Trade Price
POA
Per
1
Unit
Pack Quantity
This ABT7 transformer supplies alternating current to control circuits while isolating them from mains power. It has a rated input voltage of 230V to 400V AC, a rated output voltage of 115/230V AC thanks to its double secondary winding, and a rated power of 1kVA / 1000VA. It offers an economic way to supply each consuming load individually, or by groups of loads, in applications such as mining, refining. It is ideal for systems accepting low voltage AC power, such as motor protection relays, contactors.
Range of produc
Modicon Transformer Universal
Product or component type
Safety and isolation transformer
Rated power in VA
1000 VA
Input voltage
230 V AC single phase, terminal(s): N-L1 400 V AC phase to phase, terminal(s): L1-L2
Output voltage
115/230 V AC
Secondary winding
Double
Protective cover
Without
ambient air temperature for operation
-20…60 °C
Input voltage limits
207...253 V 360...440 V
network frequency limits
47…63 Hz
Input voltage tolerance
+/- 15 V
Efficiency
92 %
Power dissipation in W
87 W
Voltage variation at nominal load
0,0315 at 230 V 0,034 at 400 V
Output sustained overvoltage
0,035 (no load, hot state)
Maximum voltage drop at rated load
4.08 %
No load losses
31.09 W
Short-circuit voltage
0,038
Output protection type
Against overload, protection technology: with additional protection fuses or circuit-breakers in Selection of Protection Against overvoltage, protection technology: with additional protection fuses or circuit-breakers in Selection of Protection Against short-circuits, protection technology: with additional protection fuses or circuit-breakers in Selection of Protection
Connections - terminals
For input connection: screw type terminals, connection capacity: 5 x 4 mm² AWG 11 For input ground connection: screw type terminals, connection capacity: 1 x 4 mm² AWG 11 For output connection: screw type terminals, connection capacity: 6 x 10 mm² AWG 6
Marking
CE
Fixing mode
By 4 screws diameter: 7 mm on vertical panel, operating position: horizontal By 4 screws diameter: 7 mm on vertical panel, operating position: vertical By 4 screws diameter: 7 mm on horizontal panel with derating to 90 %
Output coupling
Grounding of secondary Series by internal jumper Parallel
Operating altitude
3000 m
Electrical insulation class
Class F
Width
150.0 mm
height
156.0 mm
Depth
145.0 mm
Net weight
13.58 kg
product certifications
EAC UR DNV-GL
Standards
UL 506
IP degree of protection
IP20
Environmental characteristic
EMC conforming to EN 62041 Safety conforming to EN 61558-1 Safety conforming to EN 61558-2-4
Ambient air temperature for storage
-40…80 °C
Relative humidity
0…95 % during operation
Overvoltage category
Class I conforming to VDE 0106-1
Dielectric strength
3200 V between input and ground 3200 V between output and ground 5100 V between input and output
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
21.000 cm
Package 1 Width
31.000 cm
Package 1 Length
30.000 cm
Package 1 Weight
14.406 kg
Unit Type of Package 2
P06
Number of Units in Package 2
4
Package 2 Height
75.000 cm
Package 2 Width
60.000 cm
Package 2 Length
80.000 cm
Package 2 Weight
66.124 kg
Warranty
18 months
Datasheet
Technical Data