XPSAXE5120C

SAF.MOD.E.STOP.24V AC/ DC

Trade Price

POA

Per

1

Unit

Pack Quantity

XPSAXE5120C

Information

This XPSAXE safety module monitors emergency shutdown pushbuttons and limit switches. It meets the requirements of Performance Level PL e/Category 4 conforming to standard EN/ISO 13849-1 and SILCL3 conforming to EN/IEC 61508 and EN/IEC 62061. It can be used for monitoring emergency stop circuits conforming to standards EN/ISO 13850 and EN/IEC 60204-1. 24V AC/DC supply allows direct supply via an auxiliary transformer, like ABT7 or ABL6, allowing saving at installation time. It has removable terminals for easier and better control wires tightening, thus improving installation reliability. It has spring terminals for fast and reliable wiring of safety circuits.

Technical Specifications

Range of produc

Preventa Safety automation

Product or component type

Preventa safety module

safety module name

XPSAXE

safety module application

For emergency stop and switch monitoring

Safety level

Can reach PL e/category 4 conforming to EN/ISO 13849-1 Can reach SILCL 3 conforming to EN/IEC 62061

Safety reliability data

DC > 99 % conforming to EN/ISO 13849-1 MTTFd = 457 years conforming to EN/ISO 13849-1 PFHd = 3E-8 1/h conforming to EN/IEC 62061

Connections - terminals

Spring terminals, removable terminal block, 1 x 0.2...1 x 2.5 mm² solid without cable end Spring terminals, removable terminal block, 1 x 0.2...1 x 2.5 mm² flexible without cable end Spring terminals, removable terminal block, 1 x 0.25...1 x 2.5 mm² flexible with cable end, without bezel Spring terminals, removable terminal block, 1 x 0.25...1 x 2.5 mm² flexible with cable end, with bezel Spring terminals, removable terminal block, 2 x 0.5...2 x 1 mm² flexible with cable end, with double bezel Spring terminals, removable terminal block

Output type

Relay instantaneous opening, 3 NO circuit(s), volt-free

Number of additional circuits

1 NC

[Us] rated supply voltage

24 V DC - 15...10 % 24 V AC

Synchronisation time between inputs

< 0.5 s

Supply frequency

50/60 Hz

Maximum power consumption in VA

4 VA DC

[Uc] control circuit voltage

24 V DC

Breaking capacity

1.5 A at 24 V (DC-13) time constant: 50 ms for relay output

Output thermal current

6 A for instantaneous and time delay outputs

Associated fuse rating

6 A gG for instantaneous outputs

Minimum output current

10 mA for relay output

Minimum output voltage

17 V for relay output

Maximum response time on input open

80 ms

[Ui] rated insulation voltage

300 V (pollution degree 2) conforming to IEC 60947-5-1 300 V (pollution degree 2) conforming to DIN VDE 0110 part 1

[Uimp] rated impulse withstand voltage

4 kV overvoltage category III conforming to IEC 60947-5-1 4 kV overvoltage category III conforming to DIN VDE 0110 part 1

Local signalling

2 LEDs

mounting support

35 mm symmetrical DIN rail

Net weight

0.229 kg

Standards

EN/ISO 13850 EN 1088/ISO 14119 EN/IEC 60204-1 EN/IEC 60947-5-1

product certifications

BG CSA UL

IP degree of protection

IP20 conforming to EN/IEC 60529 IP40 conforming to EN/IEC 60529

ambient air temperature for operation

-25…55 °C

Ambient air temperature for storage

-25…75 °C

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

4.0 cm

Package 1 Width

11.5 cm

Package 1 Length

12.0 cm

Package 1 Weight

203.0 g

Unit Type of Package 2

S02

Number of Units in Package 2

20

Package 2 Height

15 cm

Package 2 Width

30 cm

Package 2 Length

40 cm

Package 2 Weight

4.376 kg

Warranty

18 months

Document Links

Datasheet