurable current DQ-, DQ+: 100 mA
Sampling duration
2 ms +/- 0.5 ms (DI1...DI4) - discrete input 5 ms +/- 1 ms (DI5, DI6) - discrete input 5 ms +/- 0.1 ms (AI1, AI2, AI3) - analog input 10 ms +/- 1 ms (AO1) - analog output
Accuracy
+/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input +/- 1 % AO1, AO2 for a temperature variation 60 °C analog output
Linearity error
AI1, AI2, AI3: +/- 0.15 % of maximum value for analog input AO1, AO2: +/- 0.2 % for analog output
Relay output number
3
Relay output type
Configurable relay logic R1: fault relay NO/NC electrical durability 100000 cycles Configurable relay logic R2: sequence relay NO electrical durability 100000 cycles Configurable relay logic R3: sequence relay NO electrical durability 100000 cycles
Refresh time
Relay output (R1, R2, R3): 5 ms (+/- 0.5 ms)
Minimum switching current
Relay output R1, R2, R3: 5 mA at 24 V DC
Maximum switching current
Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 250 V AC Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 30 V DC Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC
Isolation
Between power and control terminals
Maximum output frequency
500 kHz
Maximum input current
32.8 A
Quantity per set
1
Enclosure mounting
Wall mounted
Insulation resistance
> 1 MOhm 500 V DC for 1 minute to earth
Noise level
58 dB
Power dissipation in W
Natural convection: 152 W at 500 V, switching frequency 4 kHz Forced convection: 544 W at 500 V, switching frequency 4 kHz
Volume of cooling air
330 m3/h
Operating position
Vertical +/- 10 degree
Maximum THDI
<48 % with external line choke conforming to IEC 61000-3-12
Electromagnetic compatibility
Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Pollution degree
2
Vibration resistance
1.5 mm peak to peak (f= 2…13 Hz) conforming to IEC 60068-2-6 1 gn (f= 13…200 Hz) conforming to IEC 60068-2-6
Shock resistance
15 gn for 11 ms conforming to IEC 60068-2-27
Relative humidity
5…95 % without condensation conforming to IEC 60068-2-3
Ambient air temperature for operation
-15…50 °C (without derating) 50…60 °C (with derating factor)
Ambient air temperature for storage
-40…70 °C
Operating altitude
<= 1000 m without derating 1000...4800 m with current derating 1 % per 100 m
product certifications
UL CSA TÜV
Marking
CE
standards
UL 508C EN/IEC 61800-3 EN/IEC 61800-3 environment 2 category C3 EN/IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1
Overvoltage category
III
Regulation loop
Adjustable PID regulator
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
48.5 cm
Package 1 Width
39.5 cm
Package 1 Length
80.0 cm
Package 1 Weight
31.0 kg
Warranty
18 months
Datasheet