ATV630C16N4

VSD IP00 160KW 400V/480

Trade Price

POA

Per

1

Unit

EA

Pack Quantity

1

ATV630C16N4

Information

This Altivar Process ATV600 variable speed drive can feed 3-phase synchronous and asynchronous power motors. It features 3 built-in RJ45 communication ports as standard, 1 Ethernet port, 2 serial ports. It works at a rated supply voltage from 380V to 480V AC. This drive provides up to 30% energy saving when on standby due to the innovative ‘‘Stop and Go’’operation without additional costs. It is suitable for motors with power rating up to 160kW / 250hp for applications requiring slight overload (up to 120%). It is suitable for motors with power rating up to 132kW / 200hp for applications requiring significant overload (up to 150%). It weighs 82kg and its dimensions are, 320mm wide, 852mm high, 390mm deep. This drive is focused on fluids management processing and energy saving, it offers extensive flexibility in water and wastewater, mining, minerals and metals, oil and gas and food and beverage applications. Accessories (fan kit, graphic display terminal) and options (I/O expansion modules, communication modules, EMC input filters) are available with Altivar Process ATV600 drives, depending on the drive rating. It is designed to be mounted in vertical position (+/- 10 °) on a wall. This new concept of drives meets the major needs of process and utilities in terms of equipment efficiency and total cost of ownership by supporting the energy management, asset management and also the overall performance of the process.

Technical Specifications

Range of product

Altivar Process ATV600

Product or component type

Variable speed drive

Product specific application

Process and utilities

Device short name

ATV630

Variant

Standard version

Product destination

Asynchronous motors Synchronous motors

EMC filter

Integrated with 150 m conforming to EN/IEC 61800-3 category C3

IP degree of protection

IP00 conforming to IEC 61800-5-1 IP00 conforming to IEC 60529 IP21 (with kit VW3A9704) conforming to IEC 61800-5-1 IP21 (with kit VW3A9704) conforming to IEC 60529

[Us] rated supply voltage

380...480 V - 15...10 %

Type of cooling

Forced convection

Supply frequency

50...60 Hz - 5...5 %

Motor power kW

160 kW (normal duty) 132 kW (heavy duty)

Motor power hp

250 hp normal duty 200 hp heavy duty

Line current

284 A at 380 V (normal duty) 262 A at 480 V (normal duty) 237 A at 380 V (heavy duty) 213 A at 480 V (heavy duty)

Prospective line Isc

50 kA

Apparent power

201.3 kVA at 480 V (normal duty) 161.4 kVA at 480 V (heavy duty)

Continuous output current

302 A at 2.5 kHz for normal duty 250 A at 2.5 kHz for heavy duty

Asynchronous motor control profile

Constant torque standard Optimized torque mode Variable torque standard

Synchronous motor control profile

Permanent magnet motor Synchronous reluctance motor

Speed drive output frequency

0.1…500 Hz

Nominal switching frequency

2.5 kHz

Switching frequency

2.5...8 kHz with derating factor 2...8 kHz adjustable

Safety function

STO (safe torque off) SIL 3

Discrete input logic

Positive logic (source) (DI1...DI8), < 5 V (state 0), > 11 V (state 1) Negative logic (sink) (DI1...DI8), > 16 V (state 0), < 10 V (state 1)

Communication port protocol

Modbus serial Modbus TCP Ethernet

Option card

Slot A: communication module, Profibus DP V1 Slot A: communication module, PROFINET Slot A: communication module, DeviceNet Slot A: communication module, Modbus TCP/EtherNet/IP Slot A: communication module, CANopen daisy chain RJ45 Slot A: communication module, CANopen SUB-D 9 Slot A: communication module, CANopen screw terminals Slot A/slot B: digital and analog I/O extension module Slot A/slot B: output relay extension module Slot A: communication module, Ethernet IP/Modbus TCP/MD-Link Communication module, BACnet MS/TP Communication module, Ethernet Powerlink

