This Harmony RPM power plug-in relay has a coil control voltage of 120V AC and has 4 changeover contacts 4PDT (quadruple pole double throw) with a rating of 15A. It has large choice of number of contacts for high rated current use. It also offers LED indicator to alert on the current status of the relay. It helps to reduce the size of enclosures and increase machine reliability, you can mount nearly everywhere. This RPM product is IP40. Workability for hard-wired logic automated systems to complement the functions of industrial programmable logic controllers (PLCs). Status display with LED, clearly signal both in the day and night. 0 0 0 0 0 0 0 0 0
Range of product
Harmony Electromechanical Relays
Series name
Power
Product or component type
Plug-in relay
Device short name
RPM
Contacts type and composition
4 C/O
[Uc] control circuit voltage
120 V AC 50/60 Hz
[Ithe] conventional enclosed thermal current
15 A at -40…55 °C
Status LED
With
Control type
Lockable test button
Utilisation coefficient
20 %
Shape of pin
Flat
[Ui] rated insulation voltage
250 V conforming to IEC 300 V conforming to CSA 300 V conforming to UL
[Uimp] rated impulse withstand voltage
4 kV during 1.2/50 µs
Contacts material
AgNi
[Ie] rated operational current
15 A at 277 V (AC) conforming to UL 15 A at 28 V (DC) conforming to UL 15 A at 250 V (AC) NO conforming to IEC 15 A at 28 V (DC) NO conforming to IEC 7.5 A at 250 V (AC) NC conforming to IEC 7.5 A at 28 V (DC) NC conforming to IEC
Maximum switching voltage
250 V conforming to IEC
Resistive load current
15 A at 250 V AC 15 A at 28 V DC
Maximum switching capacity
3750 VA 420 W
Minimum switching capacity
170 mW at 10 mA, 17 V
Operating rate
<= 1200 cycles/hour under load <= 18000 cycles/hour no-load
Mechanical durability
10000000 cycles
Electrical durability
100000 cycles for resistive load
Average coil consumption in VA
2.5 at 60 Hz
Drop-out voltage threshold
>= 0.15 Uc AC
Operate time
20 ms at nominal voltage
Release time
20 ms at nominal voltage
Average coil resistance
2100 Ohm at 20 °C +/- 15 %
Rated operational voltage limits
96...132 V AC
Protection category
RT I
Test levels
Level A group mounting
Operating position
Any position
Pollution degree
3
Safety reliability data
B10d = 100000
Net weight
0.071 kg
Device presentation
Complete product
Dielectric strength
1500 V AC between contacts with micro disconnection 2000 V AC between coil and contact with reinforced 2000 V AC between poles with basic
standards
CSA C22.2 No 14 UL 508 IEC 61810-1
product certifications
UL EAC CSA
Ambient air temperature for storage
-40…85 °C
Ambient air temperature for operation
-40…55 °C
Vibration resistance
3 gn, amplitude = +/- 1 mm (f = 10…150 Hz)5 cycles in operation 5 gn, amplitude = +/- 1 mm (f = 10…150 Hz)5 cycles not operating
Degree of protection (Housing only)
IP40 conforming to IEC 60529
Shock resistance
15 gn for in operation 30 gn for not operating
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
2.4 cm
Package 1 Width
3.3 cm
Package 1 Length
5.0 cm
Package 1 Weight
72.0 g
Warranty
18 months