Trade Price
£81.12
Per
1
Unit
EA
Pack Quantity
1
This Harmony RE48 timing relay can be set between 0.02 seconds and 300 hours, has an output rating of 5A, is 48mm wide and can be supplied with 24V to 240V AC. It is a plug-in device, meaning it is quick and easy to install with the need for tools. It also offers a sealable cover, simple and precise settings with rotary trimmers. It is designed for both panel mooting or socket plug in, this gives more flexibility in designing installations and stocking spares. Status display with 2 LEDs, visually inspect the status of you system without specialized tools. Single function timer for a simple integration in hard-wired logic schematics, ideal for refurbishment of old installations without using a PLC. 0 0 0 0 0 0 0 0 0 0 0 0 0
Range of product
Harmony Timer Relays
Product or component type
Single function relay
Electrical connection
Plug-in sub-base 8 pin(s)
Discrete output type
Relay
Contacts type and composition
2 C/O timed contacts, AgNi (cadmium free)
Component name
RE48
Time delay type
Power on-delay
Time delay range
5...300 h 2...120 min 0.5...30 h 0.2...12 h 0.2...12 min 0.2...12 s 0.5...30 min 2...120 h 2...120 s 0.02...1.2 s 0.5...30 s 5...300 s 0.05...3 s 5...300 min
[Us] rated supply voltage
24...240 V AC/DC 50/60 Hz
Voltage range
0.85...1.1 Us AC 0.9...1.1 Us DC
[In] rated current
5 A
Product front plate size
48 x 48 mm
Control type
Selector switch front panel
Housing material
Self-extinguishing
Repeat accuracy
+/- 0.2 % of the maximum setting value conforming to IEC 61812-1
Temperature drift
+/- 0.02 %/°C of the maximum setting value conforming to IEC 61812-1
Voltage drift
+/- 0.2 %/V of the maximum setting value at 48...240 V +/- 1 %/V of the maximum setting value at 24...48 V
Setting accuracy of time delay
+/- 5 % of full scale at 25 °C conforming to IEC 61812-1
Minimum pulse duration
20 ms
Reset time
25 ms on de-energisation
Pick up duration
55 ms
On-load factor
100 %
Power consumption in VA
1.1 VA at 24 V 4.8 VA at 240 V
Power consumption in W
0.5 W at 24 V 1.7 W at 240 V
Breaking capacity
1250 VA
Minimum switching current
100 mA
Maximum switching current
5 A
Maximum switching voltage
250 V AC/DC
Electrical durability
100000 cycles
Mechanical durability
30000000 cycles
Output voltage
240 V at 5 A AC-12 30 V at 2 A DC-13 240 V at 1.5 A AC-15
Marking
CE
Surge withstand
1 kV differential mode conforming to IEC 61000-4-5 level 3 2 kV common mode conforming to IEC 61000-4-5 level 3
mounting support
Panel mounted: system supplied with the product Base mounted: socket
Local signalling
1 LED (yellow) for output relay state LED indicator (green) for flashing: relay energised timing in progress LED indicator (green) for on steady: relay energised, no timing in progress
Net weight
0.14 kg
Humidity drift
+/- 0.05 %/%RH of the maximum setting value conforming to IEC 61812-1
Immunity to microbreaks
10 ms
Dielectric strength
1 kV 1 mA/1 minute conforming to IEC 61812-1
Protection against electric shocks
4 kV class III conforming to IEC 60664-1 4 kV class III conforming to IEC 61812-1
standards
73/23/EEC 93/68/EEC EN 50082-1/2 89/336/EEC EN 50081-1/2 IEC 61812-1 IEC 60669-2-3
product certifications
UL cULus C-Tick CSA
Ambient air temperature for storage
-40…70 °C
Ambient air temperature for operation
-20…50 °C
IP degree of protection
IP40 (housing) conforming to IEC 60529 IP50 (front face) conforming to IEC 60529
Vibration resistance
0.35 mm (f= 10…55 Hz) conforming to IEC 60068-2-6
Relative humidity
93 % without condensation conforming to IEC 60068-2-3
Resistance to electrostatic discharge
6 kV in contact conforming to IEC 61000-4-2 level 3 8 kV in air conforming to IEC 61000-4-2 level 3
Resistance to electromagnetic fields
10 V/m 26 MHz to 1 GHz conforming to IEC 61000-4-3 level 3
Resistance to fast transients
2 kV (capacitive connecting clip) conforming to IEC 61000-4-4 level 4 4 kV (direct) conforming to IEC 61000-4-4 level 4
Immunity to radioelectric fields
10 V (0.15...80 MHz) conforming to IEC 61000-4-6 level 3
Immunity to voltage dips
30 % / 10 ms conforming to IEC 61000-4-11 60 % / 100 ms conforming to IEC 61000-4-11 95 % / 5 s conforming to IEC 61000-4-11
Disturbance radiated/conducted
Class B 0.15...30 MHz conforming to EN 55022 (EN 55011 group 1)
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
5.7 cm
Package 1 Width
10.5 cm
Package 1 Length
6.2 cm
Package 1 Weight
126 g
Unit Type of Package 2
S02
Number of Units in Package 2
30
Package 2 Height
15 cm
Package 2 Width
30 cm
Package 2 Length
40 cm
Package 2 Weight
4.252 kg
Warranty
18 months
Datasheet
Technical Data