Mounting mode

Wall mount

Maximum transient current

332.2 A during 60 s (normal duty) 375 A during 60 s (heavy duty)

Network number of phases

3 phases

Discrete output number

0

Discrete output type

Relay outputs R1A, R1B, R1C 250 V AC 3000 mA Relay outputs R1A, R1B, R1C 30 V DC 3000 mA Relay outputs R2A, R2C 250 V AC 5000 mA Relay outputs R2A, R2C 30 V DC 5000 mA Relay outputs R3A, R3C 250 V AC 5000 mA Relay outputs R3A, R3C 30 V DC 5000 mA

Output voltage

<= power supply voltage

Permissible temporary current boost

1.1 x In during 60 s (normal duty) 1.5 x In during 60 s (heavy duty)

Motor slip compensation

Not available in permanent magnet motor law Automatic whatever the load Can be suppressed Adjustable

Acceleration and deceleration ramps

Linear adjustable separately from 0.01...9999 s

Physical interface

Ethernet 2-wire RS 485

Braking to standstill

By DC injection

Protection type

Thermal protection: motor Safe torque off: motor Motor phase break: motor Thermal protection: drive Safe torque off: drive Overheating: drive Overcurrent between output phases and earth: drive Overload of output voltage: drive Short-circuit protection: drive Motor phase break: drive Overvoltages on the DC bus: drive Line supply overvoltage: drive Line supply undervoltage: drive Line supply phase loss: drive Overspeed: drive Break on the control circuit: drive

Transmission rate

10, 100 Mbits 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps

Frequency resolution

Display unit: 0.1 Hz Analog input: 0.012/50 Hz

Transmission frame

RTU

Electrical connection

Control: removable screw terminals 0.5...1.5 mm²/AWG 20...AWG 16 Line side: screw terminal 2 x 95...3 x 120 mm²/2 x AWG 3/0...2 x 300 kcmil Motor: screw terminal 2 x 95...3 x 120 mm²/2 x AWG 3/0...2 x 300 kcmil

Connector type

RJ45 (on the remote graphic terminal) for Ethernet/Modbus TCP RJ45 (on the remote graphic terminal) for Modbus serial

Data format

8 bits, configurable odd, even or no parity

Type of polarization

No impedance

Exchange mode

Half duplex, full duplex, autonegotiation Ethernet/Modbus TCP

Number of addresses

1…247 for Modbus serial

Method of access

Slave Modbus TCP

Supply

External supply for digital inputs: 24 V DC (19…30 V), <1.25 mA, protection type: overload and short-circuit protection Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 mA, protection type: overload and short-circuit protection Internal supply for digital inputs and STO: 24 V DC (21…27 V), <200 mA, protection type: overload and short-circuit protection

Local signalling

3 LEDs for local diagnostic 3 LEDs (dual colour) for embedded communication status 4 LEDs (dual colour) for communication module status 1 LED (red) for presence of voltage

Width

320 mm

height

852 mm

Depth

390 mm

Net weight

82 kg

analogue input number

3

Analogue input type

AI1, AI2, AI3 software-configurable voltage: 0...10 V DC, impedance: 31.5 kOhm, resolution 12 bits AI1, AI2, AI3 software-configurable current: 0...20 mA, impedance: 250 Ohm, resolution 12 bits AI2 voltage analog input: - 10...10 V DC, impedance: 31.5 kOhm, resolution 12 bits

Discrete input number

8

Discrete input type

DI7, DI8 programmable as pulse input: 0…30 kHz, 24 V DC (<= 30 V)

Input compatibility

DI1...DI6: discrete input level 1 PLC conforming to EN/IEC 61131-2 DI5, DI6: discrete input level 1 PLC conforming to IEC 65A-68 STOA, STOB: discrete input level 1 PLC conforming to EN/IEC 61131-2

analogue output number

2

Analogue output type

Software-configurable voltage AQ1, AQ2: 0...10 V DC impedance 470 Ohm, resolution 10 bits Software-configurable current AQ1, AQ2: 0...20 mA, resolution 10 bits Software-configurable current DQ-, DQ+: 30 V DC Software-configurable current DQ-, DQ+: 100 mA

