Trade Price
£193.11
Per
1
Unit
EA
Pack Quantity
1
This voltage/current converter is part of the range of Harmony Analog. It allows conversion of the most common signals. Its supply voltage is 24V DC, isolated. It features four inputs with voltage/current range of 0V to 10V, +/- 10V, 0mA to 20mA, and 4mA to 20mA. It has four outputs with a switchable voltage/current range of 0V to 10V, +/- 10V, 0mA to 20mA, and 4mA to 20mA. It also allows the connection distance between a sensor and the measurement acquisition device to be increased. 0 It weighs 0.120Kg. 0 0 Conforming to IEC standards, UL and CSA certified, this converter is suitable for universal use. 0 0 0 0 Quick and intuitive setting, easy to use with fixed input and output values according to the market needs. The settings are secure with sealable protective cover. 0
Range of product
Harmony Analog
Product or component type
Voltage/current converter
Analogue input type
Current 0...20 mA Current 4...20 mA Voltage +/- 10 V DC Voltage 0...10 V DC
Analogue output type
Current 0...20 mA <= 500 Ohm switchable Current 4...20 mA <= 500 Ohm switchable Voltage +/- 10 V >= 100 kOhm switchable Voltage 0...10 V >= 100 kOhm switchable
Protection type
Reverse polarity protection on output Short-circuit protection on output Overvoltage protection on output (+/- 30 V)
abnormal analogue output voltage
11...15 V, output selected - 10...10 V no input or input wire broken voltage 11...15 V, output selected 0...10 V no input or input wire broken voltage -15...0 V, output selected 0...20 mA no input or input wire broken current -15...0 V, output selected 4...20 mA no input or input wire broken current
abnormal analogue output current
22…30 mA, output selected 0...20 mA no input or input wire broken voltage 22…30 mA, output selected 4...20 mA no input or input wire broken voltage -30…0 mA, output selected 0...20 mA no input or input wire broken current 4…30 mA, output selected 4...20 mA no input or input wire broken current
[Us] rated supply voltage
24 V DC +/- 20 %, isolated
Current consumption
<= 70 mA for voltage output <= 90 mA for current output
Local signalling
LED (green) for power ON
Measurement error
+/- 10 % of full scale at 20 °C (electromagnetic interference of 10 V/m) +/- 1 % of full scale at 20 °C
Repeat accuracy
+/- 0.2 % full scale at 20 °C +/- 0.6 % full scale at 60 °C
Temperature coefficient
200 ppm/°C
Clamping connection capacity
2 x 1.5 mm² 1 x 2.5 mm²
tightening torque
0.6…1.1 N.m
Marking
CE
Surge withstand
0.5 kV during 1.2/50 µs conforming to IEC 61000-4-5
[Ui] rated insulation voltage
2 kV
Fixing mode
By screws (mounting plate) Clip-on (35 mm symmetrical DIN rail)
Safety reliability data
B10d = 20000 MTTFd = 21.6 years
Net weight
0.12 kg
standards
IEC 60947-1 IEC 60584-1
product certifications
UL GL CSA
IP degree of protection
IP20 (terminal block) IP50 (housing)
Fire resistance
850 °C conforming to IEC 60695-2-1 850 °C conforming to UL
Shock resistance
50 gn for 11 ms conforming to IEC 60068-2-27
Vibration resistance
5 gn (f= 10…100 Hz) conforming to IEC 60068-2-6
Resistance to electrostatic discharge
6 kV (in contact) conforming to IEC 61000-4-2 level 3 8 kV (in air) conforming to IEC 61000-4-2 level 3
Resistance to fast transients
1 kV (on input-output) conforming to IEC 61000-4-4 2 kV (on power supply) conforming to IEC 61000-4-4
Disturbance radiated/conducted
CISPR 22 group 1 - class B CISPR 11
Ambient air temperature for storage
-40…85 °C
Ambient air temperature for operation
0…50 °C mounting side by side 0…60 °C 2 cm spacing
Pollution degree
2 conforming to IEC 60664-1
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
2.7 cm
Package 1 Width
8.2 cm
Package 1 Length
8.5 cm
Package 1 Weight
119.0 g
Unit Type of Package 2
S02
Number of Units in Package 2
47
Package 2 Height
15 cm
Package 2 Width
30 cm
Package 2 Length
40 cm
Package 2 Weight
6.14 kg
Warranty
18 months
Datasheet
Technical Data