Trade Price
£80.46
Per
1
Unit
EA
Pack Quantity
1
Range
TeSys
Device short name
LUF
Product or component type
Function module
Product compatibility
LUCC LUCB LUCD
Mounting mode
Plug-in
Mounting location
Front side
main function available
Thermal overload signalling and manual reset
Auxiliary contact composition
1 NO + 1 NC
Communication of faults
LED front panel
[Us] rated supply voltage
24...240 V DC 24...240 V AC
Current consumption
7 mA at 24 V DC 1.1 mA at 240 V AC
Discrete output function
1 NO + 1 NC (AC-15) at 230 V - power: 400 VA - electrical service life: 100000 cycles 1 NO + 1 NC (DC-13) at 24 V - power: 50 W - electrical service life: 100000 cycles
[Ith] conventional free air thermal current
2 A 70 °C
Short-circuit protection
2 A fuse gG conforming to IEC 60947-5-1
Input type
Remote reset - cable cross section: 0.2…1.5 mm² <500 m - relative impedance: 50 Ohm 52.8 mH - cable capacitance: 0.093 nF
Connection pitch
5.08 mm
Connections - terminals
Screw clamp terminals 2 cable(s) 0.2…1 mm² rigid without cable end Screw clamp terminals 2 cable(s) 0.25…1 mm² flexible with cable end Screw clamp terminals 2 cable(s) 0.5…1 mm² flexible with cable end
Tightening torque
0.5…0.6 N.m - with screwdriver 3.5 mm flat
Net weight
0.06 kg
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
3.3 cm
Package 1 Width
4.7 cm
Package 1 Length
10.5 cm
Package 1 Weight
75.0 g
Unit Type of Package 2
S01
Number of Units in Package 2
15
Package 2 Height
15.0 cm
Package 2 Width
15.0 cm
Package 2 Length
40.0 cm
Package 2 Weight
1.346 kg
Warranty
18 months
Datasheet