Sampling duration

2 ms +/- 0.5 ms (DI1...DI4) - discrete input 5 ms +/- 1 ms (DI5, DI6) - discrete input 5 ms +/- 0.1 ms (AI1, AI2, AI3) - analog input 10 ms +/- 1 ms (AO1) - analog output

Accuracy

+/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input +/- 1 % AO1, AO2 for a temperature variation 60 °C analog output

Linearity error

AI1, AI2, AI3: +/- 0.15 % of maximum value for analog input AO1, AO2: +/- 0.2 % for analog output

Relay output number

3

Relay output type

Configurable relay logic R1: fault relay NO/NC electrical durability 100000 cycles Configurable relay logic R2: sequence relay NO electrical durability 100000 cycles Configurable relay logic R3: sequence relay NO electrical durability 100000 cycles

Refresh time

Relay output (R1, R2, R3): 5 ms (+/- 0.5 ms)

Minimum switching current

Relay output R1, R2, R3: 5 mA at 24 V DC

Maximum switching current

Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 250 V AC Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 30 V DC Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC

Isolation

Between power and control terminals

Maximum output frequency

500 kHz

Maximum input current

284.0 A

Variable speed drive application selection

Building - HVAC compressor centrifugal Food and beverage processing other application Mining mineral and metal fan Mining mineral and metal pump Oil and gas fan Water and waste water other application Building - HVAC screw compressor Food and beverage processing pump Food and beverage processing fan Food and beverage processing atomization Oil and gas electro submersible pump (ESP) Oil and gas water injection pump Oil and gas jet fuel pump Oil and gas compressor for refinery Water and waste water centrifuge pump Water and waste water positive displacement pump Water and waste water electro submersible pump (ESP) Water and waste water screw pump Water and waste water lobe compressor Water and waste water screw compressor Water and waste water compressor centrifugal Water and waste water fan Water and waste water conveyor Water and waste water mixer

Motor power range AC-3

110…220 kW at 380…440 V 3 phases 110…220 kW at 480…500 V 3 phases

Quantity per set

1

Enclosure mounting

Wall mounted

Insulation resistance

> 1 MOhm 500 V DC for 1 minute to earth

Noise level

69.9 dB

Power dissipation in W

Forced convection: 3270 W at 380 V, switching frequency 2.5 kHz

Volume of cooling air

600 m3/h

Operating position

Vertical +/- 10 degree

Maximum THDI

<48 % full load conforming to IEC 61000-3-12

Electromagnetic compatibility

Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6

Pollution degree

2

Vibration resistance

1.5 mm peak to peak (f= 2…13 Hz) conforming to IEC 60068-2-6 1 gn (f= 13…200 Hz) conforming to IEC 60068-2-6

Shock resistance

15 gn for 11 ms conforming to IEC 60068-2-27

Relative humidity

5…95 % without condensation conforming to IEC 60068-2-3

Ambient air temperature for operation

-15…50 °C (without derating) 50…60 °C (with derating factor)

Ambient air temperature for storage

-40…70 °C

Operating altitude

<= 1000 m without derating 1000...4800 m with current derating 1 % per 100 m

product certifications

ATEX INERIS DNV-GL CSA TÜV UL ATEX zone 2/22

Marking

CE

standards

UL 508C EN/IEC 61800-3 EN/IEC 61800-3 environment 1 category C2 EN/IEC 61800-3 environment 2 category C3 EN/IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1

Overvoltage category

III

Regulation loop

Adjustable PID regulator

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

48.0 cm

Package 1 Width

66.0 cm

Package 1 Length

103.0 cm

Package 1 Weight

125.0 kg

Warranty

18 months

Document Links

Datasheet