Trade Price
£184.57
Per
1
Unit
EA
Pack Quantity
1
Range
TeSys
Product name
TeSys Ultra
Device short name
LU2B
Product or component type
Reversing power base
Device application
Motor control Motor protection
Product compatibility
Control unit LUC.X6BL Control unit LUC.1XBL Control unit LUC.05BL Control unit LUC.12BL
Poles description
3P
Suitability for isolation
Yes
[Ue] rated operational voltage
690 V AC for power circuit
Network frequency
40...60 Hz
[Ith] conventional free air thermal current
12 A
[Ie] rated operational current
12 A at <= 440 V 12 A at 500 V 9 A at 690 V
utilisation category
AC-43 AC-44 AC-41
[Ics] rated service breaking capacity
50 kA at 230 V 50 kA at 440 V 10 kA at 500 V 4 kA at 690 V
Auxiliary contact composition
1 NO + 1 NC
Auxiliary contacts type
type linked contacts (1 NO + 1 NC) conforming to IEC 60947-4-1 type mirror contact (1 NC) conforming to IEC 60947-1
[Uc] control circuit voltage
24 V DC
Control circuit voltage limits
14.5 V DC drop-out 20...27 V DC in operation
Typical current consumption
120 mA at 24 V DC I maximum while closing 120 mA at 24 V DC I rms sealed
Heat dissipation
2 W for control circuit with LUCA, LUCB, LUCC, LUCD 1.7 W for control circuit with LUCM
Inrush restraint duration
15 ms DC
Safety reliability level
B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Operating time
150 ms with change of direction for power circuit 75 ms without change of direction for power circuit 35 ms opening with LUCA, LUCB, LUCC, LUCD, LUCM for control circuit 75 ms closing with LUCM for control circuit 70 ms closing with LUCA, LUCB, LUCC, LUCD for control circuit
Mechanical durability
15 Mcycles
Maximum operating rate
3600 cyc/h
product certifications
CE UL CSA CCC EAC ASEFA ATEX Marine
Standards
EN 60947-6-2 IEC 60947-6-2 UL 60947-4-1, with phase barrier CSA C22.2 No 60947-4-1, with phase barrier
[Ui] rated insulation voltage
690 V conforming to IEC 60947-6-2 (pollution degree 3) 600 V conforming to UL 60947-4-1 600 V conforming to CSA C22.2 No 60947-4-1
[Uimp] rated impulse withstand voltage
6 kV conforming to IEC 60947-6-2
Safe separation of circuit
400 V SELV between the control and auxiliary circuits conforming to IEC 60947-1 appendix N 400 V SELV between the control or auxiliary circuit and the main circuit conforming to IEC 60947-1 appendix N
Fixing mode
Clipped (DIN rail) Screw-fixed (plate)
Connections - terminals
Power circuit: screw clamp terminals 1 cable(s) 1…10 mm² rigid Power circuit: screw clamp terminals 1 cable(s) 1…6 mm² flexible with cable end Power circuit: screw clamp terminals 1 cable(s) 2.5…10 mm² flexible without cable end Power circuit: screw clamp terminals 2 cable(s) 1…6 mm² flexible with cable end Power circuit: screw clamp terminals 2 cable(s) 1…6 mm² rigid Power circuit: screw clamp terminals 2 cable(s) 1.5…6 mm² flexible without cable end Control circuit: without connection
Tightening torque
Power circuit: 1.9…2.5 N.m flat screwdriver 6 mm Power circuit: 1.9…2.5 N.m Philips No 2 screwdriver 6 mm Power circuit: 1.9…2.5 N.m pozidriv No 2 screwdriver 6 mm
Width
45 mm
height
224 mm
Depth
126 mm
Net weight
1.27 kg
Compatibility code
LU2B
IP degree of protection
IP20 conforming to IEC 60947-1 (front panel and wired terminals) IP20 conforming to IEC 60947-1 (other faces) IP40 conforming to IEC 60947-1 (front panel outside connection zone)
Protective treatment
TH conforming to IEC 60068
Ambient air temperature for operation
-25…60 °C with LUCM -25…70 °C with LUCA, LUCB, LUCC, LUCD
Ambient air temperature for storage
-40…85 °C
Fire resistance
960 °C parts supporting live components conforming to IEC 60695-2-12 650 °C conforming to IEC 60695-2-12
Operating altitude
2000 m
Shock resistance
10 gn power poles open conforming to IEC 60068-2-27 15 gn power poles closed conforming to IEC 60068-2-27
Vibration resistance
2 gn (f= 5…300 Hz) power poles open conforming to IEC 60068-2-27 4 gn (f= 5…300 Hz) power poles closed conforming to IEC 60068-2-27
Resistance to electrostatic discharge
8 kV level 3 in open air conforming to IEC 61000-4-2 8 kV level 4 on contact conforming to IEC 61000-4-2
Resistance to radiated fields
10 V/m 3 conforming to IEC 61000-4-3
Resistance to fast transients
2 kV class 3 serial link conforming to IEC 61000-4-4 4 kV class 4 all circuits except for serial link conforming to IEC 61000-4-4
Immunity to radioelectric fields
10 V conforming to IEC 61000-4-6
Immunity to microbreaks
3 ms for control circuit
Immunity to voltage dips
70 % / 500 ms conforming to IEC 61000-4-11
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
5.5 cm
Package 1 Width
15.5 cm
Package 1 Length
25.5 cm
Package 1 Weight
1.281 kg
Unit Type of Package 2
S03
Number of Units in Package 2
9
Package 2 Height
30.0 cm
Package 2 Width
30.0 cm
Package 2 Length
40.0 cm
Package 2 Weight
12.062 kg
Warranty
18 months
Datasheet