Pack Quantity
This XPSAXE safety module monitors emergency shutdown pushbuttons and limit switches. It meets the requirements of Performance Level PL e/Category 4 conforming to standard EN/ISO 13849-1 and SILCL3 conforming to EN/IEC 61508 and EN/IEC 62061. It can be used for monitoring emergency stop circuits conforming to standards EN/ISO 13850 and EN/IEC 60204-1. 24V AC/DC supply allows direct supply via an auxiliary transformer, like ABT7 or ABL6, allowing saving at installation time. It has removable terminals for easier and better control wires tightening, thus improving installation reliability.
Range of product
Preventa Safety automation
Product or component type
Preventa safety module
safety module name
XPSAXE
safety module application
For emergency stop and switch monitoring
Safety level
Can reach PL e/category 4 conforming to EN/ISO 13849-1 Can reach SILCL 3 conforming to EN/IEC 62061
Safety reliability data
DC > 99 % conforming to EN/ISO 13849-1 MTTFd = 457 years conforming to EN/ISO 13849-1 PFHd = 3E-8 1/h conforming to EN/IEC 62061
Connections - terminals
Captive screw clamp terminals, removable terminal block, 2 x 0.5...2 x 1.5 mm² flexible with cable end, with double bezel Captive screw clamp terminals, removable terminal block, 1 x 0.2...1 x 2.5 mm² solid without cable end Captive screw clamp terminals, removable terminal block, 1 x 0.2...1 x 2.5 mm² flexible without cable end Captive screw clamp terminals, removable terminal block, 1 x 0.25...1 x 2.5 mm² flexible with cable end, without bezel Captive screw clamp terminals, removable terminal block, 1 x 0.25...1 x 1.5 mm² flexible with cable end, with bezel Captive screw clamp terminals, removable terminal block, 2 x 0.2...2 x 1 mm² solid without cable end Captive screw clamp terminals, removable terminal block, 2 x 0.2...2 x 1 mm² flexible without cable end Captive screw clamp terminals, removable terminal block, 2 x 0.25...2 x 1 mm² flexible with cable end, without bezel
Output type
Relay instantaneous opening, 3 NO circuit(s), volt-free
Number of additional circuits
1 NC
[Us] rated supply voltage
24 V DC - 15...10 % 24 V AC
Synchronisation time between inputs
< 0.5 s
Supply frequency
50/60 Hz
Maximum power consumption in VA
4 VA DC
[Uc] control circuit voltage
24 V DC
Breaking capacity
1.5 A at 24 V (DC-13) time constant: 50 ms for relay output
Output thermal current
6 A for instantaneous and time delay outputs
Associated fuse rating
6 A gG for instantaneous outputs
Minimum output current
10 mA for relay output
Minimum output voltage
17 V for relay output
Maximum response time on input open
80 ms
[Ui] rated insulation voltage
300 V (pollution degree 2) conforming to IEC 60947-5-1 300 V (pollution degree 2) conforming to DIN VDE 0110 part 1
[Uimp] rated impulse withstand voltage
4 kV overvoltage category III conforming to IEC 60947-5-1 4 kV overvoltage category III conforming to DIN VDE 0110 part 1
Local signalling
2 LEDs
Mounting support
35 mm symmetrical DIN rail
Net weight
0.229 kg
Standards
EN/IEC 60947-5-1 EN/IEC 60204-1 EN/ISO 13850 EN 1088/ISO 14119
product certifications
UL BG CSA
IP degree of protection
IP20 conforming to EN/IEC 60529 IP40 conforming to EN/IEC 60529
Ambient air temperature for operation
-25…55 °C
Ambient air temperature for storage
-25…75 °C
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
4.0 cm
Package 1 Width
11.5 cm
Package 1 Length
12.5 cm
Package 1 Weight
211.0 g
Unit Type of Package 2
S02
Number of Units in Package 2
20
Package 2 Height
15 cm
Package 2 Width
30 cm
Package 2 Length
40 cm
Package 2 Weight
4.584 kg
Warranty
18 months